1:7.2 Switching the Boiler Off - temporarily
The Boiler may be stopped by switching the Summer/Off/Winter switch to the OFF position on the standard
Control Panel, or the programmer switch to the OFF position on the optional programmer.
1:7.3 Sealed System Central Heating
Your Camray 5 COMBI Boiler may only be used on a SEALED SYSTEM.
It is important that the correct operating system pressure is maintained. If the System Pressure Gauge, in the
Control Panel, should indicate low pressure i.e. below the marker, contact your Installer.
1:7.4 Frost Protection
If there is any danger that your Boiler may freeze up during severe weather conditions, it is recommended that
you consult your installer who will be able to advise you on an appropriate course of action, either by installing
a frost thermostat or the addition of system anti-freeze.
CAMRAY 5 COMBI PAGE 5
1:7.5 Oil Delivery
Where possible, it is advisable to temporarily switch the Boiler off when your oil supply is being replenished.
This is to allow any sediment to settle and not be drawn into the Boiler. If not this could result in an
inconvenient break down.
We advise that you keep your Boiler off for one hour after the oil is delivered to your tank. Please ask your
supplier, or the driver to notify you before the oil is discharged.
1:8 MAINTENANCE
For normal cleaning of the outside casing, simply wipe with a dry cloth. To remove stubborn marks and stains,
wipe with a damp cloth and finish off with a dry cloth. DO NOT use abrasive cleaning materials.
The Boiler must be serviced at regular intervals by a qualified service engineer. Failure to will invalidate the
guarantee/warranty.
THE BOILER SHOULD BE SERVICED AT TWELVE MONTHLY INTERVALS.
If your boiler has a conventional flue, make sure that air intake entries on the casing panels are never
obstructed. This could lead to premature failure.
1:9 FAILURE TO START
If the Burner fails to start, adopt the following procedure:-
1. Check that there is oil in the tank and that the supply valve is open.
2. Check the programmer or Summer/Winter switch to ensure that it is operating and set to the correct time to
be "ON".
3. Check that the Boiler Control Thermostat is set high enough to be "ON" or calling for heat.
4. Check whether the limit light on the control fascia is glowing, if so it indicates an overheat situation. Press
the reset button once the temperature has dropped sufficiently.
5. Check whether the red LOCKOUT lamp on the Control Panel and Burner Control box are glowing. This
indicates that the Burner has attempted to start but has not fired successfully. Press the reset button on the
Burner Control box, when released, the lights will go out and the Burner will again attempt to start. If the
Pa