CDVI AIOM User manual

AIOM
The installer’s choice
cdvigroup.com
ENGLISH
EN
10-Input/10-Output Module

2cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
Thank you for buying our products and for
the condence you placed in CDVI.
TABLE OF CONTENTS
1] PRODUCT PRESENTATION.........................................................3
2] NOTES AND RECOMMENDATIONS ...................................................4
FCC & IC Compliance ......................................................... 4
UL/ULC Compliance .......................................................... 4
UL 294 Compliance Notice ..................................................... 4
Free Technical Support ........................................................ 4
Recommended Wiring......................................................... 5
Specications .............................................................. 5
3] PACKAGE CONTENTS .............................................................6
Content of the 10-Input/10-Output Module .......................................... 6
Location and Mounting ........................................................ 7
4] MOUNTING INSTRUCTIONS .......................................................8
Installing the Tamper Switches .................................................. 8
Installing the box lock ........................................................ 9
Fixing the Box to its Location .................................................. 10
Installing the 10-Input/10-Output Module PC board ................................... 11
5] WIRING DIAGRAM .............................................................12
Connecting the Box Tamper Switches ............................................. 12
Connecting Inputs .......................................................... 13
Examples of Input Connection Methods ........................................... 14
Connecting Outputs ......................................................... 16
LED Indicators............................................................. 17
Connecting the 10-Input/10-Output Module to the ATRIUM 2-Door Controller ................. 18
6] WARRANTY - TERMS & CONDITIONS ..............................................19
Copyright (C) 2012 CDVI. All rights reserved. ATRIUM Access Control is protected by copyright law and international treaties.
Unauthorized reproduction or distribution of this product, or any portion of it, may result in severe civil and criminal penalties,
and will be prosecuted to the maximum extent possible under law.
All other brand and product names are trademarks or registered trademarks of their respective companies.
The information contained in this publication is subject to change without notice.

3
cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
1] PRODUCT PRESENTATION
The AIOM 10-Input/10-Output Module module supports 10 zone inputs and 10 outputs. It can be connected to
the ATRIUM 2-Door Controller’s, AC22, anywhere on the 1220m (4000ft) 4 conductor RS485 communication
bus. Effortless auto-detect technology identies the AIOM on the communication bus.
• 10 Inputs (20 using zone doubling technology)
• 10 Outputs
• Auto-detect technology
• Up to 100 AIOM module can be
connected to the AC22
• 1220m (4000ft) 4 conductor RS485 expansion bus
(No jumpers or DIP switches)
• Comprehensive LED status indicators

4cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
2] NOTES AND RECOMMENDATIONS
FCC & IC Compliance
This device complies with Part 15 of the FCC rules Class A. Operation is subject to the following two conditions:
(1) this device may not cause harmful interference, and (2) this device must accept any interference received
including interference that may cause undesired operation. This class A digital apparatus meets all requirements
of the Canadian Interference Causing Equipment Regulations. The ATRIUM AIOM 10-Input/10-Output Module is
also compliant with EN55022:1998, amendment 1:1995, Class A.
UL Compliance
To comply with UL listings, the following requirements must be met:
• Use of UL listed readers (Wiegand: 26-bit, 30-bit and 40-bit; mag stripe: up to 32 digits)
• Use of a UL recognized tamper switch on every housing cabinet for the AIOM
• Use only UL listed cables
• Use only UL listed adaptors
Note: All circuits are power limited.
UL 294 Compliance Notice
• Use only UL listed power supply
• Connect CDVI LED status indicator, part number 7020-0001-0000, to the DC Input gray terminals of
the AIOM.
Note: Backup battery provides operation of up to 12 hours but has been tested for 4 hours per
Section 33 of UL 294, fth edition.
The system’s location and wiring methods shall be in accordance with the National Electrical Code,
ANSI/NFPA 70.
Free Technical Support
For technical support in Canada or the U.S., call 1-866-610-0102, Monday to Friday from 8:00 a.m. to 8:00
p.m. EST. For technical support on the International, please see the last page of this document or visit our web-
site: www.cdvigroup.com.

5
cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
Recommended Wiring
Specications
Equipment Wire Type Size Maximum
Length
Zone input and output 2 conductors, copper 22AWG (0.64mm) 22AWG (0.64mm) 600m (2000ft.)
RS485 bus, Star or
Daisy Chain (no BIAS/
EOL required)
CAT 5/5e or 4 pairs 24AWG (0.51mm)
1220m (4000ft.)
4 conductors, copper 26AWG (0.40mm) to
18AWG (1.02 mm)
System Resources
Operating Temperature -20°C to +70°C (-4°F to +158°F)
Humidity 0% to 85% (non condensing)
System Autonomy Full Distributed Architecture (100% Off-line Operation)
Firmware Online Upgradeable
PCB Dimensions 19.5cm (7.68”) x 8.9 cm (3.5”)
Cabinet Dimensions 29 cm (11.4”) high, 28 cm (11”) wide, 8 cm (3.15”) deep
Inputs
Multi-Purpose Inputs 10 zone inputs (up to 20 using ZONE DOUBLER) with optional individual WIRE CUT &
WIRE SHORT supervision.
Smoke Detector Future use
Box Tamper Normally Closed (N.C.) contact
Outputs
Multi-Purpose Outputs 10 outputs open collector 100mA
Communication
LOCAL BUS RS485 @ 57600Baud supporting star and/or daisy chain topologies up to 4000ft (1220 meters)

6cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
3] PACKAGE CONTENTS
This chapter details how to install and setup the ATRIUM 10-Input/10-Output Module.
Content of the 10-Input/10-Output Module
The 10-Input/10-Output Module contains:
• One 10-Input/10-Output Module module in its cabinet with connection diagram label
• Metal Box kit:
• Installation kit:
If any item is missing, please notify your distributor immediately.
Wall Switch
and a white
wire (115mm)
with a log at
each end
Bolts and Nuts Wall Switch
Spacer
Door Switch
and 2 white
wire (350mm)
with a log at
one end
Door Switch
Support
Metal box
screw
Metal box
lock and key
Metal Box Kit 1211141
1K Resistor 2.2K Resistor Fastener
(PCB Holder)
Installation
Kit 21 10 5

7
cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
Location and Mounting
The cabinet is designed to be installed indoors, in a safe and secure location. Suggested locations include
electrical rooms, communication equipment rooms, closets or in the ceiling. To save time, wiring and facilitate
testing, install the cabinets at an equal distance between its controlled doors. Normal temperature and humidity
levels should be maintained.
Cabinet Dimensions:
29 cm (11.4”) high, 28 cm (11”) wide, 8 cm (3.15”) deep
Multiple Conduit Knock-outs:
Two 19.05mm (0.75”) on each side and one 12.7mm (0.5”) on top
Minimum Clearance For Cabinet:
25cm (10”) clear space around all sides
38cm (15”) clear space in front of cabinet
Minimum Clearance From Electrical Interference:
2.4m (8ft.) from high voltage equipment or wiring and from electrical equipment likely to generate
interference
1.2m (4ft.) from telephone equipment or lines and 8m (25ft.) from transmitting equipment
The system’s location and wiring methods shall be in accordance with the National Electrical Code,
ANSI/NFPA 70.

8cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
4] MOUNTING INSTRUCTIONS
Cabinet Side View
Cabinet Door
Nut
Spacer
Spacer
Screw
Spacer
Install the wall tamper switch using the supplied bolts and nuts as shown in the following picture.
Install the tamper switch
plastic spacer on the
back at bottom left side of
the box as show in
the following picture.

9
cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
Fix the tamper switch to
the bracket then mount
the bracket on the
mounting flange
Door
Tamper Switch
Bracket
Door Tamper Switch
Mounting Flange
Install the door tamper switch by aligning the switch holes to the pre-installed plastic bracket pins. Press rmly
to secure the tamper switch in position, then x the bracket to is mounting ange.
Refer to page <?> for wiring diagram.

10 cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
Installing the box lock
Installing the box lock allows to secure the box from non
authorized access. If needed install the box lock as shown
in the following picture.
1. Remove the box door knock-out.
2. Insert the lock in the hole.
3. Slide the “U” metal part into the lock groove.
Alternatively or complementary to the box lock,
the box may be secured by xing the cover to
its base using screws.
However this should be done only once the
installation of the 10-Input/10-Output Module
system is completed.
1. Use the 4 screws supplied to secure
the box cover to its base as shown
in the following picture.

11
cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
Fixing the Box to its Location
Install the box to its location using 4 screws (not supplied) as shown in the following picture.
If the wall tamper switch is used, make sure that the tamper switch arm moves freely and is
completely pushed in when the enclosure is installed on the wall.

12 cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
Installing the 10-Input/10-Output Module PC board
Install the 5 fasteners (PCB holder) supplied respectively to the box holes identied in red in the following
picture.
INPUTS INPUTS OUTPUTS OUTPUTS
TMP/SMOKE LOCAL BUS
AIOM
Input / Output Module

13 cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
5] WIRING DIAGRAM
Connecting the Box Tamper Switches
Connecting the tamper switches allows the AIOM Module to detect when the cabinet door is opened and/or
when the cabinet is removed from the wall. To install the tamper switches, see “Installing the Tamper Switches”.
To use both switches:
1. Connect one end of the supplied wire, the one with a log at each end, to the door tamper switch
terminal and the other end to the wall tamper switch terminal.
2. Connect the other terminal of the door tamper switch to the “TMP” terminals using the supplied wire.
3. Connect the other terminal of the wall tamper switch to the “GND” terminals using the supplied wire.
To use only one switch:
1. Connect one terminal of the tamper switch to the “TMP” terminals using the supplied wire.
2. Connect the other terminal of the same tamper switch to the “GND” terminals using the supplied wire.
If you do not use the tamper switch, connect a wire between the “TMP” and “GND” terminals.
INPUTS INPUTS OUTPUTS OUTPUTS
TMP/SMOKE LOCAL BUS
Metal Box
Door Tamper Switch
(N.C.)
Metal Box
Wall Tamper Switch
(N.C.)
AIOM
Input / Output Module

14
cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
Connecting Inputs
The 10-Input/10-Output Module can monitor the state of up to 20 devices (using zone doubling) such as
magnetic contacts, motion detectors, temperature sensors, or other devices. The following are examples of the
type of inputs that can be monitored:
Magnetic Door Contact:
Permits supervision of door “status” (opened, closed). When using the default system settings, you
can easily swap terminals to troubleshoot the installation.
INPUTS INPUTS OUTPUTS
OUTPUTS
TMP/SMOKE LOCAL BUS
AIOM
Input / Output Module
Input 6
(1K Ohm)
OPTIONAL LOOP
SUPERVISION
1K Ohm
EOL
Input 16
(2.2K Ohm)
Input 1
Single Zone Setting
(Factory Default Settings)
Zone Doubling Settings
(Optional)
10 Zone Inputs
(20 with zone doubling)
See “Recommended Wiring” for more information on wiring type, size, and maximum length.

15 cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
Examples of Input Connection Methods
Single without EOL and without TAMPER Supervision
(Limit of 1 Detection Device on the Input)
When using this method, only one device can be connected to the
input. The input must be connected using only one Contact (NO
or NC: programmable per INPUT in Software) as described in the
following gure. This setup will not support WIRE CUT or WIRE SHORT
supervision, but will generate an alarm condition when the state of
the input is breached.
WIRE SHORT supervision: NO
WIRE CUT supervision: NO
Single with WIRE SHORT Supervision
(Limit of 1 Detection Device on the Input)
When using this method, only one device can be connected to the
input. The input must be connected using only one Contact (NO
or NC: programmable per INPUT in Software) as described in the
following gure. This setup will not support WIRE CUT supervision but
offers WIRE SHORT supervision and will generate an alarm condition
when the state of the input is breached.
WIRE SHORT supervision: YES (Detected as INPUT SHORT)
WIRE CUT supervision: NO
Single with WIRE CUT Supervision
(Limit of 1 Detection Device on the Input)
When using this method, only one device can be connected to the
input. The input must be connected using only one Contact (NO
or NC: programmable per INPUT in Software) as described in the
following gure. This setup will support WIRE CUT supervision but
will not offer WIRE SHORT supervision and will generate an alarm
condition when the state of the input is breached.
WIRE SHORT supervision: NO
WIRE CUT supervision: YES (Detected as INPUT CUT)
Input 1
12V Z1 GND Z2 Z3 GND Z4 Z5
INPUTS
1K Tamper Input 1
Input 1
12V Z1 GND Z2 Z3 GND Z4 Z5
INPUTS
Input 1
1K
EOL
12V Z1 GND Z2 Z3 GND Z4 Z5
INPUTS
1K
Input 1
12V Z1 GND Z2 Z3 GND Z4 Z5
INPUTS

16
cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
Single with WIRE SHORT and WIRE CUT Supervision
(Limit of 1 Detection Device on the Input)
When using this method, only one device can be connected to the
input. The input must be connected using only one Contact (NO or NC:
programmable per INPUT in Software) as described in the following
gure. This setup will support both WIRE CUT and WIRE SHORT
supervision and will generate an alarm condition when the state of the
input is breached.
WIRE SHORT supervision: YES (Detected as INPUT SHORT)
WIRE CUT supervision: YES (Detected as INPUT CUT)
Doubled with WIRE CUT Supervision
(2 Detection Device on the Input)
When using this method, two device can be
connected to the input. The input must be
connected using two Contacts (NO or NC:
programmable per INPUT in Software) as
described in the following gure. This setup
will support WIRE CUT supervision but not
WIRE SHORT supervision and will generate an
alarm condition when the state of one of the
input is breached.
WIRE SHORT supervision: NO
WIRE CUT supervision: YES (Detected as
INPUTS CUT)
Doubled with WIRE SHORT and WIRE CUT Supervision
(2 Detection Device on the Input)
When using this method, two device can be connected to the input. The
input must be connected using two Contacts (NO or NC: programmable
per INPUT in Software) as described in the following gure. This setup
will support WIRE CUT and WIRE SHORT supervision and will generate an
alarm condition when the state of one of the
input is breached.
WIRE SHORT supervision: YES
(Detected as INPUTS SHORT)
WIRE CUT supervision: YES
(Detected as INPUTS CUT)
1K
EOL
1K Tamper Input 1
Input 1
12V Z1 GND Z2 Z3 GND Z4 Z5
INPUTS
1K 2.2KTamper Input 1 Tamper Input 11
Input 1 Input 11
12V Z1 GND Z2 Z3 GND Z4 Z5
INPUTS
Detection device #1 Detection device #2
1K
1K
EOL
2.2KTamper Input 1 Tamper Input 11
Input 1 Input 11
12V Z1 GND Z2 Z3 GND Z4 Z5
INPUTS
Detection device #1 Detection device #2

17 cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
Connecting Outputs
The ATRIUM 10-Input/10-Output Module can control up to 10 devices such as garage doors, lights, air
conditioning, heating systems, blinds, pumps, locks, etc. Devices requiring/using 100mA or less @ 12Vdc may
be directly connected to the outputs. Outputs can be congured as normally open (deactivated) or normally
closed (activated); refer to the ATRIUM instruction manual for more information.
INPUTS
INPUTS OUTPUTS OUTPUTS
TMP/SMOKE
LOCAL BUS
AIOM
Input / Output Module
RELAY
DeviceAC or DC
Source
NC NO
C
Example of Devices:
- Garage Door
- Lights
- Air conditioning
- Heating System
- Blinds
- Pump
- Locks
See “Recommended Wiring” for more information on wiring type, size, and maximum length.

18
cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
LED Indicators
The ATRIUM 10-Input/10-Output Module has several status LEDs that are very useful to diagnose problems
when using or installing the ATRIUM system. Refer to the following picture for the emplacement of those LEDs
on the ATRIUM 10-Input/10-Output Module. All LEDs are explained in the following pages.
INPUTS INPUTS OUTPUTS OUTPUTS
TMP/SMOKE LOCAL BUS
AIOM
Input / Output Module
2
3
1
1
GLOBAL STAT Flash once per second: Firmware is operating normally.
Flash rapidly: Firmware is upgrading.
Inputs
IN1 to IN10
Green LED: Input breached
Off LED: Input normal (OK)
Green LED ashing: Input in trouble (wire cut or wire short).
2OUTPUTS OUT1 to OUT10 Green LED: Output activated.
Off LED: Output not activated.
3LOCAL BUS RX Green LED ashing: Data received on local bus.
TX Green LED ashing: Data transmitted on local bus.

19 cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
Connecting the 10-Input/10-Output Module to
the ATRIUM 2-Door Controller
The 10-Input/10-Output Module has a RS485 LOCAL BUS terminal allowing the connection with the ATRIUM
2-Door Controller, up to 1220m (4000ft). Connect the module’s to the ATRIUM 2-Door Controller’s LOCAL BUS
using Bus, star and/or daisy chain topologies. For example:
cdvigroup.com
cdvigroup.com
cdvigroup.com
cdvigroup.com
cdvigroup.com
AC22
AIOM AIOM AIOM AIOM
cdvigroup.com
cdvigroup.com
cdvigroup.com
cdvigroup.com
cdvigroup.com
AC22
AIOM
AIOM
AIOM
AIOM
cdvigroup.com
cdvigroup.com cdvigroup.com cdvigroup.com
cdvigroup.com
AC22
AIOM AIOM AIOM AIOM
cdvigroup.com
cdvigroup.com
cdvigroup.com
cdvigroup.com
cdvigroup.com
AC22
AIOM
AIOM
AIOM
AIOM
DAISY CHAIN
BUS
MIXED
DAISY CHAIN/BUS/STAR
STAR

20
cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
7] Warranty - Terms & Conditions
The “5 Year Warranty” is offered by CDVI exclusively for CDVI products featuring the logo “5 Year Warranty”,
and supplied by authorized CDVI dealers participating in the offer. You can obtain the address of the local
authorized dealer participating in the offer by contacting CDVI or a local CDVI subsidiary. The “5 Year Warranty”
is only applicable to hidden defects detected during the lifetime of the product, as dened by the CDVI Group (5
years or 200 000 operations - whichever of the two expires rst).
The “5 Year Warranty” conditions shall not modify the sales conditions between CDVI and its customers.
DURATION OF THE OFFER:
• This offer is valid from July 1st 2010; CDVI reserves the right to terminate this offer without prior
notice.
• However, any product already registered up to the date of withdrawal of the offer will remain
eligible for the “5 Year Warranty”.
• The warranty applies only to the available products mentioned in the above statement.
CONDITIONS :
• Hidden defects are guaranteed for an unlimited shelf life (period of time before use).
• To be eligible for the “5 Year Warranty”, the product must be registered at CDVI within one month
of its delivery to the end user, by completing in and returning back the “warranty” form by fax,
email or post to the local CDVI subsidiary. This information may also be registered on line at www.
cdvigroup.com.
• Only the issue of the “5 Year Warranty” certicate by CDVI can conrm product registration; CDVI
may not be held responsible in the event of loss or non-presentation of the form.
• The “5 Year Warranty” only applies to products installed by a skilled and experienced personal
with the necessary trade qualications to install according to the highest standards, respecting
the standards, instructions and guidelines dened by CDVI and according to the maximum
recommended specications.
• To enable CDVI to determine whether a product is eligible to claim for the “5 Year Warranty”,
after prior issue of a return of materials authorization number (RMA) by CDVI, the customer must
return the product and all of its accessories in the original packaging with a copy of its invoice. The
transport fees shall be paid by the customer and the package must be returned to CDVI or to a
CDVI authorized repair centre.
• Eligibility for the “5 Year Warranty” cover must be conrmed by CDVI.
• The “5 Year Warranty” only covers the replacement or repair of the parts acknowledged as faulty by
CDVI.
• CDVI reserves the right to respect its obligation by replacing the product or the parts acknowledged
as faulty by a standard part replacement or by a product or new parts, or by an updated or
improved version of the product with identical or similar functionalities.
• In respect of the applicable law, CDVI cannot be held responsible for material or immaterial
damages caused to goods or to third parties and as a direct or indirect result of the installation,
utilization, product faults or poor functioning of a device.
• The “5 Year Warranty” is non-assignable and non-transferrable; only the person who registered the
aforementioned warranty may benet from the warranty.
• The “5 Year Warranty” is limited to the eligible product and is strictly limited to the conditions in
effect on the date of purchase by the customer.
Table of contents