ICM Controls ICM455 General instructions

ICM455
Important Safety Information
HIGH VOLTAGE WARNING!
– Turn off power at the
main service panel before installing.
Programmable,
Three-Phase
Voltage Monitor
Phase Unbalance Protection
• Voltage Unbalance: 2-20%, adjustable
Over/Under Voltage
• Under Voltage: 2-25%, adjustable
• Over Voltage: 2-25%, adjustable
Phase Loss Protection
• Phase Loss Condition: Equals 25% of nominal for any given phase; system will
shut down and a fault will be recorded if this should occur.
Delay on Break Timer
• Control Voltage: 18-240 VAC
• Time Delay: 15 seconds to 10 minutes
Fault Interrogation Delay
• Time Delay: 0 – 15 seconds, adjustable
• Provides a delay between fault detection and system shutdown—helps to eliminate
nuisance trips and unnecessary shutdowns.
Parameters
Installation
1.Turnoffpoweratmainservicepanel.
2.Usingtwo(2)#8screws,mounttheICM455inacool,dry,easilyaccessible
locationinthecontrolpanel.
3.Connectvoltageasshownin“WiringDiagram”.Leaveexistinglineandloadside
connectionsintactonthecontactor.
4.Loadsidemonitoringisoptional(unitmaybeusedtomonitorlinesideonly).Wire
thecontactorandoptionalcontrolvoltagemonitorasshownin“SystemDiagram”.
Note:Load/line wire must be rated for 3-phase voltage rating, 20ga minimum.
5.Uponapplicationofpower,theICM455willbeonlineandwillbegintomonitor
thesystem.
Note:If voltage is not correct, see “Voltage Read Calibration” in Button
Functions section
• Terminals3and4arethecontrolsignalinputterminals.
• “ControlMode”isturnedONorOFFinsetup.
• With“ControlMode”settoON,theremustbeavoltagepresentonterminals3
and4fortherelayoutputterminals1and3toclose;thisvoltagecanbesupplied
fromathermostat,pressureswitch,etc.
• Whenthevoltageonthesesterminalsisre-applied,theunitwillnotre-energize
untilthedelayonbreak(0-10minutes)timehaselapsed.
• Useofterminals3and4isoptional;theywillbeignoredifthe“ControlMode”is
switchedtoOFF.
• Terminals1and3are“dry”,normallyopencontacts.
• Terminals1and3areclosedwhenpoweriswithinspecications.
• Terminals1and3openwhenthereisafaultcondition.
• Terminals1and3openwhenthereisalossofthecontrolsignalwith“Control
Mode”settoON.
• Auxiliaryterminalswillbeusedinfuturemodels.
Setting the Parameters
1.PressthegreenSETUPbuttontoenterthesetupmode.SetupLEDwilllight.
2.Usethe and buttonstochangeuserparameters.
3.ScrollthroughsetupbypressingandreleasingtheSETUPbutton.
4.Whenthelastparameterhasbeenset,thephaseaveragewillbedisplayedand
thesetupLEDwillautomaticallyturnoff.
Output Voltage Condition
8VDC PhaseLoss
7VDC PhaseReversal
6VDC UnderVoltage
5VDC OverVoltage
4VDC PhaseImbalance
2VDC LoadEnergized
0VDC NoPowertoUnit
Output Conditions
Button Functions
Press to return to home screen, which alternates between line voltage
and phase average.
Press arrow to scroll through and select parameter settings in Setup
Mode.
Voltage Read Calibration:
Hold both down to calibrate line voltage. Fault and setup LEDs will flash.
Usethe and buttonstoadjust.Press SETUP to exit calibration.
Press to enter Setup Mode and select user parameters. Setup LED
illuminates when in Setup Mode.
Press to read faults. Hold for 5 seconds to clear faults and reset memory.
Fault light will blink when fault has been added to memory.
Press and hold to reset system due to system error – this will not reset
the parameters.
To turn backlight on, press any button.
Specifications
Input
• Line Voltage: 190 – 630 VAC
• Frequency: 50 – 60 Hz
• Load Side Monitoring: Optional
• Control Voltage: 18 – 240 VAC
Control Operating Temperature
• Operating Temperature: -40°F to 167°F (-40°C to 75°C)
• Storage Temperature: -40°F to 185°F (-40°C to 80°C)
LCD Operating Temperature
• Operating Temperature: -4°F to 167°F (-40°C to 75°C)
Mechanical
• Mounting: Surface mount using two (2) #8 screws
• Terminations: Screw terminals
• Dimensions: 5.5”L x 4.5”W x 1.5”H
Output
• Type: Relay, SPDT
• Voltage Range: 240 VAC at 10A max
• Frequency: 50 – 60 Hz
• Remote Monitor Voltage: 0 – 10 VDC
Typical System Diagram
NO NC COM
CONTROL
VOLTAGE
18-240 VAC
REMOTE
MONITORING
AUX1 AUX2 AUX3 AUX4 -
+
0-10VDC
Thermostat
or Pressure
Switch
Load
Contactor
Control
Voltage
Wiring Diagram
Contactor

Fault Conditions
Fault Problem Corrective Action
Line Over
Voltage
Averagephase-phasevoltageexceedsthemaximum
percentage
1.Checksystemforover-voltagecause.
2.Increasethepercentover-voltagesettingifnecessary.
3.Increasefaultlineinterrogationifnecessary.
Line Phase
Loss
Notallthreeofthephasesonthelinesidearepresent 1.PressandholdtheREADbuttononthephasemonitororuseanACvoltmetertocarefullymeasure
allthreephase-phaselinevoltages(ex:Line1 Line2,Line2 Line3,Line3 Line1).
2.Repairthemissingphase.
Line Phase
Reversal
Lines1,2,or3arenotinsequence(not120°phaseshifted) 1.TurnOFFpower.
2.Swapany2phasesonthelinesideoftheIMC455(example:swapLine1andLine2).*
3.Re-applypower.
Line Phase
Unbalance
Avoltageunbalancebetweenthethreelinephasesexceeds
theunbalancedsetpoint
1.PresstheREADbuttontoobservethepresentlinevoltages.Checksystemforunbalancecause.
2.Increasefaultinterrogationtimeifnecessary.
3.Increasethepercentunbalancesettingifnecessary.
Line Under
Voltage
Averagephase-phasevoltageinbelowtheminimum
percentage
1.Checksystemforunder-voltagecause.
2.Increasethepercentageunder-voltagesettingifnecessary.
3.Increasefaulttimeinterrogationifnecessary.
Load
Phase
Loss
Notallthreeofthephasesontheloadsidearepresent 1.Re-energizethecontactor.
2.Ifthefaultreappearsaftertheloadenergizes:
a.TurnallpowerOFF.
b.Checkallloadsideconnections.
c. Checkthecontactsofthecontactorfordamage,debris,orexcesscarbon.
Load
Phase Rev
Loads1,2,or3arenotinsequence(not120°Phase
Shifted)
1.TurnOFFallpower.
2.Swapany2phasesontheloadsideoftheICM455only(example:swapload1and2).*
3.Re-applypower.
Load
Phase
Unbalance
Avoltageunbalancebetweenthethreeloadphases
exceedstheunbalancesetpoint
1.PresstheREADbuttontoobservethepresentloadvoltages.Checksystemforunbalancecause.
2.Increasethefaultinterrogationtimeifnecessary.
3.Increasethepercentunbalancesettingifnecessary.
Brownout Allthreephaseslost(0V) Checksystemsupplyvoltageforcauseofvoltageloss
*ONLYswapphasesduringinitialsetup,notaftertheICM455hasbeeninoperationwithouterrors.
Pressandreleasefaultbuttontoscrollthroughallsavedfaults.
Note:For initial setup, press and hold FAULT for 5 seconds to remove any previously stored faults.
Parameter Description Range Default Recommended
Line Voltage Averagephasetophaselinevoltage. 190–630V 208V NamePlate
Voltage
Delay on
Break
Amountoftimebetweentheloadde-energizingandre-energizing. 0–10
minutes
15seconds 4minutes**
Delay on Fault Amountoftimebeforetheloadde-energizesduetoanon-criticalfault.* 0–15
seconds
15seconds 7-8seconds**
% Over/Under
Voltage
Maximum/Minimumphasetophaseaveragevoltage,respectively. 2–25% 20% 12-15%
% Phase
Unbalance
Amountofallowablevoltageunbalance. 2–20% 20% 4-5%**
Reset Mode AUTOornumberoftimestheloadcanbere-energizedafteraloadsidefaultbeforeamanualresetis
necessary.
Note:When monitoring line side only, the reset mode will always be AUTO.
AUTOor
1–10retries
AUTOretries AUTOretries
Control Mode WhencontrolmodeissettoOFF,theloadwillenergizeifno3-phasefaultconditionexists.Withcontrolmode
ON,theloadwillenergizeifnofaultconditionsexistandcontrolvoltageispresentatterminals3and4.
ONorOFF ON Basedonwiring
Set Date/Time Setdateandtimeinordertostorefaultsinrealtime.Whenrstpoweredon,orafteralongpoweroutage,you
willbepromptedtosetthedateandtimewhenSETUPispressed.
ONorOFF ON Basedonwiring
* Non-criticalfaultsarefaultssuchasHigh/LowVoltageandPhaseUnbalance.Criticalfaults,suchasPhaseLossandPhaseReversal,haveafaultinterrogationofunder2
secondsanditisnotuseradjustable.
** Forbestrecommendations,consultmanufacturerofequipment.
Parameters
Troubleshooting
Parameter LCD Readout LED Status Corrective Action
Line voltage is not correct PhaseAverage N/A Usecalibrationmethoddescribedin“ButtonFunctions”.
Load will not energize PhaseAverage AllLEDsoff. Conrmthatthecontrolinput(terminals3and4)isproperlyconnectedandcongured.
Load will not energize PhaseAverage LoadLEDoff,
FaultLEDblinking
PressFAULToncetoobservethecurrentfault;correcttheconditionoftherstfault
thatappears(seeFaultConditionsaboveforalistofcorrectiveactions.
Fault LED blinks repeatedly
while load is energized
PhaseAverage FaultLEDblinking,
LoadLEDon.
Indicatestherearefaultssavedinthememory,pressFAULTrapidlytoscrollthrough
savedfaults;toclearthefaults,pressandholdFAULTformorethan5seconds.
Load will not de-energize
when control voltage is OFF
PhaseAverage LoadLEDon,
ControlLEDoff
Thecontrolmodesettingisoff;pressSETUPtogettothecontrolmode.Press to
setcontrolmodeon.
Setup LED is on while load
is being energized
AnythingOtherThanPhase
Average
SetupLEDon,
LoadLEDon
Toexitsetupmode,presseitherREADorFAULT.
Load will not energize Reset FaultLEDblinking Unitinlockout;maximumnumberofretiresinmanualresetmodehasbeenreached.To
resetunit,pressFAULT andholdformorethan5seconds.
Load turns on and off
repeatedly
ReadoutisIrrelevant FaultLEDblinking Fixloadsidefault.PressFAULTtoobservecondition;thedelayonbreakperiodmay
betooshort;pressSETUPtoenterthedelayonbreakmode;press tolengthenthe
delay.
7313 William Barry Blvd., North Syracuse, NY 13212
(Toll Free)800-365-5525(Phone)315-233-5266(Fax)315-233-5276
www.icmcontrols.com
ONE-YEAR LIMITED WARRANTY
TheSellerwarrantsitsproductsagainstdefectsinmaterialorworkmanshipforaperiodofone(1)yearfromthedateof
manufacture.TheliabilityoftheSellerislimited,atitsoption,torepair,replaceorissueanon-casecreditforthepurchase
pricesofthegoodswhichareprovidedtobedefective.Thewarrantyandremediessetforthhereindonotapplytoany
goodsorpartsthereofwhichhavebeensubjectedtomisuseincludinganyuseorapplicationinviolationoftheSeller’s
instructions,neglect,tampering,improperstorage,incorrectinstallationorservicingnotperformedbytheSeller.In
ordertopermittheSellertoproperlyadministerthewarranty,theBuyershall:1)NotifytheSellerpromptlyofanyclaim,
submittingdatecodeinformationoranyotherpertinentdataasrequestedbytheSeller.2)PermittheSellertoinspectand
testtheproductclaimedtobedefective.ItemsclaimedtobedefectiveandaredeterminedbySellertobenon-defective
aresubjecttoa$30.00perhourinspectionfee.ThiswarrantyconstitutestheSeller’ssoleliabilityhereunderandisinlieu
ofanyotherwarrantyexpressed,impliedorstatutory.Unlessotherwisestatedinwriting,Sellermakesnowarrantythat
thegoodsdepictedordescribedhereinaretforanyparticularpurpose. LIAF214-1
Other ICM Controls Monitor manuals
Popular Monitor manuals by other brands

Samsung
Samsung SyncMaster 150MP Owner's instructions

TSI Instruments
TSI Instruments PRESSURA RPM10 Installation instructions and safety information

NEC
NEC AccuSync AS221F user manual

Dahua Technology
Dahua Technology LS UCM-EF Series user manual

NEC
NEC MultiSync LCD1512 user manual

Sports Radar
Sports Radar DL431 instruction manual