
Electronic Temperature Control Settings & Specications
Description
TheRancoElectronictemperaturecontrol(ETC)isdesignedto
provide on/off control for heating and cooling. It is equipped with a
liquidcrystaldisplay(LCD)thatprovidesaconstantreadoutofthe
sensed temperature, and a touch keypad that allows the user to easily
and accurately select the set of point temperature, differential and
heating/cooling mode of operation.
Programing steps and display
TheETCcanbeprogrammedinfoursimplestepsusingtheLCD
display and three keys on the face of the control.
STEP 1 To start programming press the SET key once to access the
Fahrenheit/Celsiusmode.TheDisplaywillshowthecurrent
status, either F for degrees Fahrenheit or C for degrees
Celsius. Then press either the up or down arrow key to
toggle between the F or C designation.
STEP 2 Press the SET keyagaintoaccessthesetpoint.TheLCD
will display the current set-point and the S1 indicator will
be blinking on and off to indicate that the control is in the
set point mode. Then press either the up key to increase
or the down key to decrease the set-point to the desired
temperature.
STEP 3 Press the SETkeyagaintoaccessthedifferential.TheLCD
will display the current differential and the DIF1 indicator will
be blinking on and off to indicate that the control is in the
differential mode. Then press the up key to increase or the
down key to decrease the differential to the desired setting.
STEP 4 Press the SET key again to access the cooling or heating
mode.TheLCDwilldisplaythecurrentmode,eitherC1 for
cooling or H1 for heating. Then press either the up or down
key to toggle between the C1 or H1 designation. (This
setting must remain at H1 for proper furnace operation
and temperature regulation.) Press the SET key once more
and programming is complete.
NOTE: The ETC will automatically end programming if no keys are
pressed for thirty seconds. Any settings that have been changed on the
control will be stored at that point.
Step Indicator Description
1 F or C Fahrenheit or Celsius Scale
2 S1 blinking Setpoint Temperature
3 DIF1blinking DifferentialTemperature
4 C1/H1 Cooling or Heating Mode
Troubleshooting Error Messages
DisplayMessage
E1 Appears when either the up or down key is pressed when not in
the programming mode.
To correct: If the E1 message appears even when no keys are
being pressed replace the control.
E2 Appears if the control settings are not properly stored in memory.
To correct: Re-set all settings. If the display continues to show E2,
replace the control.
EP Appears when the probe is open, shorted, or sensing a
temperature that is out of range
To correct: Check to see if the sensed temperature is out of
range. If not, check for probe damage by com paring it to a
known ambient temperature between –30°F and 220°F. Replace
the control if necessary.
EE Appears if the EEPROM data has been corrupted.
To correct:Thisconditioncannotbeeldrepaired.Replacethe
control.
CL Appears if calibration mode has been entered.
To correct:Removepowertothecontrolforatleastve
seconds. Reapply power. If the CL message still appears, replace
the control
Specications
InputVoltage: 120or208/240VAC(24VACoptional),
50/60 Hz
Temperature Range: 30°F to 220°F
DifferentialRange: 1°Fto30°
Sensor: Thermistor,1.94in.Longx.025in.Dia.with
8 ft. cable
Power Consumption: 120/208/240 VAC: 100 Milliamps
24 VAC: 2-6 VA