Midco economite RE4850BA Quick guide

Installation and Service Instructions
12 01
8471 24
Printed in U.S.A.
In the United States, Installation must
conform with local codes or, in the absence of local
codes, with Installation of the National Fuel Gas
Code, ANSI Z223.1-latest edition, from the American
National Standard Institute. Further reference should
be made to the recommendation of your fuel supplier.
In Canada,Installation must conform with local
codes or, in the absence of local codes, with
Installation Codes for Gas Burning Appliances and
Equipment, CGA Standard CAN/CGA 1B-149.
Further reference should be made to the
recommendation of your fuel supplier.
WARNING: Additions, changes, conversions,
and service must be performed by an authorized
MIDCO representative, service agency, or the fuel
supplier. Use only MIDCO specified and approved
parts.
INSTALLER: Inform and demonstrate to the user
the correct operation and maintenance of the gas
utilization equipment. Inform the user of the
hazards of storing flammable liquids and vapors in
the vicinity of this gas utilization equipment and
remove such hazards. Affix this manual and
associated literature adjacent to the burner. CODE
COMPLIANCE IS THE SOLE RESPONSIBILITY OF
THE INSTALLER.
USER: Retain this manual for future reference. If
other than routine service or maintenance as
described in this manual and associated literature
is required, contact a qualified service agency. DO
NOT ATTEMPT REPAIRS. An inadvertent service
error could result in a dangerous condition.
Economite
RE4850BA / RE4700BA
RE4400B / RE4400BA
Gas Burners
BURNER MODEL
BILL OF MAT'L
NUMBER
SERIAL CODE #
WIRING DIAGRAM
FOR SERVICE CONTACT:
Name
Address
Phone
Date of Installation
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS:
?Do not try to light any appliance.
?Do not touch any electrical switch;do not use any
phone in your building.
?Immediately phone your gas supplier from another
building. Follow the gas supplier’s instructions. If
you cannot reach your gas supplier call the fire
department.
Installation and service must be performed by a
qualified installer, service agency or the gas supplier.
The following terms are used to identify hazards, safety precaution of special
notations and have standard meanings throughout this manual. They are printed in all capital letters using a bold type face
as shown below, and preceded by the exclamation mark symbol. When you see the safety alert symbol and one of the
safety information terms as shown below, be aware of the hazard potential.
DANGER: Identifies the most serious hazards which will result in severe personal injury or death.
WARNING: Signifies a hazard that could result in personal injury or death.
CAUTION: Identifies unsafe practices which would result in minor personal injury or product and property damage.
WARNING: If the information in these instructions
is not followed exactly, a fire or explosion may result,
causing property damage, personal injury or death.
Midco International Inc.
4140 West Victoria St. - Chicago, Illinois 60646
tel 773.604.8700 fax 773.604.4070
Quality Designed for Proven Performance

Part 1 Installation
Specifications 1The ECONOMITE Models RE 4850BA, RE4700BA, RE4400B and RE4400BA burners
with intermittent spark ignited pilot are adaptable to most gas utilization equipment, including
gravity and forced circulation furnaces and boilers. They are particularly recommended for
firing horizontal or downdraft equipment since no draft is required to maintain a pilot. Power
burner design makes them perfectly suited for oil burner replacement, including rooftop and
industrial applications.
AIR DELIVERY (Approximate Air Delivery at Zero Draft)
RE 4850BA, RE4700BA, RE4400B AND RE4400BA -125 SCFM2
FIRING RATE (NATURAL OR PROPANE )3
RE 4850BA RE4700BA RE4400B RE4400BA
MAXIMUM MBH4850 700 400 400
MINIMUM MBH 280 230 132 132
GAS SUPPLY PRESSURE REQUIRED
NATURAL ............................................................. 7.0" to 14.0" W.C.
PROPANE ............................................................ 5.0" TO 14.0" W.C.
TUBE DIAMETER.................................................................. 4"
TUBE LENGTH...................................................................... 9"
RECOMMENDED COMBUSTION CHAMBER SIZE (AT MAX. BTU/HR)
RE 4850BA RE4700BA RE4400B RE4400BA
WIDTH 15" 15" 10" 10"
LENGTH 30" 25" 16.5" 16.5"
ELECTRICAL SUPPLY......................................120 VAC...........60 Hertz5
IGNITION CONTROL MODULE VOLTAGE ....... 24 VAC
FLAME SAFETY....Electronic Flame Safety with Spark Ignited Pilot and 100% Shut-Off6
TABLE 1: Burner Specifications
1. Standard burners are shipped as NATURAL gas models. Contact your Midco dealer for
PROPANE gas burners.
2. SCFM = Standard Cubic Feet / Minute.
3. All Ratings Based on 1000 BTU/Cu. Ft. NATURAL. Derate burner for altitude over 2,000
feet by 4% for each 1,000 feet above sea level.
4. 1 MBH = 1,000 BTU/hr.
5. For 50 Hertz applications the RE4850BA, RE4700BA, RE4400B and RE4400BA will be derated
by 20%. Contact the factory for details. NOTE: Burners rated for 50Hertz are not UL Listed.
6. See Section XII of Operational Sequence
CAUTION: The ECONOMITE Models RE4850BA, RE4700BA, RE4400B and
RE4400BA Burners are not intended for outdoor installation and must be protected
from excessive moisture. Provide adequate clearance for service and proper
operation.
If the former automatic oil burner gave trouble-free operation, it is probable that the heating
plant area has sufficient infiltration of air for combustion and dilution of flue gases.
Nevertheless, the area must be checked.
?Open basement or utility areas of normal construction, without storm windows or tight
doors, will generally allow sufficient air infiltration. However, if the heating plant is located in
a tight or separate room, ventilation to an open area as described above will be required.
Install two permanently open grills, each sized on the basis of one square inch free area per
1,000 BTU (but not less than 100 square inches) of the total input rating of all gas utilization
equipment in the combined space. One grille should be located within 12 inches of the
ceiling, the other within 12 inches of the floor.
?If the heating plant is located in an area of unusually tight construction, or if an exhaust
fan, kitchen ventilation system, clothes dryer and/or fireplace is installed in the building,
provisions must be made for an outside air supply near the heating appliance area. Install
permanently open grills sized at not less than one square inch free area per 4,000 BTU of
burner input. When ventilating through horizontal ducts, grills should be sized at not less
than one square inch free area per 2,000 BTU of burner input. In any case, the minimum
dimension of rectangular air ducts shall not be less than 3 inches.
?In Canada, for detailed ventilation requirements, refer to standard CAN 1-B149.1 or .2
and/or local codes.
Part 1
Installation
2
IVentilation

?Clean the gas utilization equipment combustion chamber, heat exchanger interior, and flue
connections. Remove all adhering tars, scale, dirt and soot. Inspect for actual or potential
leaks.
?Cement all joints, including those in the heating appliance base and around the door
frames, to prevent leakage into, or out of the combustion chamber.
?The access or firing door should open easily to relieve pressure. If positive latches exist,
they should be modified to permit easy opening; a spring loaded door holder is
recommended.
?On all boilers, make certain the pressure relief safety valve is in good operating condition.
A combustion chamber liner is normally required to protect non-heat transfer surfaces and to
provide a radiant bed for rapid heat transfer to the primary surfaces of the heat exchanger.
In most cases the existing chamber liner can be used, if in good condition.
?In the case of wet base boilers, where the entire firing chamber is comprised of heat
exchange surfaces and no chamber liner was provided for oil firing, a liner is usually not
required for the ECONOMITE. However, a liner or target wall may be necessary if the firing
chamber is unusually short, in order to avoid excess flame contact on the heat exchanger
walls or flueways.
?If a built up chamber liner is required, use 2,300°F minimum insulating material.
?The burner tube, or the stainless steel sleeve that is included with the burner, must be
sealed air tight into the combustion chamber opening with refractory material. The sleeve is
preferred as it is designed to properly locate the end of the tube relative to the inside wall of
the combustion chamber, and to permit burner removal without breaking the seal.
CAUTION: In no case should the burner tube be allowed to extend into the
chamber proper; it must be set at least 1" short of the inside surface because high
combustion chamber temperatures will cause premature pilot, electrode, burner tube
and sleeve deterioration.
WARNING: BURNER MUST BE MOUNTED IN ORIENTATION SHOWN IN
FIGURES 1 AND 2. ANY OTHER MOUNTINGS MAY CAUSE A DANGEROUS
CONDITION, AND WILL VOID BURNER WARRANTY AND AGENCY APPROVALS. NON-
STANDARD ARRANGEMENTS MAY BE AVAILABLE FOR SOME MODELS. CONSULT
FACTORY FOR DETAILS IF REQUIRED.
?Before permanently setting the burner in place, check that the main burner and pilot ports
are free of foreign materials, and also that the spark electrode assembly has not been
damaged or displaced. See Figures 7A and 7B.
WARNING: The chimney shall be inspected for unsafe conditions such as
deteriorated masonry and excessive soot or other blockage or potential blockage.
Installation must conform with local codes or in the absence of local codes with NFPA,
ANSI Z223.1 latest edition.
WARNING: The vent connector shall not be connected to a chimney already
venting solid fuel burning equipment, an incinerator or an open fireplace.
?The Vent Connector shall be made of non-combustible, corrosion resistant material
capable of withstanding the vent gas temperature produced by the gas utilization equipment
and of sufficient thickness to withstand physical damage.
?The Vent Connector shall be as short as possible. The entire length shall be readily
accessible for inspection, cleaning, and replacement.
?The length of horizontal uninsulated Vent Connector between the chimney and a single
gas utilization equipment shall not exceed 75% of the the height of the chimney above the
connector, or 100% if the Vent Connector is insulated.
3
Part 1
Installation
Continued
Part 1 Installation
II Preparation of
the Gas Utilization
Equipment
III Combustion
Chamber
IV Chimney, Vent
Connector and
Draft Control
Figure 1: Dry Base Boiler with Combustion
Chamber Liner (Warm Air Furnace
Construction is Similar)
Figure 2: Wet Base Boiler with Unlined
Combustion Chamber

?The Vent Connector shall be installed so as to avoid turns or other construction features
which create excessive resistance to flow of vent gas. It shall be installed without any dips or
sags and shall slope upward at least 1/4" per foot.
?A manually operated damper shall not be placed in the Vent Connector or chimney of
any gas utilization equipment.
?The Vent Connector shall be
firmly attached to draft hood outlets
and flue collars. Joints between
sections of connector piping shall
be fastened by sheet-metal screws
or other approved means. The Vent
Connector shall be supported for
the design and weight of the
material employed to maintain
clearance and prevent physical
damage and separation of joints.
?A draft hood or a barometric
draft regulator shall be installed in
the same room or enclosure as the
equipment in such a manner as to
prevent any difference in the
pressure between the hood or
regulator and the combustion air
supply (see Figures 3 and 4). In no
case shall the relief opening of the
draft hood or barometric draft
regulator be located at a point lower
than the top of the highest flue
passage in the equipment.
?Gas utilization equipment requiring controlled draft may be equipped with a listed double
acting barometric draft regulator, if approved by local codes (see Figure 4).
?A device which will automatically shut off gas to the burner in the event of sustained
backdraft is required. It shall be of the listed manual reset type and installed and adjusted by
a qualified service technician in accordance with the manufacturer’s instructions.
?Refer to gas utilization equipment manufacturer for recommended vent connection
requirements.
Part 1
Installation
Continued
4
Part 1 Installation
Figure 3: Recommended Locations for Draft Hoods
Figure 4: Location for Barometric Draft Regulators
Note: Figure 3 and 4 :
Copyright by American Gas Association.
Used by permission of the copyright holder.
IV Chimney, Vent
Connector and
Draft Control
Continued

CAUTION:Refer to wiring diagram located on the inside of the burner housing
cover or above wiring diagram.
Installation wiring and grounding to the burner must conform to local codes, or, in their
absence in the United States to National Electric Code, ANSI/NFPA No. 70 latest edition;
in Canada, to Canadian Electrical Code Part 1, CSA Standard C22.1
?Use copper wire not less than 14 gage for line voltage wiring. Hook up to a dedicated line
with an on-off disconnect switch and a minimum 10 Amp breaker.
?The frame of the burner should be well grounded. Normally the piping and/or electric
conduit will provide sufficient grounding. However, a ground lug is located in control box for
positive grounding where insulated pipe couplings are used or where any doubt exists
regarding grounding sufficiency.
?Confirm that the polarity is correct—hot wire to strip terminal L1, neutral L2—and that the
neutral line is not subject to induced low voltage (check L2 to earth ground) from other
equipment, as that can cause the Ignition Control Module to malfunction.
?Each installation must include suitable limit control(s). Existing oil burner combination
operating and limit controls are normally NOT SUITABLE for gas burner use.
?Connect motors used on forced air furnace fans or boiler pumps to a combination limit
control and switch.
?Set the thermostat heat anticipator for the total current draw handled by the thermostat.
The current draw of the ECONOMITE 24V operating circuit is 0.9 amps.
CAUTION: Label all wires prior to disconnection when servicing controls.
Wiring errors can cause improper and dangerous operation. Verify proper operation
after servicing.
CAUTION: The available gas pressure should be within the limits shown in
SPECIFICATIONS section. Excessive pressure may damage electric valves, regulators
and manual valves. If the supply pressure exceeds the 14.0"W.C. maximum, a suitable
high pressure regulator must be installed between the Main Manual Shut-Off Valve and
burner shut-off valve as shown in Figure 5.
5
Part 1
Installation
Continued
Part 1 Installation
VElectrical
VI Piping
Wiring Diagram
Capacities shown are for a
total pressure drop of
0.3"W.C. For 0.5"W.C.
pressure drop, multiply
capacity shown by 1.3 .
Propane capacities shown
are for a total pressure drop
of 0.5” W.C. For higher
permissible pressure drops,
consult your gas supplier.
Table 2: Schedule 40 NPT
Pipe-Capacity Chart
10
200
590
400
1075
900
40
275
200
500
450
1040
650
75
190
150
360
325
750
475
20
150
400
275
730
600
900
Pipe
Size
3/4
3/4
1
1
1 1/4
1 1/4
1 1/2
1 1/2
Natural
Propane
Natural
Propane
Natural
Propane
Natural
Propane
100
160
300
275
630
400
975
Approximate Capacity -MBH
Pipe Length
Type
of Gas

6
?The burner gas supply piping should branch off from the main line as close to the gas
meter as possible. Do not connect to the bottom of a horizontal section. Use new black pipe
and malleable fittings free of cutting and threading burrs or defects.
?Provide a sediment trap, union and 1/8" pressure tap in piping close to burner as shown
in Figure 5.
?Use pipe joint compound approved for use with Liquid Petroleum Gases.
?Piping must also comply with your local codes.
?To obtain the maximum firing rate of the burner, the gas supply piping must be sized to
provide a minimum of 7.0"W.C. pressure to the inlet of the upstream automatic safety shut-
off valve when the burner and all other gas utilization equipment are on. The pilot regulator
can be mounted in any position, the main regulator, if equipped, should be mounted upright
and in a horizontal run of pipe.
CAUTION: Because it is difficult to accurately control pressure during supply
pipe leak testing, it is recommended that all low pressure (14.0"W.C. max.)
components, both main and pilot, be disconnected during testing. Exposing low
pressure regulators and valves, including manual valves, to pressures over 1/2 PSIG
(14.0"W.C.) will cause damage and void all warranties.
DANGER: Explosion hazard.
Do not use oxygen for pressure testing.
An explosion could occur during initial start up.
??If the burner piping must be rearranged because of space limitation, be sure to carry out
the general arrangement shown in Figure 5. Install the combination valve (RE4700BA,
RE4400B & RE4400BA only ) in any position except up-side down.
Part 1
Installation
Continued
Part 1 Installation
RE4400B and RE4400BA
UL, Valve Train Assembly 24VAC
VI Piping
Continued
Figure 5: Piping Diagram

7
Part 1
Installation
Continued
Part 1 Installation
RE4850BA UL, Valve Train
Assembly 24VAC
Figure 5: Piping Diagram (Continued)

?When the burner is installed in the vestibule of jacketed equipment, it is recommended that
the Automatic Safety Shut-Off Valves be left adjacent to the burner within the vestibule and the
Main Manual Shut-Off Valve be installed outside.
?Run full size pipe or tubing from regulator vent openings to outside of building. Provide no
traps in the vent lines and terminate away from all doors and windows; also make provisions
for keeping rain and foreign objects from entering the vent piping.
?When high supply gas pressure is encountered, as in the case in many industrial plants, the
gas line size can be reduced to allow for a greater pressure drop; however, the size must be
sufficient to deliver burner rating pressure.
CAUTION: High gas pressure supply lines require the proper pressure reducing
regulators. Install a high pressure regulator of the Tight Shut-Off type upstream of the
low pressure regulator. Sized for main gas input, and suitable for the minimum flow
regulating capacity of the pilot.
?The high pressure regulator must be adjustable to 14" W.C. outlet pressure.
?When the gas supply line is about to be put into service it must be tested to insure that it is
gas tight. Use air or inert gas under pressure and test with soap and water to locate leaks.
?Before gas is turned onto the system, a check must be made to see that there are no open
fittings and to make sure the burner main and pilot manual valves are closed.
?After checking for leaks, purge the gas line up to the burner inlet. Purging the air from the
gas supply line at this step will expedite the first light-off.
NOTE: If there is more than 1.0" W.C. differential in the inlet pressure to the burner compared
to when all other gas utilization equipment are off, refer to Section VI.
Burners are approved for use with NATURAL gas or PROPANE gas and should be used only
with the gas specified on the rating plate.
?The gas input should be set at the heating rate determined by the building heat loss and/or
heating plant survey, but not exceeding the rated maximum input of the gas utilization
equipment or Economite burner.
WARNING: Ignition is automatic. Make spark observations into combustion
chamber only with Main and Pilot Manual Shut-Off Valves closed. Confirm that gas
utilization equipment does not contain any accumulated gases. Purge as described in
step 3 below.
CAUTION: Cover plates, guards, and enclosures must be maintained in place at
all times except during maintenance and service.
1. Check the burner piping and valves for gas leaks by applying a weak liquid soap
solution to unions and joints with the gas supply on. Leakage will be indicated by the
appearance of soap bubbles. Locate and correct all gas leaks before proceeding.
WARNING: DO NOT USE OPEN FLAME.
2. Purging the air from the gas supply line at this step will expedite first light-off.
IMPORTANT: Purge outside the building. Do not purge into the gas utilization
equipment.
3. To purge the gas utilization equipment and chimney of any accumulated gases, turn
main Manual Gas Cock OFF, close Pilot Manual Shut-Off Valve, turn burner power on,
and set operating control to ON or thermostat to call for heat. Let the blower run long
enough to accomplish four combustion chamber volume air changes, but not less than
five minutes.
CAUTION:Make sure that the capacity range of the burner, manifold pressure,
and the combustion air shutter setting are suitable for capacity rating of the gas
utilization equipment. Refer to Section VIII and Table 3.
4. RESET the Ignition Control Module by setting the operating control to OFF or the
thermostat below room temperature for at least 30 seconds. See Section XII.
5. Confirm that Main and Pilot Manual Shut-Off Valves are open. Turn main Manual Gas
Cock ON.
6. Turn operating control to ON or set thermostat above room temperature. After the pre-
purge is complete, the pilot should ignite. Whenever the burner pilot fails to light during
the ignition trial, or if the flame is lost during the burner run and is not reestablished
within 15 seconds after the pre-purge, the Ignition Control Module will shut off the
Automatic Safety Shut-off Valves and LOCK OUT.To RESET the Ignition Control Module
Control for restart, de-energize the Ignition Control Module by setting the operating
control to OFF or thermostat below room temperature for at least 30 seconds. If burner
still fails to light, turn it off and repeat from step 4 above. Then if necessary, refer to the
TROUBLE CHART to isolate the problem.
WARNING: Repeated unsuccessful attempts to light will result in accumulated
gases in gas utilization equipment and chimney. To prevent these gases from
reaching an explosive level, periodically purge the gas utilization equipment and
chimney as described in step 3 above.
8
Part 1
Installation
Continued
Part 1 Installation
VII Main Gas
Input Selection
VIII Initial Start-
up /Adjustment
VI Piping
Continued

Part 1 Installation
9
VIII Initial Start-
up /Adjustment
Continued
RE4850BA
RE4700BA
2.8
2.5
4.1
3.4
2.8
2.3
3.4
0.3
0.422
0.422
0.358
0.358
0.358
0.358
0.290
0.422
3.5
3.0
3.3
3.2
2.7
2.9
2.3
0.4
0.688
0.688
0.563
0.500
0.500
0.422
0.422
0.688
700
650
600
550
500
450
400*
233
RE4400BA
Table 3: Capacity and Preliminary Gas Settings
1. Adjust the main regulator to vary the manifold gas pressure and burner input within the range shown.
Do not exceed pressure as listed in Table 3, under any circumstances. Use combustion readings (CO
or O2) and a flow meter to determine exact inputs.
*Orifice Size and approximate manifold gas pressure setting: as shipped. Air shutters are set at full
open (Note: RE4400B and BA full open is at the stop on mark 3.2).
NOTE: For LP Conversion kit contact the factory
DATA FOR TABLES IS APPROXIMATE AND BASED ON “0" OVERFIRE PRESSURE AT SEA LEVEL
2.4
2.5
2.7
2.8
2.4
3.9
3.3
2.7
2.2
3.3
0.15
0.688
0.563
0.500
0.422
0.422
0.358
0.358
0.358
0.358
0.290
0.688
3.5
3.1
2.7
2.8
2.4
2.8
3.15
2.4
2.6
4.3
0.4
No Orifice
No Orifice
No Orifice
0.688
0.688
0.563
0.500
0.500
0.422
0.358
No Orifice
Input
MBTU/HR1
Orifice
Size
(Inches)
Natural Gas
Natural Gas / Propane Gas Orifice Size and Pressure Settings
Manifold
Pressure
("W.C)
Orifice
Size
(Inches)
850
800
750
700
650
600
550
500
450*
400
280
Propane Gas
Manifold
Pressure
("W.C)
3.5
4.65
4.15
4.75
2.8
0.45
0.358
0.290
0.261
0.219
0.219
0.358
4.7
3.6
2.7
3.3
3.5
0.6
No Orifice
No Orifice
No Orifice
0.358
0.290
No Orifice
400
350
300
250*
200
133
-
-
-
I
I
H
G
G
F
J
-
I
H
G
F
F
J
J
J
J
B
I
J
B
C
E
E
J
-
-
-
J
B
-
Letter
Stamp
Letter
Stamp
I
I
H
G
G
F
F
I
F
F
J
J
J
J
B
F
J
B
C
E
E
J
-
-
-
J
B
-
RE4400B
2.8
3.6
3.1
3.2
2.1
0.3
0.358
0.290
0.261
0.219
0.219
0.358
4.3
3.3
2.4
2.9
2.8
0.6
No Orifice
No Orifice
No Orifice
0.358
0.290
No Orifice
400
350
300
250*
200
132
Part 1
Installation
Continued

7. To make a preliminary setting of the burner input, determine the manifold gas pressure
required from Table 3 and adjust the Main Gas Pressure Regulator accordingly. See
Section XI.
8. To determine the firing rate for NATURAL gas, accurately time test dial for the number
of seconds for one revolution and use the following formula. All other gas utilization
equipment must be off. 3600 x test dial size x BTU value = BTU/Hr.
No. of seconds for one rev. test dial
Then divide by 1,000 for MBH value.
Example: 3600 x 1 x 1000 = 360,000 BTU/HR = 360 MBH
10
9. Check the operation of the burner; start and stop it several times with the thermostat
or operating control.
10. With the burner running, check the operation of all limit and associated controls.
11. Perform the following final adjustments for combustion and flue gas temperature. Take the
flue gas samples and temperature immediately ahead of the draft control.
A. The flue gas temperature should be above 325°F but not exceeding 550°F.
Excessive flue gas temperatures will result in low efficiencies. Low flue gas
temperature may cause excessive condensation. Reset gas input, if necessary, to
adjust stack temperature.
B. Make the final setting of the combustion air shutter by checking the flue gases
with an ORSAT or similar combustion testing instrument. The carbon monoxide
content should conform to local codes, or in their absence, to the level specified
in the United States or Canadian Standard referenced on the front cover of this
10
Part 1
Installation
Continued
Part 1 Installation
VIII Initial Start-
up /Adjustment
Continued
Figure 7A: General Assembly for RE4850BA, RE4700BA and RE4400BA

11
manual; and the carbon dioxide content should be approximately 9.5% for
NATURAL or 12% for propane , or within the limits prescribed by local codes.
12. Check the draft control to make sure there is no spillage of flue products into the room.
13. FILL OUT THE INSTALLATION ADJUSTMENT DATA TAG and affix to the burner or
gas utilization equipment.
NOTE: For subsequent normal starting and shut off procedure, refer to CONSUMER
INSTRUCTIONS, located in part 3 of this manual,or to the instruction plate mounted
on the burner.
PART 2 SERVICE
DANGER: Do not tamper
with the unit or controls. If trouble
occurs contact the installing
contractor, service agency, or fuel
supplier. See front cover.
DANGER: Be sure that the
main and pilot manual Shut-Off
Valves are closed and the burner
power supply is turned off before
removing any parts for service.
CAUTION: Cover plates,
guards, and enclosures must be
maintained in place at all times
except during maintenance and
service.
Figure 7B: General Assembly for RE4400B
Part 1
Installation
Continued
Part 2
Service
6000
6000
6000
6000
3.0”
to
4.5”
W.C.
Model
RE 4850BA
RE 4700BA
RE 4400B
RE 4400BA
0.055”
0.055”
0.055”
0.055”
Table 4: Pilot Specifications
Gas
Orifice
Diameter
#54
Wire Drill
Approx.
Capacity
BTU/Hr.
Pilot Gas Pressure
2.5”
to
3.5”
W.C.
Natural Propane
Part 1 Installation
VIII Initial Start-
up /Adjustment
Continued

Part 2 Service
The pilot is of the premix, blast type. The full force of blower air is brought into the mixing tube
where the proper amount of gas is added through the pilot orifice. This mixture is discharged
through the pilot. The mixture provides the flame that contacts the flame sensing rod and also
ignites the main gas.
CAUTION: Do not indiscriminately increase pilot orifice size. Pilot troubles are rarely
cured in this manner and new troubles may be created.
?Under normal conditions, with a slight negative pressure in the combustion chamber, pilot
operating pressures should be set as indicated in Table 4.
?Some conditions which may require a change from the normal setting include: extremely long
tubing connections between the regulator and pilot solenoid, high negative or positive
combustion chamber pressure, actual air shutter setting and altitude extremes.
?Do not subject the pilot to an inlet pressure over 14.0"W.C. See Section VI PIPING for high
pressure gas.
?To adjust outlet pressure, remove the seal cap for access to the adjusting screw. Turning the
screw clockwise will increase outlet pressure, counter clockwise will decrease outlet pressure.
?The spark rod for a natural gas burner is welded to a round 1/2” perforated retention plate.
(The spark rod for a propane gas burner is welded to a round 1/2” solid retention plate.)
CAUTION: Make sure that the natural gas burner has the correct spark rod
retention plate before operating the burner. See “Replacement Parts Lists” if replacement
is needed. The 1/2” retention plate is centered in the 3/8” Tee pilot and is positioned so the high
tension voltage will arc to the inside of the 3/8” Tee pilot.(See Figure 7A and 7B).
?The flame sensing rod must be positioned as shown in Figures 7A and 7B so that the Ignition
Control Module will detect a proper flame.
?Both the spark and flame rods are current carrying conductors and, along with their
connecting wires, must be kept free of contact with conductive metal parts of the burner. Rod
insulators and wire insulators should be clean, dry and free of cracks.
?Both the spark and flame rods are made from heat resistant alloys and can be expected to
have a long service life. They should be routinely inspected, however, for corrosion or loss of
metal.
?The pilot air tubing must be kept free of kinks or inside obstructions and must be positioned
per Figures 7A & 7B, otherwise air flow could be reduced and adversely affect the pilot flame.
CAUTION: BEFORE SERVICING, mark with a scribe line or measure opening of
air controlling shutter, so that it can be reset to its original position following servicing.
?Cleaning of the blower wheel is usually the only service required. Need for cleaning is
indicated if the character of the flame indicates a deficiency of air. Motor cooling air vents (if
present) should also be cleaned at this time.
?The motor and wheel are removed as an assembly. Disconnect the motor wires from the
motor terminal strip. Disconnect the motor conduit from the motor and remove the mounting
bolts.
?The burner is equipped with a diaphragm type air pressure switch so as to prevent the burner
from firing if the blower wheel is not running at its operating speed. When the motor is off there
is no air pressure present to activate the pressure switch and in turn there is no power flow to
the Ignition Control Module.
Figure 6: Motor / Blower Assembly
Part 2
Service Continued
XMotor Blower
Interlock
12
IX Pilot

Part 2 Service
?To make a specific test of the interlock circuit:
1. Turn burner power OFF.
2. Turn Manual Gas Cock OFF.
3. Disconnect the motor wire from the terminal strip to keep the motor off.
4. Turn burner power ON and set the operating control to ON or thermostat to call for
heat. Verify there is 120VAC line voltage by using a multimeter. Check for 24V
between the Ignition Control Module 24V and 24V GND terminals.
A. No voltage: Interlock circuit OK.
B. Voltage present: check that the switch is wired properly or check switch
operation. Replace if switch tests bad.
?Should replacement or service be required, valve manufacturer's instructions must be
followed as outlined in their information sheet.
?Outlet pressure settings must be checked while the gas is flowing.
?To adjust outlet pressure, remove the seal cap for access to the adjusting screw. Turning the
screw clockwise will increase outlet pressure, counter clockwise will decrease outlet pressure.
?The RE4400B / RE4400BA / RE4700BA / RE4850BA operate when power is applied to L1
and L2 through a safety or operating control. With power applied to L1 and L2 the blower
motor starts. Once the diaphragm airflow switch proves blower operation, power is applied to
the S8680J Ignition Module. The S8680J Ignition Module provides prepurge of 30 seconds,
ignition sequence timing, flame sensing and the switching of the gas valves. If the flame
signal is above 2 DC micro amps the gas burner will remain in operation until a safety or
operating control opens the circuit to L1 and L2. For a more thorough explanation of the
Honeywell control refer to the literature provided with the power burner. For startup
information see section VIII.
?For operation characteristics, maintenance, and service procedures, refer to manufacturer's
literature provided with burner.
?To check the flame signal on the gas burner you will need a DC micro amp meter. Install
the meter probes in series with the flame rod wire and the sense terminal on the control
board. Turn on the gas burner and observe the reading on the micro amp meter. If the flame
signal is above 2 DC micro amps the gas burner will continue to operate. If the flame signal
is below 2DC micro amps increase or decrease the pilot gas pressure by adjusting the pilot
gas pressure regulator as shown in Figure 5 clockwise to increase gas pressure and
counterclockwise to decrease gas pressure. See Table 4 for the correct pilot gas pressure
settings. Gas burner flame signal will vary for all applications and adjustments should be
made to the pilot gas pressure regulator and pilot flame signal before the main gas valve is
energized. To de-energize the main gas valve remove the wire connected to the MV terminal
on the S8680J Ignition Control Module.
Special equipment, either factory or contractor installed, may cause variation in the procedures
and descriptions given in this manual.
Consult the OEM's manual to identify the differences in the information.
The major difference for the CUL version of the RE4850BA, RE4700BA, RE4400BA and
RE4400B is the French / English specification plate, French / English manual and the firing
valve for the pilot line.
XI Valve Train
XII Sequence of
Operation
XIII S8680J
Ignition
Control Module
Part 2
Service Continued
XV Special
Equipment
(OEM Versions)
13
XIV Ignition
Control Module
XVI Canadian
Specifications
XMotor Blower
Interlock
Continued

Part 3 Maintenance
CONSUMER INSTRUCTIONS
?Keep the area around the burner clear and free of combustible material, gasoline or other
flammable liquids or vapors. Do not obstruct burner air openings or ventilation grills for
combustion air.
?The motor features permanently lubricated ball bearings and requires no maintenance.
WARNING: If any flame is observed when the burner is on standby, or if the
ignition spark or valve operator is heard to come on before the motor reaches
operating speed, immediately turn off the manual gas control and burner power. A
dangerous condition has developed and must be corrected. CONTACT A QUALIFIED
SERVICE TECHNICIAN FOR CLEANING, READJUSTMENT OR REPAIR.
?Check that the pilot ignition spark does not come on before the motor reaches operating
speed. If it does, the air switch is defective and must be replaced. (See Section X, Motor /
Blower Interlock).
LIGHTING INSTRUCTIONS
1. SET OPERATING CONTROL TO OFF OR THERMOSTAT BELOW ROOM
TEMPERATURE.
2. TURN MANUAL GAS COCK ON.
3. TURN BURNER POWER ON.
4. SET OPERATING CONTROL TO ON OR THERMOSTAT TO CALL FOR
HEAT.
5. IF THE PILOT FLAME IS NOT PROVEN WITHIN 15 SECONDS, AFTER THE
PRE-PURGE, THE IGNITION CONTROL MODULE WILL SHUT OFF THE
AUTOMATIC SAFETY SHUT-OFF VALVES AND LOCK OUT. IF THE PROOF
OF FLAME IS LOST DURING BURNER RUN AND THE PILOT IS NOT RE-
ESTABLISHED WITHIN15 SECONDS AFTER THE PRE-PURGE, THE
PRIMARY SAFETY CONTROL WILL SHUT OFF THE AUTOMATIC SAFETY
SHUT-OFF VALVES AND LOCKOUT. TO RESET FOR RESTART, DE-
ENERGIZE THE CONTROL BY SETTING THE OPERATING CONTROL TO
OFF OR THERMOSTAT BELOW ROOM TEMPERATURE FOR AT LEAST 60
SECONDS.
6. REPEAT STEP 4 FOR RESTART.
TO SHUT OFF
1. TURN MANUAL GAS COCK OFF.
2. TURN BURNER POWER OFF.
SHOULD OVERHEATING OF THE APPLIANCE OCCUR
1. Shut off the manual gas control to the appliance.
2. Do not shut off the electrical supply power to the blower.
14
Part 3
Maintenance
Lighting Instructions

Part 3 Trouble Chart
TROUBLE CHART
Make sure the thermostat and operating controls are calling for heat.
CAUTION: If a test indicates an electrical component may be defective,
before replacing it, make sure that its associated wiring is not at fault.
ELECTRICAL AND FLAME CHECKS MUST BE MADE IN THE ORDER LISTED BELOW.
I. MOTOR WILL NOT RUN
A. Confirm 120V between strip terminals L1 and L2 and verify the circuit polarity and
electrical ground between strip terminal L1 and burner Ground.
B. Check for 120V between strip terminals L1 and L2.
1. No voltage, open circuit in operating controls.
2. Voltage present, motor is defective.
II. MOTOR RUNS CONTINUOUSLY, PILOT WILL NOT LIGHT
A. Confirm that ALL Main Manual Shut-Off Valves are in the ON position.
B. After the pre-purge, if the pilot flame is not proven within the pilot flame re-
re-establishing period, or if the proof of flame is lost during the burner run and the
pilot is not re-established after the pre-purge, the Ignition Control Module will lock
out. To reset the control for restart, de-energize the Ignition Control Module by
setting the operating control to OFF or thermostat below room temperature for at
least 60 seconds.
C. Clogged pilot orifice.
D. Pilot regulator mis-adjusted
or defective.
E. Defective spark electrode or
Ignition Control Module.
F. Defective high tension wire.
G. Wrong pilot orifice.
H. Defective pilot valve.
I. Pilot air tube clogged.
J. Incorrect spark gap.
K. Pilot regulator vent clogged.
L. Defective blower air switch.
M. Slow motor.
N. Step down transformer is defective.
III PILOT LIGHTS, NO MAIN FLAME
A. Poor pilot flame adjustment.
B. Clogged pilot air tube.
C. Defective flame sensing rod or wire.
D. Flame sensing rod mis-located.
E. Pilot regulator vent clogged.
F. Defective Ignition Control Module.
G. Defective main gas valve.
H. Low gas pressure.
I. Grossly mis-adjusted main gas and air.
15
Part 3
Continued
Trouble Chart
IMotor Will
Not Run or Motor
Runs in Repeated
Cycles
II Motor Runs
Continuously, But
No Flame
III Pilot Lights,
No Main Flame

16
Midco International Inc.
4140 West Victoria Street * Chicago, Illinois 60646 1201
8471 24
Printed in USA
This manual suits for next models
3
Table of contents