FW821 Input-Output Module
DESCRIPTION
The input-Output module FW821 is a UL listed device
according to UL864 and ULC-S527 for Fire Protective
Signaling Systems for indoor use. FW821 provides one
24VDC output and in addition one feedback input switch.
The input line is monitored for open line faults and
ground faults and the contact must thus be wired with an
end of line resistor. The output line is monitored for open
line, short circuit faults, ground faults, external 24VDC
power source loss and an end of line resistor is needed
as well.
When the output is activated or the feedback is switched,
the device LED will indicate the event condition by fast
blinking.
A return to normal condition will cause the event to
disappear and the device LED indicator will return to the
red idle condition.
The FW821 is intelligent addressable and takes one
address on the Signaling Line Circuit (SLC) of the fire
alarm control panel.
SPECIFICATION
SLC Nominal Voltage
24VDC
SLC Voltage Range
15 to 28VDC
Standby Current
0.15 mA
Active Current (SLC)
0.26 mA
External Input Power Supply
24VDC (nominal)
External Input Power Supply
15.4 to 24.4VDC (range)
Active Current (Output)
80 mA, 0.35pf
Output Range
(Special Application)
15.0 to 24.0VDC
(Supplied by Model FW106
Auxiliary power output);
20.0 to 25.9VDC
(Supplied by Listed 24VDC
Regulated power supply).
Max. Line Impedance (Input)
25 Ω
Max. Line Impedance (Output)
1 Ω
Max. Impedance for Grounding
6.6 KΩ
Compatible EOLR
FW421 (10KΩ)
Operating Temperature
32°F to 120°F (0°C to 49°C)
Mounting
FW800 base
Operating Humidity
0% to 93% RH
Dimension
120mm(L) x120mm(W) x
45mm(H)
Weight (with back box)
9.2 oz (261g)
Wiring Gage
12 to 18 AWG
PROGRAMMING
The module must be programmed to a valid address
before use. A valid address means the address must be in
1~252 and can’t be duplicate with other device in same
loop. Please use the hand-held programmer ReadWritor
FW411 to set device address.
Disconnect wire at terminal 1, 2, 3 and 4 before
programming.
INSTALLATION
•Mount the base, FW800, onto a 2X4 or 4x4 electrical
box using the screws provided, as illustrated in Figure
1.
Figure 1 Installation Diagram
•Connect the wires, see Figure 2. There is polarity
sensitive between terminal 1 and terminal 2. The

DOC-FW821 -UM R1.0
Installation and Operation Manual
MAPLE ARMOR FIRE ALARM DEVICE CO., LTD.
8866 Boul. du Quartier, Brossard, Quebec, Canada J4Y 0R2
www.maplearmor.com
2/2
power source at terminal3 and terminal4 is polarity
sensitive as well.
EOLR
+
-
EXTERNAL INPUT POWER SUPPLY EOLR
FW821
1
2
3
4 5
6
7
8
FROM PANEL OR
PREVIOUS DEVICE
(+)
(-)
TO NEXT DEVICE
(+)
(-)
SIGNAL LINE CIRCUIT (SLC)
TWISTED PAIR IS RECOMMENDED
FEEDBACK
OUTPUT
+
-
Figure 2 Wiring Diagram
(Note1: polarity sensitive between terminal 1 and terminal 2, terminal
3 and terminal 4, terminal 6 and terminal 5.)
(Note2: All circuits are power-limited)
(Note3: The maximum line impedance for Feedback input circuit is 25
Ω. The maximum line impedance for output circuit is 1 Ω)
(Note4: External input power supply is either PCU AUX output of FACP
or Listed 24VDC Regulated/power-limited source with ground fault
detection.)
(Note5: An example of compatible device is door strike, Model 0563
from RUTHERFORD CONTROLS IN’L INC with “Fail secure”mode.
Acceptability should be determined by Authorities Having Jurisdiction.)
•Wire the SLC to the module as illustrated in Figure 3.
FW821
1
2
3
4 5
6
7
8
LB+
LB-
LA+
LA-
FACP
ALU
FW821
1
2
3
4 5
6
7
8
FW821
1
2
3
4 5
6
7
8
(a) Class A Circuit
FW821
1
2
3
4 5
6
7
8
LB+
LB-
LA+
LA-
FACP
ALU
FW821
1
2
3
4 5
6
7
8
FW821
1
2
3
4 5
6
7
8
(b) Class B Circuit
Figure 3 SLC Wiring Diagram
•Combine the assembled unit to the base using the
screws provided.
•Apply power to the control unit.
TESTING
1. Before testing, inform proper authorities that the
system is undergoing maintenance, and will temporarily
be put out of service. Disable the system to prevent
unwanted alarms.
2. Make sure the indicator LED on the module’s surface is
flashing. Failure to flash indicates a nonfunctioning
detector or faulty wiring. Check the wiring and remount
the device.
3. Trigger the input switch to activate a feedback signal.
The LED should turn to red fast blinking. Check the event
occurrence displayed on LCD of controller and verify it.
4. Restore the input switch to normal position. The LED
should turn to red idle condition. An output signal will
display on the FACP AMI interface.
5. Activate the output (you may need to make a related
control logic at first on control panel). The LED should
turn to red fast blinking.
6. Deactivate the output. The LED should turn to red idle
condition.
7. When testing is completed, set the system back to
normal operation and inform proper authorities.
MAINTENANCE
Return the device for repair if it fails to flash or alarm
during testing. Do not disassemble the module without
permission.
ATTENTION
The products must be installed in accordance with NFPA
72, CAN/ULC-S524 and CEC depending on country of
installation. Check information of equipment used in the
system by other manufacturers for any guidelines or
restrictions.
NOTE
Do not paint this device.
Any material extrapolated from this document or from
Maple Armor’s instructions or other documents
describing the product for use in promotional or
advertising claims, or for any other use, including
description of the product’s application, operation,
installation and testing is the sole responsibility of the
user. Maple Armor will not assume any liability for such
use. In no case will Maple Armor’s liability exceed the
purchase price paid for a product.
COPYRIGHT 2017 MAPLE ARMOR FIRE ALARM DEVICE
CO., LTD.
ALL RIGHTS RESERVED.
Table of contents
Popular I/O System manuals by other brands

Rockwell Automation
Rockwell Automation Allen-Bradley POINT I/O C Series installation instructions

Midas
Midas DL153 quick start guide

ICP DAS USA
ICP DAS USA I-7530A-MR-FD quick start

Emerson
Emerson FBxEdge user guide

Siemens
Siemens SIMATIC ET 200eco PN Equipment manual

M-system
M-system R3-AS8 instruction manual

Acromag
Acromag IP1K100 Series user manual

Toa
Toa SX-2000CI operating instructions

National Instruments
National Instruments SCC-PWR01 user guide

DirectLOGIC
DirectLOGIC DL105 manual

Future Desion Controls
Future Desion Controls VR18 Procedure of Replacing

Moxa Technologies
Moxa Technologies ioLogik 2500 Series manual