manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ICM Controls
  6. •
  7. Semiconductor
  8. •
  9. ICM Controls ICM291 User guide

ICM Controls ICM291 User guide

Popular Semiconductor manuals by other brands

Honeywell CD3000M-2PH user manual

Honeywell

Honeywell CD3000M-2PH user manual

GigaDevice Semiconductor AN055 Application note

GigaDevice Semiconductor

GigaDevice Semiconductor AN055 Application note

GOWIN GW2A Series user guide

GOWIN

GOWIN GW2A Series user guide

GOWIN DK-GoAI-GW2A55PBGA484 user guide

GOWIN

GOWIN DK-GoAI-GW2A55PBGA484 user guide

GOWIN GW1N Series Programming and Configuraion Guide

GOWIN

GOWIN GW1N Series Programming and Configuraion Guide

Cypress CY8CKIT-049-4 Series manual

Cypress

Cypress CY8CKIT-049-4 Series manual

Geokon 3810A instruction manual

Geokon

Geokon 3810A instruction manual

Philips AN10369 Application note

Philips

Philips AN10369 Application note

Hotenda MPC8349EA Technical data

Hotenda

Hotenda MPC8349EA Technical data

NXP Semiconductors AN10365 Application note

NXP Semiconductors

NXP Semiconductors AN10365 Application note

Fujitsu F2MC-16L Series user guide

Fujitsu

Fujitsu F2MC-16L Series user guide

BIRD 8931A400-115 Operation manual

BIRD

BIRD 8931A400-115 Operation manual

Arrow verical CYPRESS CY8CKIT-049-42 Series Kit Guide

Arrow

Arrow verical CYPRESS CY8CKIT-049-42 Series Kit Guide

Texas Instruments SimpleLink CC2640 user guide

Texas Instruments

Texas Instruments SimpleLink CC2640 user guide

Southchip SC8913 EVM user guide

Southchip

Southchip SC8913 EVM user guide

Toshiba TPC8402 Handbook

Toshiba

Toshiba TPC8402 Handbook

Keithley 4200-SCS user manual

Keithley

Keithley 4200-SCS user manual

Toshiba Semiconductor Handling guide

Toshiba

Toshiba Semiconductor Handling guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

7313 William Barry Blvd.
North Syracuse, NY 13212
ICM CONTROLS 800.365.5525
www.icmcontrols.com LIAF098
FEATURES
• DirectSparkIgnition(DSI)controlboard
• Microprocessor-based
• Controlscombustion,blowerandindoormotors;sparkignitor;andthegasvalve
• Monitorstiming,trialforignition,amesensingandlockout
• 100%lockoutsafetyfeature
• CompatiblewithLPorNaturalGas
• StatusLEDforfaultcodestoaidintroubleshooting
• Replaces:CarrierLH33WP003A
Install New Control
1. Groundyourself.Whenhandlingcircuitboard,holditbytheedges.
2. Fastencircuitboardwithretainingscrews.
3. Connectalllinevoltage,lowvoltage,andaccessorywires.
4. Verifythesequenceofoperation.
Safety Considerations
Onlytrainedpersonnelshouldinstallorserviceheatingequipment.Whenworkingwithheating
equipment,besuretoreadandunderstandallprecautionsinthedocumentation,onlabels,andon
tagsthataccompanytheequipment.Failuretofollowallsafetyguidelinesmayresultindamageto
equipment,severepersonalinjuryordeath.
Introduction
TheICM291DSIgasignitioncontrolreplacesthefollowingCarriermodel:LH33WP003A.The
ICM291hasincorporatedLEDdiagnosticstoassistintroubleshooting.Faultcodeinformationcanbe
foundinthisapplicationguide.Pleasekeepthisapplicationguidewiththefurnaceinstallationmanual
forfuturereference.
Electrostatic Discharge (ESD) Precautions
CAUTION!
Use caution when installing and servicing the furnace to avoid and control electrostatic discharge;
ESD can impact electronic components. These precautions must be followed to prevent
electrostatic discharge from hand tools and personnel. Following the precautions will protect the
control from ESD by discharging static electricity buildup to ground.
1. Disconnectallpowertothefurnace.Donottouchthecontrolorthewiringpriortodischargingyour
body’selectrostaticchargetoground.
2. Togroundyourself,touchyourhandandtoolstoaclean,metal(unpainted)furnacesurfacenear
thecontrolboard.
3. Servicethefurnaceaftertouchingthechassis.Yourbodywillrechargewithstaticelectricityasyou
shufeyourfeetormovearound,andyoumustregroundyourself.
4. Regroundyourselfifyoutouchungroundeditems.
5. Beforehandlinganewcontrol,regroundyourself;thiswillprotectthecontrol.Storeusedandnew
controlsinseparatecontainersbeforetouchingungroundedobjects.
6. ESDdamagecanalsobepreventedbyusinganESDservicekit.
CAUTION!
To service control, and prior to disconnection, label all wires. Failure to do so may result in wiring
errors that can cause dangerous operation.
1. TurnthermostattoOFFpositionorsetittothelowestpossiblesetting.
2. TurnOFFelectricalsupplytofurnace.
3. TurnOFFgassupplytofurnace.
CAUTION:Failuretoturnoffgasandelectricsuppliescanresultinexplosion,re,death,or
personalinjury.
4. Removefurnaceblowerandcontrolaccessdoors.
5. Disconnectthermostatwiresandhumidierwires(ifequippedwithahumidier).
6. Disconnectlinevoltage,blower,electronicaircleanerwires(ifequipped),andtransformerwires.
7. Removescrewsandanyotherfasteners,andtheoldcircuitboard.
8. Examinecontrolandcontrolboxtocheckforwaterstains.
9. Makerepairsifanysourcesofwaterleakagearefound.Besuretocheckhumidiers,evaporator
coils,andventsystemsintheareaofthecontrol.
Remove Existing Control
SPECIFICATIONS
• Controlvoltage:24VAC(18-30VAC),60Hz
• Linevoltage:208/230VAC,60Hz
• Powerconsumption: 0.3Aplusgasvalvecurrentat24VAC
• OperatingTemperature: -40°C(-40°F)to75°C(176°F)
Timing
• Pre-purge:45seconds
• TrialforIgnition:5+2seconds
• Retryperiod:every20sec.for15min.
• Lockout:manualreset
• Post-purge:45seconds
Inputs
• Power:RTandC
• Thermostatinterface:R,WandG
• Safetyswitches:RS,LS,andCS
• CombustionmotorHallEffectsensor
• FlameSensing
Outputs
• Spark
• GasValve:GV
• Combustionmotor:CM
• Blowermotor:BM
• Indoorfanmotor:IFO
LEDindicators
• RedLED: SteadyON-normaloperation
  Flashing-faultcodes
ICM291
Gas Ignition Control Board
AWcallfromtheT’statwillengagethecombustionmotor.Ignitionsequencebegins,gasvalveand
sparkareengaged,providingthatsystemsafetyswitches(RS,LS,andCS)areclosedandthereis
feedbackfromthecombustionmotorHallEffectsensor.Theblowerandindoormotorswillengage45
secondsafterameisestablishedandsensed.Theydisengage45secondsafterWcallissatised.
AGcallfromtheT’statwillengageblowerandindoormotorsrightaway.Theydisengage25seconds
afterGcallisremoved.
Sequence of Operation
Flamenotestablished
1. Ifameisnotestablishedduringthe5+2initialsequencethenthecontrolwillstartthenexttrialfor
ignitionin20seconds.
2. Theattempttoignitewillcontinuefor15minutesbeforetherespectivefaultcodeistriggeredand
ignitiontrialsarestopped.
3.Thegasvalveisenergizedonlyduringtheignitionsequenceof5+2seconds.
4. Blowerandindoorfanmotorsareoffuntilameisestablishedand45secondslater.
Flameout
1. Flameoutisconsideredwhenameislostduringheating.
2. WhenWsignalispresentandameissensedoutthenthesparkwillstartrightaway.
3. Ifameisnotestablishedontheimmediatesequence(2above)thenthecontrolwillcontinue
attemptsevery20secondsfor15minutesbeforetherespectivefaultcodeistriggeredandignition
trialsarestopped.
4. Blowerandindoorfanmotorswillcontinuerunningduringameoutscenariofor15minutes+45
seconds.
5.Combustionmotorremainsonthroughouttheameoutscenario.
Flameoutofsequence
1. FlameoutofsequencerepresentsascenariowhenameissensedwhileWsignalisnotpresent.
2. Combustion,blowerandindoorfanmotorswillbeengaged(ifnotalreadyrunning)rightawayand
keeprunningforaslongasthefaultconditionispresent.
3. Theunitisoperablebutwilldisplaythefaultcodeconstantlyuntilreplacedbyanotherfaultcodeor
powerreset.
NosignalfromtheHallaffectsensor
1. OnaWcall,iftheinputfromtheHallaffectsensor(RA0)isnotpresentformorethanaminute,
thenthecombustionmotorwillcontinuerunningendlesslyandtherespectivefaultisashed.
2. DuringrunningstateiftheinputfromtheHallaffectsensorisnotsensedthenthegasvalvewill
shutoffrightaway,blowerandindoorfanmotorswillcontinuerunningfor30secondsandthen
turnoff,combustionmotorrunscontinuously.
Troubleshooting Tips
LED Fault Codes
#OfFlashes
representsConstant
ONNormal
operation
Results
1Thecontrolhasmodiedthefanondelayto0andoffdelayto3minutes
duetosensingLStripwithin10minutesofacall
2a) LSisopenduetohightemperature(fanisn’tworkingscenario)
b) Theunitwillnotstartatrialforignitionuntiltheswitchclosesback
3
a) Flamesensedoutofsequence.
b) Theunitisoperable,howeverwilldisplaythisfaultcodeuntilpower
resetoranothercode
4a) LSopened4consecutivetimesduringacallforheating
b) ThefaultcodeisresetonthenextWcall
5a) Ignitionlockout.Thecontroltriedunsuccessfullytoignitefor15minutes
b) Theunitwillnotoperate.Requirespowerreset
6a) ThecombustionmotorisnotsensedrunningORCSopen
b) Theunitwillnotoperate.Requirespowerreset
7a) RStripped
b) Theunitwillnotoperate.Requirespowerreset
8a) Internalcontrolfault(softwareselfcheck)
Typical Wiring Diagram
LEGEND
Field Splice
Terminal (marked)
Terminal (unmarked)
Splice
Splice (marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To Indicate Common Potential
Only: Not to Represent Wiring
BR Blower Relay
C Contactor
CAP Capacitor
COMP Compressor Motor
CR Combustion Relay
EQUIP Equipment
FS Flame Sensor
FU Fuse
GND Ground
GVR Gas Valve Relay
HPS High Pressure Switch
HS Hall Effect Sensor
HV TRAN High Voltage Transformer
I Ignitor
ICM Integrated Control Motor
IDM Induced Draft Motor
IFM Indoor Fan Motor
IGC Integrated Gas Unit
Controller
IMR Indoor Motor Relay
LPS Low Pressure Switch
LS Limit Switch
MGV Main Gas Valve
OFM Outdoor Fan Motor
QT Quadruple Terminal
RS Rollover Switch
TRAN Transformer