manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Comfortmaker
  6. •
  7. Furnace
  8. •
  9. Comfortmaker F80CTL Guide

Comfortmaker F80CTL Guide

Installation, Start–Up, Operating and
Service and Maintenance Instructions
NOTE: Read the entire instruction manual before starting the
installation.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 1 – Minimum Free Area Required for Each Combustion Air
opening of Duct to Outdoors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Table 2 – Minimum Space Volumes for 100% Combustion, Ventila-
tion, and Dilution from Indoors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Table 3 – Opening Dimensions - In. (mm). . . . . . . . . . . . . . . . . . . . 10
AIR DUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
GAS PIPING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 4 – Maximum Capacity of Pipe . . . . . . . . . . . . . . . . . . . . . . . 14
ELECTRICAL CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 5 – Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
VENTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 6 – Minimum Allowable Input Rating of
Space-Heating Appliance in Thousands of Btuh per Hour. . . . . . . . 21
Table 7 – Combined Appliance Maximum Input Rating
in Thousands of Btuh per Hour. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 8 – Recommended Minimum Vent Height Per Furnace and Vent
Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
START-UP, ADJUSTMENT, AND SAFETY CHECK . . . . . . . . . . . 25
Table 9 – Altitude Derate Multiplier for U.S.A.. . . . . . . . . . . . . . . . 26
Table 10 – Gas Rate (CU ft./hr) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 11 – Blower Off Delay Setup Switch . . . . . . . . . . . . . . . . . . . 28
Table 12 – Cooling Airflow Adjustments from 1.5 to 6 Tons . . . . . 29
Table 13 – Air Delivery - CFM (With Filter). . . . . . . . . . . . . . . . . . 30
Table 14 – Furnace Setup Switch Description . . . . . . . . . . . . . . . . . 34
Table 15 – Orifice Size and Manifold Pressure (In. W.C.) for Gas Input
Rate (Tabulated Data Based on 22,000 Btuh High-Heat/14,500 Btuh
for Low-Heat per Burner, Derated 4 Percent for Each 1000 Ft. (305 M)
Above Sea Level) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 16 – Orifice Size and Manifold Pressure (In. W.C.) for Gas Input
Rate (Tabulated Data Based on 21,000 Btuh High-Heat/14,500 Btuh
for Low-Heat Per Burner, Derated 4 Percent for Each 1000 Ft. (305 M)
Above Sea level). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
SERVICE AND MAINTENANCE PROCEDURES. . . . . . . . . . . . . . 37
Table 17 – Filter Size Information - In. (mm) . . . . . . . . . . . . . . . . . 39
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
PARTS REPLACEMENT INFORMATION GUIDE . . . . . . . . . . . . . 48
EXAMPLE OF MODEL NUMBER . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Most states in the USA an jurisdictions in Canada have laws that require
the use of Carbon Monoxide (CO) alarms with fuel burning products.
Examples of fuel burning products are furnaces, boilers, space heaters,
generators, water heaters, stoves/ranges, clothes dryers, fireplaces,
incinerators, automobiles, and other internal combustion engines. Even
if there are no laws in your jurisdiction requiring a CO Alarm, it’s highly
recommended that whenever any fuel burning product is used in or
around the home or business that the dwelling be equipped with a CO
Alarm(s). The Consumer Product Safety Commission recommends the
use of CO Alarm(s). The CO Alarm(s) must be installed, operated, and
maintained according to the CO Alarm manufacturer’s instructions. For
more information about Carbon Monoxide, local laws, or to purchase a
CO Alarm online, please visit the following website.
https://www.kidde.com.
A200115
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1E, with permission of National Fire Protection Association, Quincy, MA
02269 and American Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI
on the referenced subject, which is represented only by the standard in its entirety.
F80CTL & G80CTL
80% AFUE, Two-Stage, Variable–Speed
4–Way Multipoise Gas Furnace
(Series A)
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury and/or
death.
Carbon Monoxide (CO) is a colorless, odorless, and tasteless poisonous
gas that can be fatal when inhaled. Follow all installation, maintenance,
and service instructions. See additional information below regarding
the installation of a CO Alarm.
Use of the AHRI Certified TM Mark indicates
a manufacturer’s participation in the program.
For verification of certification for individual
products, go to www.ahridirectory.org .
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
2
A190045
Fig. 1 – Dimensional Drawing
FURNACE SIZE
A
CABINET WIDTH
B
OUTLET WIDTH
C
TOP AND
BOTTOM FLUE
COLLAR
D
BOTTOM
INLET WIDTH
VENT
CONNECTION
SIZE
SHIP WT.
LB (KG)
0451712 17-1/2 (445) 15-7/8 (403) 11-9/16 (294) 16 (406) 4 (102) 118 (53.5)
0701412 14-3/16 (360) 12-9/16 (319) 9-5/16 (237) 12-11/16 (322) 4 (102) 118 (53.5)
0701716 17-1/2 (445) 15-7/8 (403) 11-9/16 (294) 16 (406) 4 (102) 126 (57.1)
0702120 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 147 (66.7)
0901716 17-1/2 (445) 15-7/8 (403) 11-9/16 (294) 16 (406) 4 (102) 134 (60.8)
0902120 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 153 (69.4)
1102120 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 156 (70.7)
1352422 24-1/2 (622) 22-7/8 (581) 15-1/16 (383) 23 (584) 4 (102)*
*. 135 size furnace require a 5 or 6-in. (127 or 152 mm) vent. Use a vent adapter between furnace and vent stack. See Installation Instructions for complete installation
requirements.
169 (76.6)
U.S. ECCN: Not Subject to Regulation (N.S.R.)
SD5523-4 REV. B
NOTE: ALL DIMENSIONS IN INCH (MM)
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
3
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to gas
and electrical components. Only trained and qualified personnel should
install, repair, or service heating equipment. Untrained personnel can
perform basic maintenance functions such as cleaning and replacing air
filters. All other operations must be performed by trained service
personnel. When working on heating equipment, observe precautions in
literature, on tags, and on labels attached to or shipped with furnace and
other safety precautions that may apply.
These instructions cover minimum requirements and conform to existing
national standards and safety codes. In some instances, these instructions
exceed certain local codes and ordinances, especially those that may not
have kept up with changing residential construction practices. We
require these instructions as a minimum for a safe installation.
Wear safety glasses, protective clothing and work gloves. Have fire
extinguisher available during start-up and adjustment procedures and
service calls.
This is the safety-alert symbol . When you see this symbol on the
furnace and in instructions or manuals, be alert to the potential for
personal injury.
Understand the signal words DANGER, WARNING, and CAUTION.
These words are used with the safety-alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury or
death. WARNING signifies a hazard which could result in personal
injury or death. CAUTION is used to identify hazards which may result
in minor personal injury or product and property damage. NOTE is used
to highlight suggestions which will result in enhanced installation,
reliability, or operation.
The following additional safety considerations should be followed for
gas furnaces:
1. Use only with type of gas approved for this furnace. Refer to the
furnace rating plate.
2. Install this furnace only in a location and position as specified in the
“Location” section of these instructions.
3. Provide adequate combustion and ventilation air to the furnace
space as specified in “Air for Combustion and Ventilation” section.
4. Combustion products must be discharged outdoors. Connect this
furnace to an approved vent system only, as specified in the
“Venting” section of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of leaks
to check all connections, as specified in the “Gas Piping” section.
6. Always install furnace to operate within the furnace’s intended
temperature-rise range with a duct system which has an external
static pressure within the allowable range, as specified in the
“Start-Up, Adjustments, and Safety Check” section. See furnace
rating plate.
7. When a furnace is installed so that supply ducts carry air circulated
by the furnace to areas outside the space containing the furnace, the
return air shall also be handled by duct(s) sealed to the furnace
casing and terminating outside the space containing the furnace.
See “Air Ducts” section.
8. A gas-fired furnace for installation in a residential garage must be
installed as specified in the warning box in the “Location” section.
9. The furnace may be used for construction heat provided that the
furnace installation and operation complies with the first
CAUTION in the LOCATION section of these instructions.
10. These Multipoise Gas-Fired Furnaces are CSA (formerly A.G.A.
and C.G.A.) design-certified for use with natural and propane gases
(see furnace rating plate) and for installation in alcoves, attics,
basements, closets, utility rooms, crawlspaces, and garages. The
furnace is factory-shipped for use with natural gas. A CSA (A.G.A.
and C.G.A.) listed accessory gas conversion kit is required to
convert furnace for use with propane gas.
11. See Fig. 2 for required clearances to combustible construction.
12. Maintain a 1-in. (25 mm) clearance from combustible materials to
supply air ductwork for a distance of 36 in. (914 mm) horizontally
from the furnace. See NFPA 90B or local code for further
requirements.
13. These furnaces SHALL NOT be installed directly on carpeting, tile,
or any other combustible material other than wood flooring. In
downflow installations, factory accessory floor base MUST be used
when installed on combustible materials and wood flooring. Special
base is not required when this furnace is installed on manufacturer’s
Coil Assembly Part No. END4X, ENW4X or coil casing model
number NAEA. See Fig. 2 for clearance to combustible
construction information.
WARNING
!
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation,
personal injury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or
use can cause carbon monoxide poisoning, explosion, fire, electrical
shock, or other conditions which may cause personal injury or property
damage. Consult a qualified service agency, local gas supplier, or your
distributor or branch for information or assistance. The qualified
service agency must use only factory-authorized and listed kits or
accessories when modifying this product.
CAUTION
!
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit component damage.
Application of this furnace should be indoors with special attention
given to vent sizing and material, gas input rate, air temperature rise,
unit leveling, and unit sizing.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear
appropriate protective clothing, safety glasses and gloves when
handling parts, and servicing furnaces.
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
INTRODUCTION
A10269
Fig. 2 – Clearances to Combustibles
The 4-way multipoise Category I fan-assisted furnace is CSA (formerly
A.G.A. and C.G.A.) design-certified. A Category I fan-assisted furnace is
an appliance equipped with an integral mechanical means to either draw
or force products of combustion through the combustion chamber and/or
heat exchanger. The furnace is factory-shipped for use with natural gas.
This furnace is not approved for installation in mobile homes,
recreational vehicles, or outdoors.
This furnace is designed for minimum continuous return-air temperature
of 60°F (15°C) db or intermittent operation down to 55°F (13°C)db such
as when used with a night setback thermostat. Return-air temperature
must not exceed 80°F (27°C) db. Failure to follow these return-air
temperature limits may affect reliability of heat exchangers, motors, and
controls, see Fig. 3.
For accessory installation details, refer to the applicable instruction
literature.
NOTE: Remove all shipping brackets and materials before operating the
furnace.
A06745
Fig. 3 – Return Air Temperature
A02054
Fig. 4 – Prohibit Installation on Back
A93044
Fig. 5 – Installation in a Garage
CODES AND STANDARDS
Follow all national and local codes and standards in addition to these
instructions. The installation must comply with regulations of the
serving gas supplier, local building, heating, plumbing, and other codes.
In absence of local codes, the installation must comply with the national
codes listed below and all authorities having jurisdiction.
In the United States, follow all codes and standards for the following:
Safety
NFPA 54/ANSI Z223.1 and the Installation Standards, Warm Air
Heating and Air Conditioning Systems ANSI/NFPA 90B.
General Installation
Current edition of the NFGC and the NFPA 90B. For copies, contact the
National Fire Protection Association Inc., Batterymarch Park, Quincy,
MA 02269; (www.NFPA.org) or for only the NFGC, contact the
American Gas Association, 400 N. Capitol Street, N.W., Washington,
DC 20001 (www.AGA.org.).
Combustion and Ventilation Air
Section 9.3 NFPA 54/ANSI Z223.1, Air for Combustion and Ventilation.
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death
and/or property damage.
Do not install the furnace on its back or hang furnace with control
compartment facing downward. Safety control operation will be
adversely affected. Never connect return-air ducts to the back of the
furnace, see Fig. 4.
60
80 / 27 C
/ 16 C
WARNING
!
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal injury, death
and/or property damage.
When the furnace is installed in a residential garage, the burners and
ignition sources must be located at least 18 in. (457 mm) above the
floor. The furnace must be located or protected to avoid damage by
vehicles. When the furnace is installed in a public garage, airplane
hangar, or other building having a hazardous atmosphere, the furnace
must be installed in accordance with the NFPA 54/ANSI Z223.1, see
Fig. 5.
18-IN. (457.2 mm)
MINIMUM TO BURNERS
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
5
Duct Systems
Air Conditioning Contractors Association (ACCA) Manual D, Sheet
Metal and Air Conditioning Contractors National Association
(SMACNA), or American Society of Heating, Refrigeration, and Air
Conditioning Engineers (ASHRAE) 2001 Fundamentals Handbook
Chapter 34 or 2000 HVAC Systems and Equipment Handbook Chapters
9 and 16.
Acoustical Lining and Fibrous Glass Duct
Current edition of SMACNA and NFPA 90B as tested by UL Standard
181 for Class I Rigid Air Ducts.
Gas Piping and Gas Pipe Pressure Testing
NFPA 54/ANSI Z223.1; Chapters 5, 6, and 7 and National Plumbing
Codes.
Electrical Connections
National Electrical Code (NEC) ANSI/NFPA70.
Venting
NFPA 54/ANSI Z223.1; Chapters 12 and 13.
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
1. Disconnect all power to the furnace. Multiple disconnects may be
required. DO NOT TOUCH THE CONTROL OR ANY WIRE
CONNECTED TO THE CONTROL PRIOR TO DISCHARGING
YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the furnace
chassis which is close to the control. Tools held in a person’s hand
during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the control
or connecting wires as long as you do nothing to recharge your
body with static electricity (for example; DO NOT move or shuffle
your feet, do not touch ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with
static electricity), firmly touch a clean, unpainted metal surface of
the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded)
furnaces.
6. Before removing a new control from its container, discharge your
body’s electrostatic charge to ground to protect the control from
damage. If the control is to be installed in a furnace, follow items 1
through 4 before bringing the control or yourself in contact with the
furnace. Put all used and new controls into containers before
touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also
be used to prevent ESD damage. LOCATION
GENERAL
This multipoise furnace is shipped in packaged configuration. Some
assembly and modifications are required when used in any of four
applications, see in Fig. 6.
CAUTION
!
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit component damage.
Electrostatic discharge can affect electronic components. Take
precautions during furnace installation and servicing to protect the
furnace electronic control. Precautions will prevent electrostatic
discharges from personnel and hand tools which are held during the
procedure. These precautions will help to avoid exposing the control to
electrostatic discharge by putting the furnace, the control, and the
person at the same electrostatic potential.
CAUTION
!
PERSONAL INJURY AND/OR PROPERTY
DAMAGE HAZARD
Improper use or installation of this furnace may result in premature
furnace component failure. This gas furnace may be used for heating
buildings under construction provided that:
– The furnace is permanently installed with all electrical wiring, piping,
venting and ducting installed according to these installation
instructions. A return air duct is provided, sealed to the furnace casing,
and terminated outside the space containing the furnace. This prevents
a negative pressure condition as created by the circulating air blower,
causing a flame rollout and/or drawing combustion products into the
structure.
– The furnace is controlled by a thermostat. It may not be “hot wired”
to provide heat continuously to the structure without thermostatic
control.
– Clean outside air is provided for combustion. This is to minimize the
corrosive effects of adhesives, sealers and other construction materials.
It also prevents the entrainment of drywall dust into combustion air,
which can cause fouling and plugging of furnace components.
– The temperature of the return air to the furnace is maintained between
55°F (13°C) and 80°F (27°C), with no evening setback or shutdown.
The use of the furnace while the structure is under construction is
deemed to be intermittent operation per our installation instructions.
– The air temperature rise is within the rated rise range on the furnace
rating plate, and the gas input rate has been set to the nameplate value.
– The filters used to clean the circulating air during the construction
process must be either changed or thoroughly cleaned prior to
occupancy.
– The furnace, ductwork and filters are cleaned as necessary to remove
drywall dust and construction debris from all HVAC system
components after construction is completed.
– Verify proper furnace operating conditions including ignition, gas
input rate, air temperature rise, and venting according to these
installation instructions.
WARNING
!
CARBON MONOXIDE POISONING / COMPONENT
DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death
and unit component damage.
Corrosive or contaminated air may cause failure of parts containing flue
gas, which could leak into the living space. Air for combustion must not
be contaminated by halogen compounds, which include fluoride,
chloride, bromide, and iodide. These elements can corrode heat
exchangers and shorten furnace life. Air contaminants are found in
aerosol sprays, detergents, bleaches, cleaning solvents, salts, air
fresheners, and other household products. Do not install furnace in a
corrosive or contaminated atmosphere. Make sure all combustion and
circulating air requirements are met, in addition to all local codes and
ordinances.
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
6
A02097
Fig. 6 – Multipoise Orientations
NOTE: For high-altitude installations, the high-altitude conversion kit
MUST be installed at or above 5500 ft. (1676 M) above sea level. Obtain
high-altitude conversion kit from your area authorized distributor.
This furnace must:
• be installed so the electrical components are protected from water.
• not be installed directly on any combustible material other than
wood flooring (refer to SAFETY CONSIDERATIONS).
• be located close to the chimney or vent and attached to an air
distribution system. Refer to Air Ducts section.
• be provided ample space for servicing and cleaning. Always
comply with minimum fire protection clearances shown on the
furnace clearance to combustible construction label.
The following types of furnace installations may require OUTDOOR
AIR for combustion due to chemical exposures:
• Commercial buildings
• Buildings with indoor pools
• Laundry rooms
• Hobby or craft rooms, and
• Chemical storage areas
If air is exposed to the following substances, it should not be used for
combustion air, and outdoor air may be required for combustion:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine based swimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry acid washing materials
All fuel-burning equipment must be supplied with air for fuel
combustion. Sufficient air must be provided to avoid negative pressure
in the equipment room or space. A positive seal must be made between
the furnace cabinet and the return-air duct to prevent pulling air from the
burner area and from draft safeguard opening.
AIR FOR COMBUSTION AND VENTILATION
Provisions for adequate combustion, ventilation, and dilution air must be
provided in accordance with:
• U.S. Installations: Section 9.3 of the NFPA 54/ANSI Z223.1, Air
for Combustion and Ventilation and applicable provisions of the
local building codes.
The requirements for combustion and ventilation air depend upon
whether or not the furnace is located in a space having a volume of at
least 50 cubic feet per 1,000 Btuh input rating for all gas appliances
installed in the space.
• Spaces having less than 50 cubic feet per 1,000 Btuh require the
OUTDOOR COMBUSTION AIR METHOD.
• Spaces having at least 50 cubic feet per 1,000 Btuh may use the
INDOOR COMBUSTION AIR, STANDARD or KNOWN AIR
INFILTRATION METHOD.
Minimum dimensions of 3-in. (76 mm).
NOTE: Use any of the following combinations of openings:
A & B C & D D & E F & G
A03174
Fig. 7 – Air for Combustion, Ventilation, and Dilution for Outdoors
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper combustion,
ventilation, and dilution of flue gases using permanent horizontal or
vertical duct(s) or opening(s) directly communicating with the
outdoors or spaces that freely communicate with the outdoors.
2. Fig. 7 illustrates how to provide TWO OUTDOOR OPENINGS,
one inlet and one outlet combustion and ventilation air opening, to
the outdoors.
a. One opening MUST commence within 12 in. (300 mm) of the
ceiling and the second opening MUST commence within 12 in.
(300 mm) of the floor.
CAUTION
!
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage.
Air for combustion must not be contaminated by halogen compounds,
which include fluoride, chloride, bromide, and iodide. These elements
can corrode heat exchangers and shorten furnace life. Air contaminants
are found in aerosol sprays, detergents, bleaches, cleaning solvents,
salts, air fresheners, and other household products.
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT. WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers,
attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE
CONDITION at the furnace. Make-up air MUST be provided for the
ventilation devices, in addition to that required by the furnace. Refer to
the Carbon Monoxide Poisoning Hazard warning in the venting section
of these instructions to determine if an adequate amount of make-up air
is available.
1 SQ IN.
PER
4000
BTUH*
DUCTS
TO
OUTDOORS
1 SQ IN.
PER 4000
BTUH*
CIRCULATING
AIR DUCTS
VENT
THROUGH
ROOF
D
B
A
C
E
1 SQ IN.
PER 4000
BTUH*
DUCT
TO
OUTDOORS
CIRCULATING AIR DUCTS
1 SQ IN.
PER 2000
BTUH*
1 SQ IN.
PER 2000
BTUH*
DUCTS
TO
OUTDOORS
12″MAX
12″MAX
12″MAX
12″
MAX
12″
MAX
OUTDOORS
1 SQ IN.
PER
4000
BTUH*
F
G
CLEARANCE IN FRONT
OF COMBUSTION AIR
OPENINGS SHALL BE
AT LEAST 3 IN.
(305mm)
(305mm)
(305mm)
(305mm)
(305mm)
(76mm)
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7
b. Size openings and ducts per Fig. 7 and Table 1.
c. TWO HORIZONTAL DUCTS require 1 sq. in. (645 sq. mm) of
free area per 2,000 Btuh (1,100 mm2/kW) of combined input for
all gas appliances in the space per Fig. 7 and Table 1.
d. TWO OPENINGS OR VERTICAL DUCTS require 1 sq. in.
(645 sq. mm) of free area per 4,000 Btuh (550 mm2/kW) for
combined input of all gas appliances in the space per Fig. 7 and
Table 1.
3. ONE OUTDOOR OPENING requires:
a. 1 sq. in. (645 sq. mm) of free area per 3,000 Btuh (734 mm2/kW)
for combined input of all gas appliances in the space per Table 1
and
b. Not less than the sum of the areas of all vent connectors in the
space.
.
NP = Not Permitted
The opening shall commence within 12 in. (300 mm) of the ceiling.
Appliances in the space shall have clearances of at least 1 in. (25 mm)
from the sides and back and 6 in. (150 mm) from the front. The opening
shall directly communicate with the outdoors or shall communicate
through a vertical or horizontal duct to the outdoors or spaces (crawl or
attic) that freely communicate with the outdoors.
•Indoor Combustion Air© NFPA & AGA
•Standard and Known-Air-Infiltration Rate Methods
•Indoor air is permitted for combustion, ventilation, and dilution, if
the Standard or Known-Air-Infiltration Method is used. The Standard Method:
Use the Standard Method if:
1. The space has no less volume than 50 cubic feet per 1,000 Btuh of
the maximum input ratings for all gas appliances installed in the
space and
2. The air infiltration rate is not known to be less than 0.40 air changes
per hour (ACH).
Table 1 – Minimum Free Area Required for Each Combustion Air opening of Duct to Outdoors
FURNACE
INPUT
(BTUH)
TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING TWO OPENINGS OR VERTICAL DUCTS
(1 SQ. IN./2,000 BTUH) (1,100 SQ. MM/KW) (1 SQ. IN./3,000 BTUH) (734 SQ. MM/KW) (1 SQ. IN./4,000 BTUH) (550 SQ. MM/KW)
Free Area of Opening and
Duct
Sq. In. (Sq. mm)
Round Duct Dia.
In. (mm)
Free Area of Opening and
Duct
Sq. In. (Sq. mm)
Round Duct Dia.
In. (mm)
Free Area of Opening and
Duct
Sq. In. (Sq. mm)
Round Duct Dia.
In. (mm)
44,000 22 (14194) 6 (152) 14.7 (9484) 5 (127) 11 (7096) 4 (102)
66,000 33 (21290) 7 (178) 22 (14193) 6 (152) 16.5 (10645) 5 (127)
88,000 44 (28387) 8 (203) 29.3 (18903) 7 (178) 22 (14193) 6 (152)
110,000 55 (35484) 9 (229) 36.7 (23677) 7 (178) 27.5 (17742) 6 (152)
132,000 66 (42580) 10 (254) 44 (28387) 8 (203) 33 (21290) 7 (178)
EXAMPLES: DETERMINING FREE AREA
FURNACE WATER HEATER TOTAL INPUT
110,000 + 30,000 = (140,000 divided by 4,000) = 35.0 Sq. In. for each two Vertical Ducts or Openings
66,000 + 40,000 = (106,000 divided by 3,000) = 35.3 Sq. In. for a Single Duct or Opening
88,000 + 30,000 = (118,000 divided by 2,000) = 59.0 Sq. In. for each of two Horizontal Ducts
Table 2 – Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors
OTHER THAN FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
ACH
30 40 50 44 66 88 110 132 154
Space Volume Ft3 (M3)
0.60 1,050
(29.7)
1,400
(39.6)
1,750
(49.5)
1,100
(31.1)
1,650
(46.7)
2,200
(62.2)
2,750
(77.8)
3,300
(93.4)
3,850
(109.0)
0.50 1,260
(35.6)
1,680
(47.5)
2,100
(59.4)
1,320
(37.3)
1,980
(56.0)
2,640
(74.7)
3,300
(93.4)
3,960
(112.1)
4,620
(130.8)
0.40 1,575
(44.5)
2,100
(59.4)
2,625
(74.3)
1,650
(46.7)
2,475
(70.0)
3,300
(93.4)
4,125
(116.8)
4,950
(140.1)
5,775
(163.5)
0.30 2,100
(59.4)
2,800
(79.2)
3,500
(99.1)
2,200
(62.2)
3,300
(93.4)
4,400
(124.5)
5,500
(155.7)
6,600
(186.8)
7,700
(218.0)
0.20 3,150
(89.1)
4,200
(118.9)
5,250
(148.6)
3,300
(93.4)
4,950
(140.1)
6,600
(186.8)
8,250
(233.6)
9,900
(280.3)
11,550
(327.0)
0.10 6,300
(178.3)
8,400
(237.8)
10,500
(297.3)
6,600
(186.8)
9,900
(280.3)
13,200
(373.7)
16,500
(467.2)
19,800
(560.6)
23,100
(654.1)
0.00 NP NP NP NP NP NP NP NP NP
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Many homes require air to be supplied from outdoors for furnace
combustion, ventilation, and dilution of flue gases.
The furnace combustion air supply must be provided in accordance
with this instruction manual.
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
8
Use the Known Air Infiltration Rate Method if the infiltration rate is
known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The minimum
required volume of the space varies with the number of ACH and shall
be determined per Table 2 or Equations 1 and 2. Determine the minimum
required volume for each appliance in the space and add the volumes
together to get the total minimum required volume for the space.
Table 2 - Minimum Space Volumes were determined by using the
following equations from the National Fuel Gas Code ANSI
Z223.1/NFPA 54, 9.3.2.2:
1. For other than fan-assisted appliances, such as a draft
hood-equipped water heater, use the following equation:
A04002
2. For fan-assisted appliances such as this furnace, use the following
equation:
A04003
If the following is applied to either equation:
Iother = combined input of all other than fan-assisted appliances in
Btuh/hr
Ifan = combined input of all fan-assisted appliances in Btuh/hr
ACH = air changes per hour (ACH shall not exceed 0.60.)
* Minimum opening size is 100 sq in. (64516 sq. mm) with minimum dimensions of 3 in.
(76 mm)
† Minimum of 3 in. (76 mm) when type-B1 vent is used.
A03175
Fig. 8 – Air for Combustion, Ventilation, and Dilution from Indoors
Then the following requirements apply to both the Standard Method
and to the Known Air Infiltration Rate Method:
1. Adjoining rooms can be considered part of a space if:
a. There are no closeable doors between rooms.
b. Combining spaces on same floor level. Each opening shall have
free area of at least 1 in.2/1,000 Btuh (2,000 mm2/kW) of the
total input rating of all gas appliances in the space, but not less
than 100 in.2 (0.06 m2). One opening shall commence within 12
in. (300 mm) of the ceiling and the second opening shall
commence within 12 in. (300 mm) of the floor. The minimum
dimension of air openings shall be at least 3 in. (80 mm), see
Fig. 8.
c. Combining space on different floor levels. The volumes of
spaces on different floor levels shall be considered as
communicating spaces if connected by one or more permanent
openings in doors or floors having free area of at least 2
in.2/1,000 Btuh (4,400 mm2/kW) of total input rating of all gas
appliances
2. An attic or crawlspace may be considered a space that freely
communicates with the outdoors provided there are adequate
permanent ventilation openings directly to outdoors having free
area of at least 1-in.2/4,000 Btuh of total input rating for all gas
appliances in the space.
3. In spaces that use the Indoor Combustion Air Method, infiltration
should be adequate to provide air for combustion, permanent
ventilation and dilution of flue gases. However, in buildings with
unusually tight construction, additional air MUST be provided
using the methods described in the Outdoor Combustion Air
Method section.
4. Unusually tight construction is defined as Construction with:
a. Walls and ceilings exposed to the outdoors have a continuous,
sealed vapor barrier. Openings are gasketed or sealed and
b. Doors and openable windows are weatherstripped and
c. Other openings are caulked or sealed. These include joints
around window and door frames, between sole plates and floors,
between wall-ceiling joints, between wall panels, at penetrations
for plumbing, electrical and gas lines, etc.
Combination of Indoor and Outdoor Air
1. Indoor openings shall comply with the Indoor Combustion Air
Method below and,
2. Outdoor openings shall be located as required in the Outdoor
Combustion Air Method mentioned previously and,
3. Outdoor openings shall be sized as follows:
a. Calculate the Ratio of all Indoor Space volume divided by
required volume for Indoor Combustion Air Method below.
b. Outdoor opening size reduction Factor is 1 minus the Ratio in a.
above.
c. Minimum size of Outdoor openings shall be the size required in
Outdoor Combustion Air Method above multiplied by reduction
Factor in b. above. The minimum dimension of air openings shall
be not less than 3 in. (80 mm).
INSTALLATION
UPFLOW INSTALLATION
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. Remove and discard this panel when bottom return
air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler
panel, see Fig. 9.
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
A10273
Fig. 9 – Removing Bottom Closure Panel
Volume Other =21ft3
ACH
I other
1000 Btu/hr
Volume Fan =15ft3
ACH
I fan
1000 Btu/hr
CIRCULATING AIR
DUCTS
6" MIN
(FRONT)Ü
CIRCULATING AIR DUCTS
VENT THROUGH ROOF
1 SQ IN.
PER 1000
BTUH* IN DOOR
ORWALL
12" MAX
1 SQ IN.
PER 1000
BTUH* IN DOOR
ORWALL
12" MAX
UNCONFINED
SPACE
INTERIOR
HEATED
SPACE
CLEARANCE IN FRONT OF COMBUSTION AIR
OPENINGS SHALL BE AT LEAST3 IN.
(305mm)
(152mm)
(305mm)
Bottom
Closure Panel
Bottom Filler Panel
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
9
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. This panel MUST be in place when only side return
air is used.
NOTE: Side return-air openings can be used in UPFLOW and most
HORIZONTAL configurations. Do not use side return-air openings in
DOWNFLOW configuration.
DOWNFLOW INSTALLATION
NOTE: For downflow applications, this furnace is approved for use on
combustible flooring when any one of the following accessories are
used:
•Downflow combustible factory-approved floor subbase
•Coil model numbers EAM4X, EDM4X, EMA4X, END4X or ENW4X
•Coil casing model number NAEA
1. Determine application being installed from Table 3.
2. Construct hole in floor, see Table 3 and Fig. 10.
3. Construct plenum to dimensions specified, see Table 3 and Fig. 10.
4. If downflow subbase is used, install as, see Fig. 11. If coil model
numbers END4X, ENW4X or coil casing model number NAEA are
used, install as, see Fig. 12.
NOTE: It is recommended that the perforated supply-air duct flanges be
completely folded over or removed from furnace when installing the
furnace on a factory-supplied cased coil or coil box. To remove the
supply-air duct flange, use wide duct pliers or hand seamers to bend
flange back and forth until it breaks off. Be careful of sharp edges. Refer
to Duct Flanges (Fig. 17) in the “Air Ducts” section.
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. Remove and discard this panel when bottom return
air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler
panel, Fig. 9.
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
A96283
Fig. 10 – Floor and Plenum Opening Dimensions
A96285
Fig. 11 – Furnace, Plenum, and Subbase Installed on a Combustible
Floor
A08556
Fig. 12 – Furnace, Plenum, and Coil Assembly or Coil Box Installed
on a Combustible Floor
HORIZONTAL INSTALLATION
The furnace can be installed horizontally in an attic or crawlspace on
either the left-hand (LH) or right-hand (RH) side. The furnace can be
hung from floor joists, rafters or trusses or installed on a
non-combustible platform, blocks, bricks or pad.
Suspended Furnace Support
The furnace may be supported under each end with threaded rod, angle
iron or metal plumber’s strap as shown, see Fig. 14 and Fig. 15. Secure
angle iron to bottom of furnace as shown. Heavy-gauge sheet metal
straps (plumber’s straps) may be used to suspend the furnace from each
bottom corner. To prevent screws from pulling out, use 2 #8 x in. screws
into the side and 2 #8 x in. screws in the bottom of the furnace casing for
each strap, see Fig. 14 and Fig. 15.
If the screws are attached to ONLY the furnace sides and not the bottom,
the straps must be vertical against the furnace sides and not pull away
from the furnace sides, so that the strap attachment screws are not in
tension (are loaded in shear) for reliable support.
Platform Furnace Support
Construct working platform at location where all required furnace
clearances are met, see Fig. 2 and Fig. 13. For furnaces with 1-in. (25
mm) clearance requirement on side, set furnace on non-combustible
blocks, bricks or angle iron. For crawlspace installations, if the furnace
is not suspended from the floor joists, the ground underneath furnace
must be level and the furnace set in blocks or bricks.
PLENUM
OPENING
C
A
BD
FLOOR
OPENING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
APPROVED
COIL ASSEMBLY
OR
COIL BOX
FURNACE
SHEET METAL
PLENUM
FLOOR
OPENING
COMBUSTIBLE
FLOORING
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
10
Roll-Out Protection
Provide a minimum 17-3/4-in. X 22-in. (451 X 559 mm) piece of sheet
metal for flame roll-out protection in front of burner area for furnaces
closer than 12-in. (305 mm) above the combustible deck or suspended
furnaces closer than 12-in. (305 mm) to joists. The sheet metal MUST
extend underneath the furnace casing by 1-in. (25 mm) with the door
removed.
The bottom closure panel on furnaces of widths 17-1/2-in. (445 mm) and
larger may be used for flame roll-out protection when bottom of furnace
is used for return air connection. See Fig. 13 for proper orientation of
roll-out shield.
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. Remove and discard this panel when bottom return
air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove two screws holding bottom filler
panel, see Fig. 9.
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
A10164
Fig. 13 – Typical Attic Installation
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. This panel MUST be in place when side return air
inlet(s) are used without a bottom return air inlet.
Not all horizontal furnaces are approved for side return air connections,
see Fig. 20.
Table 3 – Opening Dimensions - In. (mm)
FURNACE
CASING
WIDTH
IN. (mm)
APPLICATION
PLENUM OPENING FLOOR OPENING
A B C D
14–3/16
(360)
Upflow Applications on Combustible or Noncombustible
Flooring (subbase not required)
12-11/16
(322)
21-5/8
(549)
13-5/16
(338)
22-1/4
(565)
Downflow Applications on Noncombustible Flooring
(subbase not required)
12-9/16
(319)
19
(483)
13-3/16
(335)
19-5/8
(498)
Downflow applications on Combustible Flooring
(subbase required)
11-13/16
(284)
19
(483)
13-7/16
(341)
20-5/8
(600)
Downflow Applications on Combustible Flooring with coil assembly or coil
box (subbase not required)
12-5/16
(319)
19
(483)
13-5/16
(338)
20
(508)
17–1/2
(445)
Upflow Applications on Combustible or Noncombustible
Flooring (subbase not required)
16
(406)
21-5/8
(549)
16-5/8
(422)
22-1/4
(565)
Downflow Applications on Noncombustible Flooring
(subbase not required)
15-7/8
(403)
19
(483)
16-1/2
(419)
19-5/8
(498)
Downflow Applications on Combustible Flooring
(subbase required)
15-1/8
(384)
19
(483)
16-3/4
(425)
20-5/8
(600)
Downflow Applications on Combustible Flooring with coil assembly or coil
box (subbase not required)
15-1/2
(394)
19
(483)
16-1/2
(419)
20
(508)
21
(533)
Upflow Applications on Combustible or Noncombustible
Flooring (subbase not required)
19-1/2
(495)
21-5/8
(549)
20-1/8
(511)
22-1/4
(565)
Downflow Applications on Noncombustible Flooring
(subbase not required)
19-3/8
(492)
19
(483)
20
(508)
19-5/8
(498)
Downflow Applications on Combustible Flooring
(subbase required)
18-5/8
(473)
19
(483)
20-1/4
(514)
20-5/8
(600)
Downflow Applications on Combustible Flooring with coil assembly or coil
box (subbase not required)
19
(483)
19
(483)
20
(508)
20
(508)
24-1/2
(622)
Upflow Applications on Combustible or Noncombustible
Flooring (subbase not required)
23
(584)
21-1/8
(537)
23-5/8
(600)
22-1/4
(565)
Downflow Applications on Noncombustible Flooring
(subbase not required)
22-7/8
(581)
19
(483)
23-1/2
(597)
19-5/8
(498)
Downflow Applications on Combustible Flooring
(subbase required)
22-1/8
(562)
19
(483)
23-3/4
(603)
20-5/8
(600)
Downflow Applications on Combustible Flooring with coil assembly or coil
box (subbase not required)
22-1/2
(572)
19
(483)
23-1/2
(597)
20
(508)
30-IN. (762mm)
MIN WORK AREA
6″ MIN*
TYPE-B
VENT
17 3/4
″
22
″
SHEET
METAL
SEDIMENT
TRAP
EQUIPMENT MANUAL
SHUT-OFF GAS VALVE
LINE CONTACT ONLY PERMISSIBLE BETWEEN
LINES FORMED BY INTERSECTIONS OF
THE TOP AND TWO SIDES OF THE FURNACE
JACKET AND BUILDING JOISTS,
STUDS, OR FRAMING.
GAS
ENTRY
17 3/4
″
(451mm)
OVERALL
4 3/4
″
(121mm)
UNDER DOOR
1″
(25mm)
UNDER FURNACE
EXTEND OUT 12″
(305mm)
FROM FACE OF DOOR
* WHEN USED WITH
SINGLE WALL VENT
CONNECTIONS
UNION
(152mm)
(451mm)
(559mm)
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
11
A10130
Fig. 14 – Horizontal Unit Suspension
A10131
Fig. 15 – Horizontal Suspension with Straps
FILTER ARRANGEMENT
There are no provisions for an internal filter rack in these furnaces. A
field-supplied accessory external filter rack is required.
Refer to the instructions supplied with the external filter rack for
assembly and installation options.
Leveling Legs (If Desired)
In upflow position with side return inlet(s), leveling legs may be used,
see Fig. 16. Install field-supplied, 5/16 X 1-1/2 in. (8 X 38 mm) (max)
corrosion-resistant machine bolts, washers and nuts.
A89014
Fig. 16 – Leveling Legs
NOTE: Bottom closure must be used when leveling legs are used. It
may be necessary to remove and reinstall bottom closure panel to install
leveling legs. To remove bottom closure panel, see Item 1 in “Bottom
Return Air Inlet” section in Step 1 above.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each bottom
corner of furnace, see Fig. 16.
2. For each leg, install nut on bolt and then install bolt with nut in
hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer
if desired.)
4. Adjust outside nut to provide desired height, and tighten inside nut
to secure arrangement.
5. Reinstall bottom closure panel if removed.
LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with, or on the downstream
side of the unit to avoid condensation in the heat exchangers. When
installed parallel with the furnace, dampers or other flow control must
prevent chilled air from entering the furnace. If the dampers are
manually operated, they must be equipped with means to prevent
operation of either unit unless the damper is in the full-heat or full-cool
position.
AIR DUCTS
GENERAL REQUIREMENTS
The duct system should be designed and sized according to accepted
national standards such as those published by: Air Conditioning
Contractors Association (ACCA), Sheet Metal and Air Conditioning
Contractors National Association (SMACNA) or American Society of
Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or
consult The Air Systems Design Guidelines reference tables available
from your local distributor. The duct system should be sized to handle
the required system design CFM at the design external static pressure.
The furnace airflow rates are provided in Table 13-Air Delivery-CFM
(With Filter). When a furnace is installed so that the supply ducts carry
air circulated by the furnace to areas outside the space containing the
WARNING
!
FIRE, EXPLOSION, AND CARBON MONOXIDE
POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
Do not install the furnace on its back or hang furnace with control
compartment facing downward. Safety control operation will be
adversely affected. Never connect return-air ducts to the back of the
furnace.
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, or death.
Never operate a furnace without a filter or with filter access door
removed.
1/4" (6mm) THREADED ROD
4 REQ.
SECURE ANGLE
IRON TO BOTTOM
OF FURNACE WITH
3 #8 x3/4" (19mm) SCREWS
TYPICAL FOR 2 SUPPORTS
1” (25mm) SQUARE, 1-1/4”x1-1/4”x1/8” (32x32x3mm)
ANGLE IRON OR UNI-STRUT MAY BE USED
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS
REQ. PER ROD
8" (203mm) MIN
FOR DOOR REMOVAL
OUTER DOOR
ASSEMBLY
METHOD 2
USE (4) #8 x 3/4 (19 mm) SHEET
METAL SCREWS FOR EACH
STRAP. THE STRAPS
SHOULD BE VERTICAL
AGAINST THE FURNACE
SIDES AND NOT PULL AWAY
FROM THE FURNACE
SIDES.
METHOD 1
FOLD ALL STRAPS UNDER
FURNACE AND SECURE WTH
(4) #8 x 3/4 (19 mm) SHEET METAL SCREWS
(2 SCREWS IN SIDE AND 2 SCREWS
IN BOTTOM).
1
3
/
4
1
3
/
4
1
3/
4
1
3/
4
5/
16
5
/
16
5/
16
5/
16
(44mm)
(8mm)
(44mm)
(8mm)
(8mm)
(8mm)
(44mm)
(44mm)
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
12
furnace, the return air shall also be handled by duct(s) sealed to the
furnace casing and terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used. Seal
supply- and return-duct connections to furnace with code approved tape
or duct sealer.
NOTE: Flexible connections should be used between ductwork and
furnace to prevent transmission of vibration.
Ductwork passing through unconditioned space should be insulated to
enhance system performance. When air conditioning is used, a vapor
barrier is recommended.
Maintain a 1-in. (25 mm) clearance from combustible materials to
supply air ductwork for a distance of 36-in. (914 mm) horizontally from
the furnace. See NFPA 90B or local code for further requirements
Ductwork Acoustical Treatment
NOTE: Metal duct systems that do not have a 90 degree elbow and 10
ft. (3 M) of main duct to the first branch take-off may require internal
acoustical lining. As an alternative, fibrous ductwork may be used if
constructed and installed in accordance with the latest edition of
SMACNA construction standard on fibrous glass ducts. Both acoustical
lining and fibrous ductwork shall comply with NFPA 90B as tested by
UL Standard 181 for Class 1 Rigid air ducts.
SUPPLY AIR CONNECTIONS
For a furnace not equipped with a cooling coil, the outlet duct shall be
provided with a removable access panel. This opening shall be
accessible when the furnace is installed and shall be of such a size that
the heat exchanger can be viewed for possible openings using light
assistance or a probe can be inserted for sampling the air stream. The
cover attachment shall prevent leaks.
Upflow and Horizontal Furnaces
Connect supply-air duct to flanges on furnace supply-air outlet. Bend
flange upward to 90° with wide duct pliers, see Fig. 17. The supply-air
duct must be connected to ONLY the furnace supply-outlet-air duct
flanges or air conditioning coil casing (when used). DO NOT cut main
furnace casing side to attach supply air duct, humidifier, or other
accessories. All accessories MUST be connected to duct external to
furnace main casing.
NOTE: For horizontal applications, the top most flange may be bent
past 90° to allow the evaporator coil to hang on the flange temporarily
while the remaining attachment and sealing of the coil are performed.
Downflow Furnaces
Connect supply-air duct to supply-air outlet on furnace. Bend flange
inward past 90° with wide duct pliers, see Fig. 17. The supply-air duct
must be connected to ONLY the furnace supply outlet or air conditioning
coil casing (when used). When installed on combustible material,
supply-air duct must be connected to ONLY the factory-approved
accessory subbase, or a factory-approved air conditioning coil casing.
DO NOT cut main furnace casing to attach supply side air duct,
humidifier, or other accessories. All accessories MUST be connected to
duct external to furnace casing.
RETURN AIR CONNECTIONS
A190346
Fig. 17 – Duct Flanges
Downflow Furnaces
The return-air duct must be connected to return-air opening bottom inlet,
see Fig. 1. DO NOT cut into casing sides (left or right). Side opening is
permitted for only upflow and certain horizontal furnaces. Bypass
humidifier connections should be made at ductwork or coil casing sides
exterior to furnace, see Fig. 18.
Upflow and Horizontal Furnaces
The return-air duct must be connected to bottom, sides (left or right), or a
combination of bottom and side(s) of main furnace casing, see Fig. 1.
Bypass humidifier may be attached into unused return air side of the
furnace casing, see Fig. 19 and Fig. 20. Not all horizontal furnace
models are approved for side return air connections, see Fig. 20.
WARNING
!
FIRE HAZARD
A failure to follow this warning could cause personal injury, death
and/or property damage.
Never connect return-air ducts to the back of the furnace. Follow
instructions below.
UPFLOW/
HORIZONTAL DOWNFLOW
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
13
A02163
Fig. 18 – Downflow Return Air Configurations and Restrictions
A02075
Fig. 19 – Upflow Return Air Configurations and Restrictions
A02162
Fig. 20 – Horizontal Return Air Configurations and Restrictions
DOWNFLOW RETURN AIR CONFIGURATIONS AND RESTRICTIONS
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
14
GAS PIPING
Gas piping must be installed in accordance with national and local
codes. Refer to current edition of NFGC in the U.S.
Installations must be made in accordance with all authorities having
jurisdiction. If possible, the gas supply line should be a separate line
running directly from meter to furnace.
NOTE: In the state of Massachusetts:
1. Gas supply connections MUST be performed by a licensed plumber
or gas fitter.
2. When flexible connectors are used, the maximum length shall not
exceed 36 in. (915 mm).
3. When lever handle type manual equipment shutoff valves are used,
they shall be T-handle valves.
4. The use of copper tubing for gas piping is NOT approved by the
state of Massachusetts.
Refer to Table 4 for recommended gas pipe sizing. Risers must be used
to connect to furnace and to meter. Support all gas piping with
appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft.
(1.8 M). Joint compound (pipe dope) should be applied sparingly and
only to male threads of joints. Pipe dope must be resistant to the action
of propane gas.
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-In. W.C.) or less and a pressure
drop of 0.5-In. W.C. (based on a 0.60 specific gravity gas). Ref: Table 6 and 9.2 NFGC.
An accessible manual equipment shutoff valve MUST be installed
external to furnace casing and within 6 ft. (1.8 M) of furnace. A 1/8-in.
(3 mm) NPT plugged tapping, accessible for test gauge connection,
MUST be installed immediately upstream of gas supply connection to
furnace and downstream of manual equipment shutoff valve.
NOTE: The furnace gas control valve inlet pressure tap connection is
suitable to use as test gauge connection providing test pressure DOES
NOT exceed maximum 0.5 psig (14-In. W.C.) stated on gas control
valve, see Fig. 21.
Some installations require gas entry on right side of furnace (as viewed
in upflow), see Fig. 22.
A04167
Fig. 21 – Redundant Automatic Gas Control Valve
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Never purge a gas line into a combustion chamber. Never test for gas
leaks with an open flame. Use a commercially available soap solution
made specifically for the detection of leaks to check all connections. A
fire or explosion may result causing property damage, personal injury
or loss of life.
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Use proper length of pipe to avoid stress on gas control manifold and
gas valve.
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Gas valve inlet and/or inlet pipe must remain capped until gas supply
line is permanently installed to protect the valve from moisture and
debris. Also, install a sediment trap in the gas supply piping at the inlet
to the gas valve.
Table 4 – Maximum Capacity of Pipe
NOMINAL
IRON PIPE
SIZE
IN. (MM)
INTERNAL
DIA.
IN. (MM)
LENGTH OF PIPE - FT (M)
10
(3.0)
20
(6.0)
30
(9.1)
40
(12.1)
50
(15.2)
1/2 (12.7) 0.622(158) 175 120 97 82 73
3/4 (19.0) 0.824 (20.9) 360 250 200 170 151
1 ( 25.4) 1.049 (26.6) 680 465 375 320 285
1-1/4 (31.8) 1.380 (35.0) 1400 950 770 660 580
1-1/2 (38.1) 1.610 (40.9) 2100 1460 1180 990 900
WARNING
!
FIRE OR EXPLOSION HAZARD
A failure to follow this warning could result in personal injury, death,
and/or property damage.
If local codes allow the use of a flexible gas appliance connector,
always use a new listed connector. Do not use a connector which has
previously served another gas appliance. Black iron pipe shall be
installed at the furnace gas control valve and extend a minimum of 2-in.
(51 mm) outside the furnace.
CAUTION
!
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in furnace damage.
Connect gas pipe to furnace using a backup wrench to avoid damaging
gas controls and burner misalignment.
REGULATOR COVER SCREW
PLASTIC ADJUST SCREW
LOW STAGE
GAS PRESSURE
REGULATOR ADJUSTMENT
MANIFOLD
PRESSURE TAP
INLET
PRESSURE TAP
ON/OFF SWITCH
REGULATOR SPRING
HIGH STAGE GAS
PRESSURE REGULATOR
ADJUSTMENT
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
15
A08551
Fig. 22 – Burner and Manifold
Install a sediment trap in riser leading to furnace, see Fig. 23. Connect a
capped nipple into lower end of tee. Capped nipple should extend below
level of furnace gas controls. Place a ground joint union between furnace
gas control valve and exterior manual equipment gas shutoff valve.
A 1/8-in. (3 mm) NPT plugged tapping, accessible for test gauge
connection, MUST be installed immediately upstream of gas supply
connection to furnace and downstream of manual equipment shutoff
valve.
A02035
Fig. 23 – Typical Gas Pipe Arrangement
Piping should be pressure and leak tested in accordance with the current
addition of the NFGC in the United States, local, and national plumbing
and gas codes before the furnace has been connected. After all
connections have been made, purge lines and check for leakage at
furnace prior to operating furnace.
If pressure exceeds 0.5 psig (14-In. W.C.), gas supply pipe must be
disconnected from furnace and capped before and during supply pipe
pressure test. If test pressure is equal to or less than 0.5 psig (14-In.
W.C.), turn off electric shutoff switch located on furnace gas control
valve and accessible manual equipment shutoff valve before and during
supply pipe pressure test. After all connections have been made, purge
lines and check for leakage at furnace prior to operating furnace.
The gas supply pressure shall be within the maximum and minimum
inlet supply pressures marked on the rating plate with the furnace
burners ON and OFF.
ELECTRICAL CONNECTIONS
See Fig. 24 for field wiring diagram showing typical field 115-v wiring.
Check all factory and field electrical connections for tightness.
Field-supplied wiring shall conform with the limitations of 63°F (33°C)
rise.
2” (51mm)
Street Elbow
UNION
SEDIMENT
TRAP
MANUAL
SHUTOFF
VALVE
(REQUIRED)
GAS
SUPPLY
WARNING
!
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings could result in dangerous operation,
serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury,
death or property damage.
- Before servicing, disconnect all electrical power to furnace.
- When servicing controls, label all wires prior to disconnection.
Reconnect wires correctly.
- Verify proper operation after servicing.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Blower access panel door switch opens 115-v power to control. No
component operation can occur. Do not bypass or close switch with
panel removed.
WARNING
!
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
The cabinet MUST have an uninterrupted or unbroken ground
according to NEC NFPA 70 or local codes to minimize personal injury
if an electrical fault should occur. This may consist of electrical wire,
conduit approved for electrical ground or a listed, grounded power cord
(where permitted by local code) when installed in accordance with
existing electrical codes. Refer to the power cord manufacturer’s
ratings for proper wire gauge. Do not use gas piping as an electrical
ground.
CAUTION
!
FURNACE MAY NOT OPERATE HAZARD
Failure to follow this caution may result in intermittent furnace
operation.
Furnace control must be grounded for proper operation or else control
will lock out. Control must remain grounded through green/yellow wire
routed to gas valve and manifold bracket screw.
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
Do not connect aluminum wire between disconnect switch and furnace.
Use only copper wire, see Fig. 25.
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
16
A95236
Fig. 24 – Field Wiring Diagram
A190279
Fig. 25 – Field-Supplied External
Electrical Box on Furnace Casing
115-V Wiring
Verify that the voltage, frequency, and phase correspond to that specified
on unit rating plate. Also, check to be sure that service provided by
utility is sufficient to handle load imposed by this equipment. Refer to
rating plate or Table 5 for equipment electrical specifications.
U.S. Installations: Make all electrical connections in accordance with
National Electrical Code (NEC) NFPA 70 and any local codes or
ordinances that might apply.
Use a separate, fused branch electrical circuit with a properly sized fuse
or circuit breaker for this furnace. See Table 5 for wire size and fuse
specifications. A readily accessible means of electrical disconnect must
be located within sight of the furnace.
NOTE: Proper polarity must be maintained for 115-v wiring. If polarity
is incorrect, control LED status indicator light will flash status code 10
and furnace will NOT operate.
J-BOX RELOCATION
NOTE: If factory location of J-Box is acceptable, go to next section
(ELECTRICAL CONNECTION to J-Box).
NOTE: On 14-in. (356 mm) wide casing models, the J-Box shall not be
relocated to other side of furnace casing when the vent pipe is routed
within the casing.
1. Remove and save two screws holding J-Box, see Fig. 26.
NOTE: The J-Box cover need not be removed from the J-Box in order
to move the J-Box. Do NOT remove green ground screw inside J-Box,
see Fig. 26.
2. Cut wire tie on loop in furnace wires attached to J-Box.
3. Move J-Box to desired location.
4. Fasten J-Box to casing with the two screws removed in Step 1.
5. Route J-Box wires within furnace away from sharp edges, rotating
parts and hot surfaces.
Table 5 – Electrical Data
FURNACE
SIZE
VOLTS-
HERTZ-
PHASE
OPERATING
VOLTAGE RANGE*
*. Permissible limits of the voltage range at which the unit operates satisfactorily.
MAX.
UNIT
AMPS
UNIT
AMPACITY†
†. Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load
amps.
MAX. WIRE LENGTH
- FT (M)‡
‡. Length shown is as measured 1 way along wire path between furnace and service panel for maximum 2 percent voltage drop.
MAX. FUSE OR CKT
BKR AMPS **
**. Time-delay type is recommended.
MIN. WIRE
GAUGE
Max. Min.
0451712 115-60-1 127 104 9.0 12.0 30 (9.4) 15 14
0701412 115-60-1 127 104 9.0 12.0 30 (9.4) 15 14
0701716 115-60-1 127 104 9.0 13.0 28 (8.7) 15 14
0702120 115-60-1 127 104 14.1 18.4 31 (9.5) 20 12
0901716 115-60-1 127 104 9.6 12.63 29 (9.0) 15 14
0902120 115-60-1 127 104 14.7 19.0 30 (9.2) 20 12
1102120 115-60-1 127 104 15.0 19.3 29 (9.1) 20 12
1352422 115-60-1 127 104 15.0 19.3 29 (9.1) 20 12
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
JUNCTION
BOX CONTROL
BOX
24-VOLT
TERMINAL
BLOCK
THREE-WIRE
HEATING-
ONLY
FIVE
WIRE
NOTE 2
NOTE 1
1-STAGE
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
FUSED DISCONNECT
CONDENSING
UNIT
FURNACE
COM
R
WCY RG
GND
GND
FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-VOLT WIRING
Connect Y/Y2-terminal as shown for proper operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
208/230- O
R
460-VOLT
THREE
PHASE
208/230-
VOLT
SINGLE
PHASE
W
HT
BLK
WHT
BLK
W/W1
W2
Y/Y2
G
NOTES: 1.
2.
3.
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
17
A10291
Fig. 26 – Relocating J-Box
Electrical Connection to J-Box
Electrical Box on Furnace Casing Side
A190278
Fig. 27 – Field-Supplied Electrical Box on Furnace Casing
1. Select and remove a hole knockout in the casing where the
electrical box is to be installed.
NOTE: Check that duct on side of furnace will not interfere with
installed electrical box.
2. Remove the desired electrical box hole knockout and position the
hole in the electrical box over the hole in the furnace casing.
3. Fasten the electrical box to casing by driving two field-supplied
screws from inside electrical box into casing steel.
4. Remove and save two screws holding J-Box, see Fig. 26.
5. Pull furnace power wires out of 1/2-in. (12 mm) diameter hole in
J-Box. Do not loosen wires from strain-relief wire-tie on outside of
J-Box.
6. Route furnace power wires through holes in casing and electrical
box and into electrical box.
7. Pull field power wires into electrical box.
8. Remove cover from furnace J-Box.
9. Route field ground wire through holes in electrical box and casing,
and into furnace J-Box.
10. Reattach furnace J-Box to furnace casing with screws removed in
Step 4.
11. Secure field ground wire to J-Box green ground screw.
12. Complete electrical box wiring and installation. Connect line
voltage leads, see Fig. 27. Use best practices (NEC in U.S. for wire
bushings, strain relief, etc.
13. Reinstall cover to J-Box. Do not pinch wires between cover and
bracket.
Power Cord Installation in Furnace J-Box
NOTE: Power cords must be able to handle the electrical requirements
listed in Table 5. Refer to power cord manufacturer’s listings.
1. Remove cover from J-Box.
2. Route listed power cord through 7/8-in. (22 mm) diameter hole in
J-Box.
3. Secure power cord to J-Box bracket with a strain relief bushing or a
connector approved for the type of cord used.
4. Secure field ground wire to green ground screw on J-Box bracket.
5. Connect line voltage leads, see Fig. 24.
6. Reinstall cover to J-Box. Do not pinch wires between cover and
bracket.
BX Cable Installation in Furnace J-Box
1. Remove cover from J-Box.
2. Route BX cable into 7/8-in. (22 mm) diameter hole in J-Box.
3. Secure BX cable to J-Box bracket with connectors approved for the
type of cable used.
4. Secure field ground wire to green ground screw on J-Box bracket.
5. Connect line voltage leads, see Fig. 24.
6. Reinstall cover to J-Box. Do not pinch wires between cover and
bracket.
24-V Wiring
Make field 24-v connections at the 24-v terminal strip, see Fig. 24 -
Fig. 32. Connect terminal Y/Y2 as shown in Fig. 28 - Fig. 31 for proper
cooling operation. Use only AWG No. 18, color-coded, copper
thermostat wire.
The 24-v circuit contains an automotive-type, 3-amp. fuse located on the
control. Any direct shorts during installation, service, or maintenance
could cause this fuse to blow. If fuse replacement is required, use ONLY
a 3-amp. fuse of identical size.
ACCESSORIES
1. Electronic Air Cleaner (EAC)
Connect an accessory Electronic Air Cleaner (if used) using 1/4-in
female quick connect terminals to the two male 1/4-in
quick-connect terminals on the control board marked EAC-1 and
EAC-2. The terminals are rated for 115VAC, 1.0 amps maximum
and are energized during blower motor operation, see Fig. 32.
2. Humidifier (HUM)
Connect an accessory 24 VAC, 0.5 amp. maximum humidifier
(if used) to the 1/4-in male quick-connect HUM terminal and
COM-24V screw terminal on the control board thermostat strip.
The HUM terminal is energized when blower is energized in
heating, see Fig. 32.
NOTE: DO NOT connect furnace control HUM terminal to HUM
(humidifier) terminal on Thermostat, Zone Controller or similar device.
See Thermostat, Zone Controller, thermostat, or controller
manufacturer’s instructions for proper connection.
WARNING
!
FIRE OR ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
If field-supplied manual disconnect switch is to be mounted on furnace
casing side, select a location where a drill or fastener cannot damage
electrical or gas components.
FactoryFactory
InstalledInstalled
AlternateAlternate
LocationLocation
GROUND
NEUTRAL
INE VOLTAGE
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
18
L09F025
Fig. 28 – Variable Furnace with Single-Speed Air Conditioner
L09F026
Fig. 29 – Variable Furnace with Two-Speed Air Conditioner
L09F026
Fig. 30 – Variable Furnace with Single-Speed Heat Pump
(Dual Fuel)
L09F028
Fig. 31 – Variable Furnace with Two-Speed Heat Pump
(Dual Fuel)
NOTES FOR FIGURE 28 - FIGURE 31
1. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
2. Outdoor Air Temperature Sensor must be attached in all dual fuel applications.
3. Refer to ICP thermostat Installation Instructions for additional information and setup procedure.
4. When using a Humidity Sensing Thermostat, set DEHUMIDIFY OPTIONS to H DE-ENRGZD FOR DEHUM.
5. Optional connection. If wire is connected SW1-2 on VS furnace control should be set in ON position to allow
ICP Thermostat to control the furnace staging.
6. HUM connection is 24 VAC and is energized when the blower turns on during a call for heat.
7. When connecting 115 VAC to humidifier use a separate 115 VAC supply.
8. When using a humidifier on a HP installation connect humidifier to
hot water.
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
19
A190154
Fig. 32 – Variable Speed Furnace Control for ECM Blower Motor
VENTING
The furnace shall be connected to a listed factory built chimney or vent,
or a clay-tile lined masonry or concrete chimney. Venting into an unlined
masonry chimney or concrete chimney is prohibited.
When an existing Category I furnace is removed or replaced, the original
venting system, may no longer be sized to properly vent the attached
appliances. An improperly sized Category I venting system could cause
the formation of condensate in the furnace and vent, leakage of
condensate and combustion products, and spillage of combustion
products into the living space.
Vent system or vent connectors may need to be resized. Vent systems or
vent connectors must be sized to approach minimum size as determined
using appropriate table found in the current edition of NFGC.
GENERAL VENTING REQUIREMENTS
Follow all safety codes for proper vent sizing and installation
requirements, including local building codes, the National Fuel Gas
Code NFPA 54/ANSI Z223.1 (NFGC), Parts 12 and 13 in the United
States, the local building codes, and furnace and vent manufacturers’
instructions.
These furnaces are design-certified as Category I furnaces in accordance
with ANSI Z21.47/CSA 2.3 and operate with a non-positive vent static
pressure to minimize the potential for vent gas leakage. Category I
furnaces operate with a flue loss not less than 17 percent to minimize the
potential for condensation in the venting system. These furnaces are
approved for common venting and multistory venting with other fan
assisted or draft hood equipped appliances in accordance with the
NFGC, the local building codes, and furnace and vent manufacturers’
instructions. The following information and warning must be considered
in addition to the requirements defined in the NFGC.
1. If a vent (common or dedicated) becomes blocked, the furnace will
be shut off by the draft safeguard switch located on the vent elbow.
2. Two-stage furnaces require Type B vent connectors outside the
casing in all configurations. Single wall vent connector may be
used inside the furnace casing with the transition to Type B vent
outside the furnace casing. Size the connector so that the FAN-Min
vent connector capacity is equal to or lower than the low fire rate of
the furnace and the FAN-Max vent connector capacity is equal to or
higher than the furnace high fire rate.
3. Do not vent this Category I furnace into a single wall dedicated or
common vent. The dedicated or common vent is considered to be
the vertical portion of the vent system that terminates outdoors.
4. Vent connectors serving Category I furnaces shall not be connected
into any portion of a mechanical draft system operating under
positive pressure.
5. Do not vent this appliance with any solid fuel burning appliance.
6. Category I furnaces must be vented vertically or nearly vertically
unless equipped with a listed mechanical venter. See SIDEWALL
VENTING section.
7. Do not vent this appliance into an unlined masonry chimney. (Refer
to Chimney Inspection Chart, Fig. 33.
24-V THERMOSTAT
TERMINALS
PL2 – HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
115-VAC (L2) NEUTRAL
CONNECTIONS 115-VAC (L1) LINE
VOLTAGE CONNECTIONS
EAC-1 TERMINAL
(
115-VAC 1.0 AMP MAX.
)
PL1 – LOW VOLTAGE MAIN
HARNESS CONNECTOR
TRANSFORMER 24-VAC
CONNECTIONS
3-AMP FUSE
STATUS AND COMM
LED LIGHTS
SW1 SETUP
SWITCHES AND
BLOWER OFF-
DELAY
MODEL PLUG
CONNECTOR
COMMUNICATION
CONNECTOR
AIR CONDITIONING (A/C) &
CONTINUOUS FAN (CF)
AIRFLOW SETUP SWITCHES
OUTDOOR
AIR TEMP
CONNECTOR
HUMIDIFIER
TERMINAL (24-VAC
0.5 AMP MAX.)
FLASH
UPGRADE
CONNECTOR
(FACTORY
ONLY)
SOFTWARE
VERSION
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Do not bypass the draft safeguard switch, as an unsafe condition could
exist which must be corrected.
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
20
Masonry Chimney Requirement
NOTE: These furnaces are CSA design-certified for use in exterior
tile-lined masonry chimneys with a factory accessory Chimney Adapter
Kit. Refer to the furnace rating plate for correct kit usage. The Chimney
Adapter Kits are for use with ONLY furnaces having a Chimney Adapter
Kit number marked on the furnace rating plate.
If a clay tile-lined masonry chimney is being used and it is exposed to
the outdoors below the roof line, relining might be required. Chimneys
shall conform to the Standard for Chimneys, Fireplaces, Vents, and Solid
Fuel Burning Appliances ANSI/NFPA 211 in the United States and must
be in good condition.
U.S.A. – Refer to Sections 13.1.8 and 13.2.20 of the NFPA 54/ANSI
Z223.1 or the authority having jurisdiction to determine whether relining
is required. If relining is required, use a properly sized listed metal liner,
Type-B vent, or a listed alternative venting design.
NOTE: See the NFPA 54/ANSI Z223.1 13.1.9 and 13.2.20 regarding
alternative venting design and the exception, which cover installations
such as our Chimney Adapter Kits which are listed for use with these
furnaces. See Specification Sheet for accessory listing.
A10133
Fig. 33 – Chimney Inspection Chart
The Chimney Adapter Kit is a listed alternative venting system for these
furnaces. See the kit instructions for complete details.
This furnace is permitted to be vented into a clay tile-lined masonry
chimney that is exposed to the outdoors below the roof line, provided:
1. Vent connector is Type-B double-wall, and
2. This furnace is common vented with at least 1 draft hood equipped
appliance, and
3. The combined appliance input rating is less than the maximum
capacity given in Table 6, and
4. The input rating of each space heating appliance is greater than the
minimum input rating given in Table 6 for the local 99% Winter
Design Temperature. Chimneys having internal areas greater than
38 sq. in. (24516 sq. mm) require furnace input ratings greater than
the input ratings of these furnaces. See footnote at bottom of
Table 6, and
5. The authority having jurisdiction approves.
If all of these conditions cannot be met, an alternative venting design
shall be used, such as the listed chimney adapter kit with a furnace listed
for use with the kit, a listed chimney-lining system, or a Type-B common
vent.
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected
to the venting system being placed into operation could result in carbon
monoxide poisoning or death.
The following steps shall be followed for each appliance connected to
the venting system being placed into operation, while all other
appliances connected to the venting system are not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and horizontal pitch, as
required in the National Fuel Gas Code, NFPA 54/ANSI Z223.1
and these instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies, which could
cause an unsafe condition.
3. As far as practical, close all building doors and windows and all
doors between the space in which the appliance(s) connected to
the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the
venting system. Turn on any exhaust fans, such as range hoods and
bathroom exhausts, so they are operating at maximum speed. Do
not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being
inspected into operation. Adjust the thermostat so appliance is
operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft
hood relief opening after 5 minutes of main burner operation. Use
the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the
venting system must be corrected in accordance with the National
Fuel Gas Code, NFPA 54/ANSI Z223.1.
9. After it has been determined that each appliance connected to the
venting system properly vents when tested as outlined above,
return doors, windows, exhaust fans, fireplace dampers and any
other gas-fired burning appliance to their previous conditions of
use.
CHIMNEY INSPECTION CHART
For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211
Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances
Consult
Par t C of
chimney adapter venting
instructions for
application
suitability
Is chimney
lined with properly
sized, listed liner or
Type-B vent?
Is chimney
to be dedicated to
a single
furnace?
Chimney
exposed to
outdoors below
roof line?
Repair
liner or top seal
or reline chimney as
necessary.
Mortar
or tile
debris?
Clay
tile misalignment,
missing sections,
gaps?
Debris
in cleanout?
Mortar, tile, metal vent,
fuel oil residue?
Is
liner and top
seal in good
condition?
Is chimney
property lined with
clay tile liner?
Crown
condition:
Missing mortar
or brick?
Rebuild
crown.
Ye s
Ye s
No
No
No Reline
Ye s Repair
Ye s
Ye s
Ye s
No
No
Remove mortar
and tile debris
Remove metal vent
or liner.
No
No
No
No
Ye s
Ye s
Suitable
Suitable
Not Suitable
Line chimney with property
sized, listed flexible metal
liner or Type-B vent per
NFGC Vent
Sizing Tables and liner or
vent manufacturer’s
Installation instructions.
Install chimney
adapter per
instructions.
Chimney is
acceptable for use.
Install chimney
adapter per
instructions.
Consult
Par t B of
chimney adapter venting
instructions for
application
suitability.
Ye s
Not Suitable
Condensate
drainage at bottom
of chimney?
Ye s
No

This manual suits for next models

2

Popular Furnace manuals by other brands

Carrier 59SU5A manual

Carrier

Carrier 59SU5A manual

VERDER Carbolite Gero EVT 12/600B Installation, operation and maintenance instructions

VERDER

VERDER Carbolite Gero EVT 12/600B Installation, operation and maintenance instructions

Fire Chief FC500E operating manual

Fire Chief

Fire Chief FC500E operating manual

Lennox ML180UHE User's information manual

Lennox

Lennox ML180UHE User's information manual

Empire DV-210-7SG Installation instructions and owner's manual

Empire

Empire DV-210-7SG Installation instructions and owner's manual

Wood master MAXIM M255 PE owner's manual

Wood master

Wood master MAXIM M255 PE owner's manual

Payne C Series Installation, start-up, operating and service and maintenance instructions

Payne

Payne C Series Installation, start-up, operating and service and maintenance instructions

Empire Heating Systems GWT-25-3 Installation instructions and owner's manual

Empire Heating Systems

Empire Heating Systems GWT-25-3 Installation instructions and owner's manual

Lennox G32 SERIES User's information manual

Lennox

Lennox G32 SERIES User's information manual

Chinook c45-1-x Installation guide and owner's manual

Chinook

Chinook c45-1-x Installation guide and owner's manual

VERDER TZF 12/65/550 Installation, operation and maintenance instructions

VERDER

VERDER TZF 12/65/550 Installation, operation and maintenance instructions

Empire Heating Systems 3588-3 Installation and service manual

Empire Heating Systems

Empire Heating Systems 3588-3 Installation and service manual

Bryant PG96VTA Installation, start-up, operating and service and maintenance instructions

Bryant

Bryant PG96VTA Installation, start-up, operating and service and maintenance instructions

Dekema AUSTROMAT 624 operating instructions

Dekema

Dekema AUSTROMAT 624 operating instructions

Haier GE NF96DS installation instructions

Haier

Haier GE NF96DS installation instructions

Bryant 820TA Installation, start-up, operating and service and maintenance instructions

Bryant

Bryant 820TA Installation, start-up, operating and service and maintenance instructions

Rheem 97MDV060 Series installation instructions

Rheem

Rheem 97MDV060 Series installation instructions

Adams UFO Installation, maintenance & operating instructions

Adams

Adams UFO Installation, maintenance & operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.