14.04-11
Section E: 2100-D Wiring & Installation.
THE 2100-D IS TO BE INSTALLED AND SERVICED BY SERVICE PERSONNEL ONLY. NOOPERATOR / USER SERVICEABLE PARTS.
All power and signals must be de-energised before connecting any wiring, or altering any Jumpers or Dip Switches.
Donotstartthe Microscan before programming in a unique station number.Refer ‘Station Number Programmingand
Serial Number’.
Mounting.
* Also refer to Connection Diagrams and Notes.
(1) Mount in a clean environment in an electrical cabinet on 35mm Symmetrical mounting rail.
(2) Draft holes must have minimum free air space of 20mm. Foreign matter must not enter or block draft holes.
(3) Do not subject to vibration or excess temperature or humidity variations.
(4) Avoid mounting in cabinets with power control equipment.
(5) To maintain compliance with the EMC Directives the 2100-D is to be mounted in a fully enclosed steel fire
cabinet. The cabinet must be properly earthed, with appropriate input / output entry points and cabling.
Cover Removal and Fitting
Toremove2100covers,firmlypushdownthebuttoninthemiddleofoneendplate,andpulltheendplateoutwards,while
pulling the cover up and out.
To fit the cover, first make sure the cover is being fitted the correct way around, (Terminal 82 on the cover is above 82
onthe board.)andthat theserialnumberontheboardmatchestheserialnumberon thecover(if applicable).Slideone
endofthecoverintotheslotintheendplate.Pulltheotherendplateoutwardsandpushthecoverdownuntilitslidesinto
the slot of this endplate. Check both ends are firmly held.
Power Supply Wiring.
(1) Areadilyaccessibledisconnectdeviceanda1A,250Vacovercurrentdevice,mustbeinthepowersupplywiring.
(2) For power supply, connect Phase (or +Ve) to terminal 82, Neutral (or -Ve) to 81, and Earth to 80. To ensure
compliance to CE Safety requirements, the grey terminal insulators must be fitted to ALL mains terminals after
wiring is completed. (ie. terminals 82, 81 and 80.) For Non Hazardous Voltage power supplies (not exceeding
42.4Vpeak or 60Vdc) terminals 81 and 80 may be linked together, instead of connecting an earth.
RS422/485 Comms Signal Cabling.
(1) Useonly lowcapacitance,twisted pair,overallscreened datacable.Thecablemustequalorbetterthefollowing
specifications.
NOTE: All cables are to be subject during manufacture to in-process spark testing @ 4kVrms.
All cables are to be tested between conductors and conductors to screen for 1min @ 1500Vrms.
(2) Minimum cable pairs: RS422 = 2. (Plus overall screen.) RS485 = 1. (Plus overall screen.)
(3) Take care not to stress or damage cables during installation.
(4) Total length of trunk line, including spurs, is not to exceed 1200m without isolating boosters.
(5) Terminating resistors -1kΩ.
(6) Cabling paths should avoid sources of radio frequency interferences such as fluorescent lights, variable speed
motor drives, welding equipment, radio transmitters, etc.
(7) There should be a minimum of 200mm physical separation between power cables and data cables.
(8) Datacablesshouldnotbeexposedtoexcessiveheatormoisture,andshouldnotbeburieddirectlyintheground
withoutprotection.
(9) Avoid powering a remote station or controller from the same power supply as a variable speed drive.
(10) All unused twisted pairs should be terminated at both ends with 1kΩ resistors. DO NOT ground unused pairs.
.snoitacificepSelbaC
.eziSrotcudnoC GWA42,mm02.0/7
.C02@ecnatsiseRrotcudnoC 9.8 Ωm001/
.egatloVgnikroW.xaM smrV003
.riapafoseriwneewtebecnaticapaC 05 ρm/F
.rehtegotdehcnubsrehtollaoteriwhcaeneewtebecnaticapaC 59 ρm/F
:sriapneewtebklat-ssorC zHk1@ zHk001@ m001/Bd09-> m001/Bd05->
.ecnadepmIcitsiretcarahC zHk001@ 531 Ω
:riapafonoitaunettA
zHk1@ zHk01@ zHk001@ zHk05@ zHM1@ zHM5.1@
m001/Bd51.0 m001/Bd24.0 m001/Bd8.0 m001/Bd9.0 m001/Bd9.1 m001/Bd4.2