
O
1/27/2021
Kele, Inc. • 3300 Brother Blvd. • Memphis, TN 38133
3 ELECTRICAL I
The controller is not equipped with a power switch; it is operational whenever sufficient power is applied to the
power input terminals.
All electrical connections to the controller are made through screw terminals that can be unplugged
landing of wires. The controll
installation; refer to Figure 1 and
3.1 ANALOG OUTPUT C
The sensor’s readings are reported at the controller’s
20mA analog output connections.
Current flows out of the ‘+’
terminal and returns to the ‘-
The oxygen sensor
output is provided at the terminal
Figure 3
. Analog output connection has polarity as labeled on the
controller silkscreen: care must be taken to ensure proper
connection. To wire the analog output connections:
1.
Power down the controller, this can be done by unplugging
the control
2.
Unplug the analog output screw terminal
3. Attach the signal wires,
paying close attention to the
polarity.
4.
Plug the analog output screw terminal back into the
controller.
3.2 RELAY C
The controller has two, 10 Amp, 120
relay output connections (shown In
loads up to 10 Amps.
The relay connections have three
connectors that allow devices to be wired to the controller in
normally-open (NO) or normally-
outputs are activated when ambient air
below
the controller threshold settings (refer to
information).
In the NO Configuration
, the voltage attached to the
be present at the COM terminal
activated.
In the NC Configuration
, the voltage attached to the
the relay output is deactivated:
the voltage attached to the NC terminal is removed when the relay output is
activated.
S-2 Oxygen Sensor
Kele, Inc. • 3300 Brother Blvd. • Memphis, TN 38133
The controller is not equipped with a power switch; it is operational whenever sufficient power is applied to the
All electrical connections to the controller are made through screw terminals that can be unplugged
conduit knockouts on all sides for flexibility during
2 for details and dimensions of the enclosures.
The sensor’s readings are reported at the controller’s
powered 4-
Current flows out of the ‘+’
.
output is provided at the terminal
highlighted in
. Analog output connection has polarity as labeled on the
controller silkscreen: care must be taken to ensure proper
connection. To wire the analog output connections:
Power down the controller, this can be done by unplugging
Figure 6).
Unplug the analog output screw terminal
labeled O1.
paying close attention to the
Plug the analog output screw terminal back into the
VAC rated, SPDT dry-contact
4) that can directly control
The relay connections have three
-terminal screw
connectors that allow devices to be wired to the controller in
either
NC) configuration. These
outputs are activated when ambient air
oxygen concentrations fall
the controller threshold settings (refer to
Section 4.2 for more
, the voltage attached to the
NO terminal will
the relay output is
, the voltage attached to the
NC terminal will be present at the COM
the voltage attached to the NC terminal is removed when the relay output is
FIGURE 3: Analog Output
Figure 4:
Page 3 of 14
The controller is not equipped with a power switch; it is operational whenever sufficient power is applied to the
All electrical connections to the controller are made through screw terminals that can be unplugged
for easy
conduit knockouts on all sides for flexibility during
only while
the voltage attached to the NC terminal is removed when the relay output is