ICM Controls ICM455 General instructions

ICM455
Important Safety Information
HIGH VOLTAGE WARNING!
– Turn off power at the
main service panel before installing.
Programmable,
Three-Phase
Voltage Monitor
Phase Unbalance Protection
• Voltage Unbalance: 2-20%, adjustable
Over/Under Voltage
• Under Voltage: 2-25%, adjustable
• Over Voltage: 2-25%, adjustable
Phase Loss Protection
• Phase Loss Condition: Equals 25% of nominal for any given phase; system will
shut down and a fault will be recorded if this should occur.
Delay on Break Timer
• Control Voltage: 18-240 VAC
• Time Delay: 15 seconds to 10 minutes
Fault Interrogation Delay
• Time Delay: 0 – 15 seconds, adjustable
• Provides a delay between fault detection and system shutdown—helps to eliminate
nuisance trips and unnecessary shutdowns.
Parameters
Installation
1.Turnoffpoweratmainservicepanel.
2.Usingtwo(2)#8screws,mounttheICM455inacool,dry,easilyaccessible
locationinthecontrolpanel.
3.Connectvoltageasshownin“WiringDiagram”.Leaveexistinglineandloadside
connectionsintactonthecontactor.
4.Loadsidemonitoringisoptional(unitmaybeusedtomonitorlinesideonly).Wire
thecontactorandoptionalcontrolvoltagemonitorasshownin“SystemDiagram”.
Note:Load/line wire must be rated for 3-phase voltage rating, 20ga minimum.
5.Uponapplicationofpower,theICM455willbeonlineandwillbegintomonitor
thesystem.
 Note:If voltage is not correct, see “Voltage Read Calibration” in Button
Functions section
• Terminals3and4arethecontrolsignalinputterminals.
• “ControlMode”isturnedONorOFFinsetup.
• With“ControlMode”settoON,theremustbeavoltagepresentonterminals3
and4fortherelayoutputterminals1and3toclose;thisvoltagecanbesupplied
fromathermostat,pressureswitch,etc.
• Whenthevoltageonthesesterminalsisre-applied,theunitwillnotre-energize
untilthedelayonbreak(0-10minutes)timehaselapsed.
• Useofterminals3and4isoptional;theywillbeignoredifthe“ControlMode”is
switchedtoOFF.
• Terminals1and3are“dry”,normallyopencontacts.
• Terminals1and3areclosedwhenpoweriswithinspecications.
• Terminals1and3openwhenthereisafaultcondition.
• Terminals1and3openwhenthereisalossofthecontrolsignalwith“Control
Mode”settoON.
• Auxiliaryterminalswillbeusedinfuturemodels.
Setting the Parameters
1.PressthegreenSETUPbuttontoenterthesetupmode.SetupLEDwilllight.
2.Usethe and buttonstochangeuserparameters.
3.ScrollthroughsetupbypressingandreleasingtheSETUPbutton.
4.Whenthelastparameterhasbeenset,thephaseaveragewillbedisplayedand
thesetupLEDwillautomaticallyturnoff.
Output Voltage Condition
8VDC PhaseLoss
7VDC PhaseReversal
6VDC UnderVoltage
5VDC OverVoltage
4VDC PhaseImbalance
2VDC LoadEnergized
0VDC NoPowertoUnit
Output Conditions
Button Functions
Press to return to home screen, which alternates between line voltage
and phase average.
Press arrow to scroll through and select parameter settings in Setup
Mode.
Voltage Read Calibration:
Hold both down to calibrate line voltage. Fault and setup LEDs will flash.
Usethe and buttonstoadjust.Press SETUP to exit calibration.
Press to enter Setup Mode and select user parameters. Setup LED
illuminates when in Setup Mode.
Press to read faults. Hold for 5 seconds to clear faults and reset memory.
Fault light will blink when fault has been added to memory.
Press and hold to reset system due to system error – this will not reset
the parameters.
To turn backlight on, press any button.
Specifications
Input
• Line Voltage: 190 – 630 VAC
• Frequency: 50 – 60 Hz
• Load Side Monitoring: Optional
• Control Voltage: 18 – 240 VAC
Control Operating Temperature
• Operating Temperature: -40°F to 167°F (-40°C to 75°C)
• Storage Temperature: -40°F to 185°F (-40°C to 80°C)
LCD Operating Temperature
• Operating Temperature: -4°F to 167°F (-40°C to 75°C)
Mechanical
• Mounting: Surface mount using two (2) #8 screws
• Terminations: Screw terminals
• Dimensions: 5.5”L x 4.5”W x 1.5”H
Output
• Type: Relay, SPDT
• Voltage Range: 240 VAC at 10A max
• Frequency: 50 – 60 Hz
• Remote Monitor Voltage: 0 – 10 VDC
Typical System Diagram
NO NC COM
CONTROL
VOLTAGE
18-240 VAC
REMOTE
MONITORING
AUX1 AUX2 AUX3 AUX4 -
+
0-10VDC
Thermostat
or Pressure
Switch
Load
Contactor
Control
Voltage
Wiring Diagram
Contactor
Fault Conditions
Fault Problem Corrective Action
Line Over
Voltage
Averagephase-phasevoltageexceedsthemaximum
percentage
1.Checksystemforover-voltagecause.
2.Increasethepercentover-voltagesettingifnecessary.
3.Increasefaultlineinterrogationifnecessary.
Line Phase
Loss
Notallthreeofthephasesonthelinesidearepresent 1.PressandholdtheREADbuttononthephasemonitororuseanACvoltmetertocarefullymeasure
allthreephase-phaselinevoltages(ex:Line1 Line2,Line2 Line3,Line3 Line1).
2.Repairthemissingphase.
Line Phase
Reversal
Lines1,2,or3arenotinsequence(not120°phaseshifted) 1.TurnOFFpower.
2.Swapany2phasesonthelinesideoftheIMC455(example:swapLine1andLine2).*
3.Re-applypower.
Line Phase
Unbalance
Avoltageunbalancebetweenthethreelinephasesexceeds
theunbalancedsetpoint
1.PresstheREADbuttontoobservethepresentlinevoltages.Checksystemforunbalancecause.
2.Increasefaultinterrogationtimeifnecessary.
3.Increasethepercentunbalancesettingifnecessary.
Line Under
Voltage
Averagephase-phasevoltageinbelowtheminimum
percentage
1.Checksystemforunder-voltagecause.
2.Increasethepercentageunder-voltagesettingifnecessary.
3.Increasefaulttimeinterrogationifnecessary.
Load
Phase
Loss
Notallthreeofthephasesontheloadsidearepresent 1.Re-energizethecontactor.
2.Ifthefaultreappearsaftertheloadenergizes:
 a.TurnallpowerOFF.
 b.Checkallloadsideconnections.
 c. Checkthecontactsofthecontactorfordamage,debris,orexcesscarbon.
Load
Phase Rev
Loads1,2,or3arenotinsequence(not120°Phase
Shifted)
1.TurnOFFallpower.
2.Swapany2phasesontheloadsideoftheICM455only(example:swapload1and2).*
3.Re-applypower.
Load
Phase
Unbalance
Avoltageunbalancebetweenthethreeloadphases
exceedstheunbalancesetpoint
1.PresstheREADbuttontoobservethepresentloadvoltages.Checksystemforunbalancecause.
2.Increasethefaultinterrogationtimeifnecessary.
3.Increasethepercentunbalancesettingifnecessary.
Brownout Allthreephaseslost(0V) Checksystemsupplyvoltageforcauseofvoltageloss
*ONLYswapphasesduringinitialsetup,notaftertheICM455hasbeeninoperationwithouterrors.
Pressandreleasefaultbuttontoscrollthroughallsavedfaults.
Note:For initial setup, press and hold FAULT for 5 seconds to remove any previously stored faults.
Parameter Description Range Default Recommended
Line Voltage Averagephasetophaselinevoltage. 190–630V 208V NamePlate
Voltage
Delay on
Break
Amountoftimebetweentheloadde-energizingandre-energizing. 0–10
minutes
15seconds 4minutes**
Delay on Fault Amountoftimebeforetheloadde-energizesduetoanon-criticalfault.* 0–15
seconds
15seconds 7-8seconds**
% Over/Under
Voltage
Maximum/Minimumphasetophaseaveragevoltage,respectively. 2–25% 20% 12-15%
% Phase
Unbalance
Amountofallowablevoltageunbalance. 2–20% 20% 4-5%**
Reset Mode AUTOornumberoftimestheloadcanbere-energizedafteraloadsidefaultbeforeamanualresetis
necessary.
Note:When monitoring line side only, the reset mode will always be AUTO.
AUTOor
1–10retries
AUTOretries AUTOretries
Control Mode WhencontrolmodeissettoOFF,theloadwillenergizeifno3-phasefaultconditionexists.Withcontrolmode
ON,theloadwillenergizeifnofaultconditionsexistandcontrolvoltageispresentatterminals3and4.
ONorOFF ON Basedonwiring
Set Date/Time Setdateandtimeinordertostorefaultsinrealtime.Whenrstpoweredon,orafteralongpoweroutage,you
willbepromptedtosetthedateandtimewhenSETUPispressed.
ONorOFF ON Basedonwiring
* Non-criticalfaultsarefaultssuchasHigh/LowVoltageandPhaseUnbalance.Criticalfaults,suchasPhaseLossandPhaseReversal,haveafaultinterrogationofunder2
secondsanditisnotuseradjustable.
** Forbestrecommendations,consultmanufacturerofequipment.
Parameters
Troubleshooting
Parameter LCD Readout LED Status Corrective Action
Line voltage is not correct PhaseAverage N/A Usecalibrationmethoddescribedin“ButtonFunctions”.
Load will not energize PhaseAverage AllLEDsoff. Conrmthatthecontrolinput(terminals3and4)isproperlyconnectedandcongured.
Load will not energize PhaseAverage LoadLEDoff,
FaultLEDblinking
PressFAULToncetoobservethecurrentfault;correcttheconditionoftherstfault
thatappears(seeFaultConditionsaboveforalistofcorrectiveactions.
Fault LED blinks repeatedly
while load is energized
PhaseAverage FaultLEDblinking,
LoadLEDon.
Indicatestherearefaultssavedinthememory,pressFAULTrapidlytoscrollthrough
savedfaults;toclearthefaults,pressandholdFAULTformorethan5seconds.
Load will not de-energize
when control voltage is OFF
PhaseAverage LoadLEDon,
ControlLEDoff
Thecontrolmodesettingisoff;pressSETUPtogettothecontrolmode.Press to
setcontrolmodeon.
Setup LED is on while load
is being energized
AnythingOtherThanPhase
Average
SetupLEDon,
LoadLEDon
Toexitsetupmode,presseitherREADorFAULT.
Load will not energize Reset FaultLEDblinking Unitinlockout;maximumnumberofretiresinmanualresetmodehasbeenreached.To
resetunit,pressFAULT andholdformorethan5seconds.
Load turns on and off
repeatedly
ReadoutisIrrelevant FaultLEDblinking Fixloadsidefault.PressFAULTtoobservecondition;thedelayonbreakperiodmay
betooshort;pressSETUPtoenterthedelayonbreakmode;press tolengthenthe
delay.
7313 William Barry Blvd., North Syracuse, NY 13212
(Toll Free)800-365-5525(Phone)315-233-5266(Fax)315-233-5276
www.icmcontrols.com
ONE-YEAR LIMITED WARRANTY
TheSellerwarrantsitsproductsagainstdefectsinmaterialorworkmanshipforaperiodofone(1)yearfromthedateof
manufacture.TheliabilityoftheSellerislimited,atitsoption,torepair,replaceorissueanon-casecreditforthepurchase
pricesofthegoodswhichareprovidedtobedefective.Thewarrantyandremediessetforthhereindonotapplytoany
goodsorpartsthereofwhichhavebeensubjectedtomisuseincludinganyuseorapplicationinviolationoftheSeller’s
instructions,neglect,tampering,improperstorage,incorrectinstallationorservicingnotperformedbytheSeller.In
ordertopermittheSellertoproperlyadministerthewarranty,theBuyershall:1)NotifytheSellerpromptlyofanyclaim,
submittingdatecodeinformationoranyotherpertinentdataasrequestedbytheSeller.2)PermittheSellertoinspectand
testtheproductclaimedtobedefective.ItemsclaimedtobedefectiveandaredeterminedbySellertobenon-defective
aresubjecttoa$30.00perhourinspectionfee.ThiswarrantyconstitutestheSeller’ssoleliabilityhereunderandisinlieu
ofanyotherwarrantyexpressed,impliedorstatutory.Unlessotherwisestatedinwriting,Sellermakesnowarrantythat
thegoodsdepictedordescribedhereinaretforanyparticularpurpose. LIAF214-1

Other ICM Controls Monitor manuals

ICM Controls ICM450A General instructions

ICM Controls

ICM Controls ICM450A General instructions

ICM Controls ICM450 User guide

ICM Controls

ICM Controls ICM450 User guide

ICM Controls ICM450A General instructions

ICM Controls

ICM Controls ICM450A General instructions

Popular Monitor manuals by other brands

Broadcast Tools Silence Monitor III Plus Installation and operation manual

Broadcast Tools

Broadcast Tools Silence Monitor III Plus Installation and operation manual

Philips 170S2B Manual de uso

Philips

Philips 170S2B Manual de uso

Philips MGD203 user manual

Philips

Philips MGD203 user manual

Lenovo Q27h-20 Assembly instructions

Lenovo

Lenovo Q27h-20 Assembly instructions

LG 34WN750-B.AAU owner's manual

LG

LG 34WN750-B.AAU owner's manual

Asus VN289QL Series user guide

Asus

Asus VN289QL Series user guide

Radar Electronics Preco Electronics PVM500 Operating & installation guide

Radar Electronics

Radar Electronics Preco Electronics PVM500 Operating & installation guide

Samsung SyncMaster 730MP Service manual

Samsung

Samsung SyncMaster 730MP Service manual

Dell UltraSharp U2717D user guide

Dell

Dell UltraSharp U2717D user guide

Philips BRILLIANCE 170P5 user manual

Philips

Philips BRILLIANCE 170P5 user manual

Acer P225HQ owner's manual

Acer

Acer P225HQ owner's manual

NEC MultiSync EA221WM user manual

NEC

NEC MultiSync EA221WM user manual

Samsung IER Series user manual

Samsung

Samsung IER Series user manual

Philips LTC 2814/90 installation instructions

Philips

Philips LTC 2814/90 installation instructions

Samsung SyncMaster T220M Service manual

Samsung

Samsung SyncMaster T220M Service manual

Asus VA325H Series user guide

Asus

Asus VA325H Series user guide

Microtek JTX V5 user guide

Microtek

Microtek JTX V5 user guide

Acer Z301C quick start guide

Acer

Acer Z301C quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.