Daikin 910193093 Operating instructions

Auto
Changeover
Programmable Thermostat
AUTO
SCHEDULE
COOL
FAN
COOL
MODE
PM OFF
Wed
• 7-Day, 5-2-Day, or 5-1-1- Day Programmable
• Configurable for Multiple Systems
• Large Display with Backlight
• Selectable Fahrenheit or Celsius
• Icon Indicator Lights
• Relay Outputs – Minimum Voltage Drop in
Thermostat
• WSHP Alarm Indicator
• Remote Sensor Compatible
• Ideally Suited for:
– Residential (New Construction/Replacement)
– Light Commercial
• Works with two-transformer systems
Installation, Operation
and Application Guide
www.daikinapplied.com 800-432-1342

2
Thermostat Controls
Left Arrow
(Go Back)
Alarm
Right Arrow
(Forward)
Down Arrow
Up Arrow
HomeMenu Mode (Heat/Cool) Fan Schedule
Package Contents/Tools Required
Package includes: Thermostat, base, wiring labels, screws, wall anchors, and Installation, Operation and Application Guide.
Tools required for installation: Drill with 3/16” bit, hammer, screwdriver
AUTO
SCHEDULE
COOL
FAN
COOL
MODE
PM OFF
Wed
Specifications
Electrical Rating: 24 VAC (18-30 VAC), 1 amp maximum per output terminal, 5 amp maximum total load
Temperature Control Range: 45°F to 90°F (7°C to 32°C) Accuracy: ±1°F (±0.5°C)
Anti-short Cycle: 4 minutes (bypass anti-short cycle delay by returning to OFF mode and pressing the icon)
Backlight Operations: 15 seconds DC Power: 3.0 VDC (2 “AA”Alkaline batteries)
Water Source Heat Pump Configurations:
Daikin P/N I3 Thermostats
910193093 2-stage heat, 2-stage cool, 2 speed fan
910193126 2-stage heat, 2-stage cool
910193127 2-stage heat, 3-stage cool
910193128 3-stage heat, 2-stage cool
910193129 2-stage heat, 2-stage cool, dehumidification

3
Mode of Operation
The thermostat is a programmable, manual or auto changeover, up to 3-stage heat (depending on your model) and up to
3-stage cool (depending on your model) thermostat. It functions with air conditioning, heat pumps, gas, oil, or electric heat
systems. The thermostat activates the heating appliance when the room temperature is below the set heat temperature (by the
differential temperature). When the call for heat has been satisfied, the outputs are turned off. With heat pumps, the thermostat
will not let the compressor come on for 4 minutes after it turns off to protect your compressor.
When the room temperature is greater than the set cool temperature (by the differential temperature), the cooling device is
activated. When the call for cooling has been satisfied, the outputs are turned off. The thermostat will not let the compressor
come on for 4 minutes after it turns off to protect your compressor.
The program schedule can be overridden by changing the set temperature ( or ). This puts the thermostat into a
temporary hold. To remove the temporary hold, press icon twice.
UP – Used to increase the time, set temperatures, and to adjust configuration settings.
DOWN – Used to decrease the time, set temperatures, and to adjust configuration settings.
MENU – Used to enter configuration, set the clock, lock the thermostat, or select viewing options.
CONFIG Sets up thermostat to work for specific systems.
CLOCK Set year, month, date, and time.
LOCK Allows you to lock the thermostat to prevent tampering.
VIEW Allows you to see the remote sensor temperatures, date, current schedule period, lock screen, filter
accumulated time, and show details (system status).
HUMIDITY (910193129 model only)
Allows you to view the current relative humidity and change humidity setpoint (10% to 80%).
FAN – Used to select between AUTO, ON, and HOURLY fan operation.
MODE – Used to select between OFF, HEAT, COOL, and AUTO changeover modes.
HOME – Wakes thermostat, returns to home screen, and enters changes into memory.
SCHEDULE – Used to edit program schedule, turn program on and off, and set vacation return dates.
ALARM – The water source heat pump Microtech III unit alarm will be displayed notifying the occupant that
service may be required.
Icon Functions

4
Important Safety Information
WARNING!:
Always turn off power at the main power supply before installing, cleaning, or removing thermostat.
• This thermostat is for 24 VAC applications only; do not use on voltages over 30 VAC.
• Do not short across terminals of gas valve or system control to test operation; this will damage your thermostat and void your
warranty.
• All wiring must conform to local and national electrical and building codes.
• Do not use air conditioning when the outdoor temperature is below 50 degrees; this can damage your A/C system and cause
personal injuries.
• Use this thermostat only as described in this manual.
ELECTRICAL SHOCK HAZARD
– Turn off power at the main service panel by removing the fuse or switching the
appropriate circuit breaker to OFF position before installing new thermostat.
IMPORTANT: Thermostat installation must conform to local and national building and electrical codes and ordinances.
Note: Mount the thermostat about five feet above the floor. Do not mount the thermostat on an outside wall, in direct
sunlight, behind a door, or in an area affected by a vent or duct.
1. Turn off power to heating & cooling system by removing the fuse or switching the appropriate circuit breaker off.
2. Put thermostat sub base against the wall where you plan to mount it (be sure wires will feed through the wire opening in
the sub base of the thermostat).
3. Mark the placement of the mounting holes.
To Install Thermostat
ELECTRICAL SHOCK HAZARD
– Turn off power at the main service panel by removing the fuse or switching the
appropriate circuit breaker to OFF position before removing the existing thermostat.
To Remove Existing Thermostat
1. Turn off power to heating & cooling system by removing the fuse or switching the appropriate circuit breaker off.
2. Remove cover of old thermostat; this should expose the wires.
3. Label the existing wires with the enclosed wire labels before removing wires.
4. After labeling wires, remove wires from wire terminals.
5. Remove existing thermostat base from wall.
6. Refer to the following section for instructions on how to install this thermostat.
A – Alarm
C – 24 VAC common
DH – Dehumidification
G – Low speed fan
G2 – High speed fan

5
4. Set thermostat sub base and thermostat away from working area.
5. Using a 3/16” drill bit, drill holes in the places you have marked for mounting.
6. Use a hammer to tap supplied anchors in mounting holes.
7. Use supplied screws to mount thermostat sub base to wall (make sure thermostat wire is through hole).
8. Insert stripped, labeled wires in matching wire terminals. Tighten screws to secure wires.
CAUTION!
: Be sure exposed portion of wires do not touch other wires.
9. Gently tug wire to be sure of proper connection. Double check that each wire is connected to the proper terminal.
10. Snap thermostat onto the sub base.
11. Turn on power to the system at the main service panel.
12. Configure thermostat to match the type of system you have.
13. Test thermostat operation as described in “Testing the Thermostat”.
Terminal Designator Descriptions
A – Alarm
C – 24 VAC common
DH – Dehumidification
G – Low speed fan
G2 – High speed fan
RC, RH – 24 VAC hot
SC, S1 – Remote sensor or outdoor sensor
W1 – 1st stage heat
W2 – 2nd stage heat
W3 – 3rd stage heat
Y1 – 1st stage cool
Y2 – 2nd stage cool
Y3 – 3rd stage cool
Note 1:
Not all terminals are used in every model.
Note 2:
A connection to 24VAC common (C) is required.

6
Wiring Diagrams

7
Wiring Diagrams (continued)

8
Wiring Diagrams (continued)

9
Remote Sensor Installation (Optional)
Terminals S1 and SC are used with a remote sensor. S1 can be used with a remote sensor to
monitor indoor temperatures. An indoor remote sensor is used to read the indoor temperature
in a different location. This is beneficial when the thermostat is not mounted in the ideal
location.
1. Remove cover from remote sensor housing.
2. Select an appropriate location for mounting the remote sensor.
3. Mount the remote sensor using hardware provided.
4. Install two-strand shielded wire between the S1 terminal on the remote sensor and the S1
terminal on the thermostat.
5. From the remote sensor, install a two-strand shielded wire from the common to the SC
terminal on the thermostat.
6. Configure the thermostat to work with the remote sensor.
Ordering Information:
Remote Sensor 1
– Indoor remote sensor: 107096001
Note:
Remote sensor reading
can be displayed by
pressing the icon.
Press , select
press

10
910193093 Output Chart
1st Cool 2nd Cool 1st Heat 2nd Heat
Water Source Heat Pump (w/ Low Speed Fan) Y1, G Y1, Y2, G W1, G W1, W2, G
Water Source Heat Pump (w/High Speed Fan) Y1, G2 Y1, Y2, G2 W1, G2 W1, W2, G2
Electric Y1, G Y1, Y2, G W1, G W1, W2, G
Electric (w/ High Speed Fan) Y1, G2 Y1, Y2, G2 W1, G2 W1,W2, G2
Heat Pump (One Compressor) Y1, G, O Y1, G, O Y1, G, B Y1, W2, G, B
Heat Pump (One Compressor w/ High Speed Fan) Y1, G2, O Y1, G2, O Y1, G2, B Y1, W2, G2, B
Heat Pump (Two Compressors) Y1, G, O Y1, Y2, G, O Y1, G, B Y1, Y2, G, B
Heat Pump (Two Compressors w/ High Speed Fan) Y1, G2, O Y1, Y2, G2, O Y1, G2, B Y1, Y2, G2, B
910193126 Output Chart
1st Cool 2nd Cool 1st Heat 2nd Heat
Water Source Heat Pump Y1, G Y1, Y2, G W1 W1, W2
Electric Y1, G Y1, Y2, G W1, G W1, W2, G
Heat Pump (One Compressor) Y1, G, O Y1, G, O Y1, G, B Y1, W2, G, B
Heat Pump (Two Compressors) Y1, G, O Y1, Y2, G, O Y1, G, B Y1, Y2, G, B
910193127 Output Chart
1st Cool 2nd Cool 3rd Cool 1st Heat 2nd Heat
Water Source Heat Pump Y1, G Y1, Y2, G Y1, Y2, Y3 W1 W1, W2
Electric Y1, G Y1, Y2, G Y1, Y2, Y3, G W1, G W1, W2, G
Heat Pump (One Compressor) Y1, G, O Y1, G, O Y1, G, O Y1, G, B Y1, W2, G, B
Heat Pump (Two Compressors) Y1, G, O Y1, Y2, G, O Y1, Y2, Y3, G, O Y1, G, B Y1, Y2, G, B

11
910193128 Output Chart
1st Cool 2nd Cool 1st Heat 2nd Heat 3rd Heat
Water Source Heat Pump Y1, G Y1, Y2, G W1 W1, W2 W1, W2, W3
Electric Y1, G Y1, Y2, G W1, G W1, W2, G W1, W2, W3, G
Heat Pump (One Compressor) Y1, G, O Y1, G, O Y1, G, B Y1, W2, G, B Y1, W2, W3, G, B
Heat Pump (Two Compressors) Y1, G, O Y1, Y2, G, O Y1, G, B Y1, Y2, G, B Y1, Y2, W2, G, B
910193129 Output Chart
1st Cool 2nd Cool 1st Heat 2nd Heat
Water Source Heat Pump Y1, G Y1, Y2, G W1 W1, W2
Electric Y1, G Y1, Y2, G W1, G W1, W2, G
Heat Pump (One Compressor) Y1, G, O Y1, G, O Y1, G, B Y1, W2, G, B
Heat Pump (Two Compressors) Y1, G, O Y1, Y2, G, O Y1, G, B Y1, Y2, G, B
Water Source Heat Pump w/ Humidity Control 910193129 Output Chart
(De)humidification 1st Cool 2nd Cool 1st heat 2nd heat Fan Only
WSHP DH Y1 Y1, Y2 W1 W1, W2 G

12
Configuration and Thermostat Lock
During Configuration Mode, certain settings are protected by a
numeric code access screen to prevent unintentional changes that
could potentially damage the system or create a dangerous condition.
Whenever changes are attempted to one of the
critical settings, the unlock code screen will appear:
The unlock code for these critical settings can be found during the
power-up sequence.
The large number (indicated by “98” in the diagram) is the code that
will unlock the desired configuration setting.
The smaller numbers (indicated by “93” and “82” in the diagram) are
codes used to lock and unlock your thermostat to prevent tampering.
To view the default codes for your thermostat, remove the thermostat from the sub base
for 10 seconds. Reinstalling thermostat will cause the codes to display for approximately 5 seconds.
Write your
codes here
Thermostat lock code
Configuration safety lock code
Locking & Unlocking Thermostat
Press , then , then
MENU
LOCK, then
Use & to select digit.
Use & to set number.
Press to lock or unlock.
LOCK
Enter Code
To lock and unlock thermostat, perform the following steps:

13
Configuration Mode
The configuration mode is used to set the thermostat to match your heating/cooling system. The thermostat functions with heat
pump, air conditioning, gas, oil, or electric heat systems. To configure the thermostat, perform the following steps:
Press , then press repeatedly until is selected.
Press to advance from one screen to the next.
Note: Pressing will return you to the previous screen.
Press the or to change settings within each screen. Changes are saved automatically.
To exit configuration mode, press . Auto exit occurs after two minutes with no icons touched.
To change the lock code, do the following:
1. Press , then press until Lock menu displays.
2. Enter the current lock codes. To find the current lock codes, follow the instructions under “Configuration and Thermostat
Lock”.
3. Press to enter new lock codes.
4. Enter new lock codes.
5. Press . The Lock Codes have been updated.
Note: Upon subsequent power ups, new lock codes will display.
Changing the Lock Code

14
Configuration Mode Settings
The setup screens for Configuration Mode are as follows:
1. Temperature Scale (F or C)
Choose Fahrenheit or Celsius.
Press the or to select.
Press to advance to the next screen.
CONFIG
2. 1st Stage Temperature Differential (1°F to 5°F) (0.5°C to 2.5°C)
Set the number of degrees between your “setpoint” temperature and your “turn on” temperature.
Press the or to set differential value.
Press to advance to the next screen.
CONFIG
3. 2nd Stage Temperature Differential (1°F to 5°F) (0.5°C to 2.5°C)
Set the number of degrees between when stage 1 turns on and when stage 2 turns on.
Press the or to set differential value.
Press to advance to the next screen.
CONFIG
4. 3rd Stage Temperature Differential (1°F to 5°F) (0.5°C to 2.5°C)
Set the number of degrees between when stage 2 turns on and when stage 3 turns on.
Press the or to set differential value.
Press to advance to the next screen.
CONFIG
Note: Only for 910193127, 910193128

15
6. Minimum Deadband (1°F to 9°F) (1°C to 5°C)
Set the minimum separation between heat setpoint and cool setpoint in Auto Changeover Mode.
Press the or to set deadband value.
Press to advance to the next screen.
CONFIG
5. Staged Off Outputs
Select whether the outputs for heating and cooling are staged off independently or are
satisfied simultaneously.
= Outputs off simultaneously. = Outputs staged off independently.
Note: For 2 compressor heat pumps and multi-stage gas/oil systems, stage 3 is staged off
independently when SO is set to .
Press the or to set.
Press to advance to the next screen.
CONFIG
7. Heat Source: There are six heat source settings:
WARNING!
:
Incorrect settings can damage system and/or cause potentially dangerous conditions. Use the code
described in Configuration and Thermostat Lock.
CONFIG
Note: Daikin Water Source Heat Pumps require setting “9” for proper operation.
Water Source Heat Pump
8. Auxiliary Delay ON (0-60 minutes)
Set the delay time in minutes for auxiliary heat to be locked out after a call for second stage. This
extra savings feature is used to temporarily lock out auxiliary heat devices, allowing just heat pump to
try to satisfy heat call.
Press the or to select.
Press to advance to the next screen.
CONFIG
HEAT

16
9. Lockout (0-8°, SLEEP, COOL-HEAT)
Select the number of degrees set temperature can be changed during keypad lockout. SLEEP
setting locks thermostat only during the sleep period to prevent after hours tampering. COOL-HEAT
lockout allows adjustment of the set temperatures to the maximum heat set temperature selected and
minimum cool set temperature selected.
Note: The mode cannot be changed while the thermostat is locked.
Press the or to select.
Press to advance to the next screen.
CONFIG
10. Maximum Heat Setpoint (45°F to 90°F) (7°C to 32°C)
Adjust to control the maximum heat set temperature allowed.
Press the or to select.
Press to advance to the next screen. CONFIG
HEAT
11. Minimum Cool Setpoint (45°F to 90°F) (7°C to 32°C)
Adjust to control the minimum cool set temperature allowed.
Press the or to select.
Press to advance to the next screen. CONFIG COOL
13. Vacation Heating Setpoint
These work in conjunction with the Schedule mode where you set the date and time of your
RETURN from vacation (Page 28).
Until that date/time, system will remain at the heating setpoint specified here.
Press the or to select.
Press to advance to the next screen.
CONFIG
HEAT
VACATION
12. Vacation Cooling Setpoint
These work in conjunction with the Schedule mode where you set the date and time of your
RETURN from vacation (Page 28).
Until that date/time, system will remain at the cooling setpoint specified here.
Press the or to select.
Press to advance to the next screen.
CONFIG COOL
VACATION

17
14. Room Temperature Offset (+9°F to -9°F) (+4.5°C to -4.5°C)
Adjust to calibrate displayed room temperature to match actual room temperature.
Press the or to select.
Press to advance to the next screen. CONFIG
CONFIG
15. Maximum Cycles Allowed Per Hour (- -, 2-6)
= as many as needed, 2-6 = maximum cycles/hour
Press or to select.
Press to advance to the next screen.
WARNING!
:
Incorrect settings can damage system and/or cause potentially dangerous
conditions. Use the code described in Configuration Safety Lock to access this screen setting.
16. Temperature Sensor (L, r, A, r sleep)
Note: If there is no remote sensor, option 1 (L) must be selected. May only be used with remote
temperature sensor 1.
CONFIG
Appears only for non-heat pump systems and heat pumps without an outdoor sensor.
1. L – Only on-board sensor determines room temperature.
2. r – Only remote sensor determines room temperature.
3. A – Average temperature of on-board and remote sensor.
4. r Sleep – Only on-board sensor will be used until SLEEP period, and then only remote sensor is used for SLEEP period.
Press the or to select. Press to advance to the next screen.
17. Fan Delay Off Time (0, 30, 60, 90 seconds)
Select the amount of time the fan continues to operate after the cool/heat demand has been
satisfied. Functions for cooling, heat pumps and electric heat.
Press or to select.
Press to advance to the next screen.
CONFIG

18
CONFIG
HUMIDITY
20. Condition to Turn On
Set the condition for system to follow:
Humidication
No = No condition other than humidity reading below setpoint and differential will turn on the
humidier.
HEAT = Heat must be energized in order for the humidier to turn on.
HEAT-FAN: Either the heat or the fan must be energized in order for the humidier to turn on.
Dehumidication
No = No condition other than humidity reading above setpoint and differential will turn on the dehumidier.
COOL-FAN = Either the cooling system or the fan must be energized in order for the dehumidier to turn on.
COOL-no = Cooling system cannot be energized in order for the dehumidier to turn on.
Press or to select.
Press to advance to the next screen.
CONFIG
HUMIDITY
%RH
19. Humidity Differential (1% to 10%)
Set the percent difference between the setpoint humidity and when the humidier or dehumidier
system turns on.
Press or to select.
Press to advance to the next screen.
CONFIG
HUMIDITY
18. Humidication/Dehumidication (Hu, dE)
Set system conguration to work with a humidier or dehumidier (including air conditioner).
Note: Incorrect settings can damage system and/or cause potentially dangerous conditions.
Use the code described in Conguration Safety Lock to access this screen setting.
Hu: used with a humidier to humidify home.
dE: used with air conditioner or dehumidier to dehumidify home.
Press or to select.
Press to advance to the next screen.
Note: Humidity option is only available on 910193129 model only.

19
23. Hourly Cycle Fan Operation (1-30 minutes per hour)
Used in conjunction with the Fan HOURLY mode. When the user selects this option, the fan will
turn on at the beginning of every hour and run for the number of minutes indicated here.
Press or to select.
Press to advance to the next screen.
CONFIG
HOURLY
24. Fan on Schedule (OFF, WAKE, LEAVE, RETURN, SLEEP)
The fan will run continuously during this scheduled period when the mode is not set to OFF. To
turn on the fan during one of the scheduled periods (WAKE, LEAVE, RETURN, SLEEP), please
do the following:
Press or to select.
Press to advance to the next screen.
CONFIG
ON
SCHEDULEFAN
OFF
22. Relay Operation (dehumidication only)
Set the relay function to match your system (normally open, normally closed).
Press or to select.
Press to advance to the next screen.
CONFIG
HUMIDITY
CONFIG
HUMIDITY
21. Extended AC (no, COOL -2 (Fahrenheit), COOL -1 (Celsius))
Note: Only used for Dehumidication when condition is set to COOL-FAN.
Set an extended time on the AC to increase dehumidication capabilities.
no = No extended AC time.
COOL -2 or COOL -1 = Cooling system will continue to operate after the set temperature has
been reached until the room temperature is 3°F (1.5°C) below the set
temperature if dehumidication has not been satised.
Press or to select.
Press to advance to the next screen.

20
26. Reset Check Filter Timer
Used to reset the elapsed number of (fan running) hours for the Check Filter Timer.
Press or to select (YES).
Press to advance to the next screen. CONFIG
RESET
Check
Filter
25. Check Filter Timer (800-2500 hours)
After the number of (fan running) hours specified (for example, 1200 hours), the words “CHECK
FILTER” will display to remind you to check/change the system filter. The next configuration screen is
where the elapsed number of run hours can be reset.
Press or to select.
Press to advance to the next screen.
CONFIG
Check
Filter
Setting the Time and Date
1. Press , then press until CLOCK is displayed.
2. Press to enter date/time setting. Year blinks.
3. Press or to select the year.
4. Press to save value and move to month.
5. Press or to select the month.
6. Press to save value and move to day.
7. Press or to select the day.
8. Press to save value and move to hour.
9. Press or to select the hour.
Note: As you move past 12:00, the AM/PM symbol will
change automatically.
10. Press to save the value and move to minutes.
11. Press or to select the minutes.
12. Press to exit Time/Date setting.
This manual suits for next models
4
Table of contents