MW KSI-01U User manual

KSI-01U
KNX-USB Interface
Instruction manual

KSI-01U Instruction Manual
Content
May. 2019 Version 0
1.Product Description
2.Operational Description
3.State of Delivery
1.1 Front Panel
2.1 KNX Programming Interface
3.1 General Factory Setting
3.2 Technical Datasheet
3.3 Technical Drawings
2.2 Physical Address Assignment
2.3 Project Physical Address
2.4 Group Associations
1.2 LED Indication
1.3 Commissioning
1.4 Feature Summary
..............................................................................
........................................................................
...................................................................................
.....................................................................................
............................................................
..................................................................
.......................................................................
.........................................................................
.........................................................
.................................................................
........................................................................
................................................................................
...............................................................................
............................................................................
1
3
7
1
4
7
7
8
4
5
6
2
2
3

1
1 Product Description
The KNX USB Interface KSI-01U provides a bi-directional data connection between
USB and KNX TP. PCs can be connected via USB and the bus system is galvanically
isolated. KSI-01U establishes access to all bus devices for commissioning,
addressing, setting parameters, visualization, protocolling, and diagnostic
operation. Operational states are shown by LEDs. KSI-01U is supplied by both KNX
TP and USB. No external power supply is necessary.
With the ETS (or compatible commissioning tool) KSI-01U works as the KNX
programming interface having no KNX communication objects for itself. Due to HID
profile support no specific USB driver is required. USB suspend mode is supported.
The protocol used for communication between interface and host is the flexible
“cEMI” protocol.
The connection between KNX and a PC with standard software (like ETS, EITT, also
in Raw Frame operating mode) or other software is handled by the Falcon driver.
KSI-01U supports extended frames and long messages with up to 220 byte APDU
length. Easy software handling is ensured. For specific diagnostic applications like
EITT, KSI-01U supports the "Raw Frame" operating mode.
1.1 Front Panel
Figure 1: Front View
LEDs
A1 A3
A2 A4
State USB (+Telegram Traffic USB) USB Connector
Bus State KNX TP (+Telegram Traffic KNX TP) KNX TP Connector
Buttons / Connectors
+
-
+
-
USB
KNX
A1
A2
A3
A4
Table 1: Front Panel Elements

2
Figure 2: Connection Scheme
Number
A1
A2
LED
State USB
Bus state KNX TP
Note: Without connection to USB KSI-01U is not powered.
Colour
green
green
blinking green
red
<off>
blinking green
<off>
Explanation / Range
USB connection OK / No telegram traffic
KNX TP connection OK / No telegram traffic
Telegram traffic extent indicated by blinking
USB Suspend Mode
No USB connection
Telegram traffic extent indicated by blinking
KNX TP line not connected (or no USB connection)
1.2 LED Indication
1.3 Commissioning
Please note for commissioning with default settings:
● Physical address is 0.2.255
● After connection to USB, the device works with its default settings.
Please read carefully before first use:
● The device may only be installed and put into operation by a qualified electrician or
● For planning and construction of electric installations the appropriate specifications,
● Connect the KNX bus line as for common KNX bus connections with a KNX bus cable,
● Do not damage electrical insulations during connecting.
●. Installation only in dry locations
● . Accessibility of the device for operation and visual inspection must be provided
●. For changing the configuration use the ETS
●. The housing must not be opened
● For mounting use an appropriate equipment according to IEC60715.
● Installation on a 35 mm DIN rail (TH35).
● Warning: Do not connect to 230 V. The device is supplied by USB and does not require
any additional external power supply.
authorized personnel.
guidelines and regulations in force of the respective country have to be complied.
to be stripped and plugged into a KNX TP connector.
Table 2: LEDs Colours
USB
To the personal
KSI-01U
KNX cable
computer USB port
(Type A)
To the
USB cable is
not included
in the industrial
package
interface
()Type B
Personal Computer
KNX
Device
+
-
ETS

3
1.4 Feature Summary
● Protect the device from moisture, dirt and damage.
●. The device needs no maintenance
● If necessary, the device can be cleaned with a dry cloth.
● Data connection between PC and KNX bus line.
● Suitable for usage with ETS. No extra application program necessary.
● KSU-01U supports extended frames and long telegrams up to 220 bytes APDU length.
● Access to every bus device in the KNX bus system for commissioning, addressing,
● Use of cEMI ("Common EMI") protocol.
● Galvanic isolated bi-directional access to KNX TP.
● Usage also without Falcon driver software.
● Support of Raw Mode, a special diagnostic mode.
● Can be used with EITT.
● Low current consumption.
● Installation module for 35mm top-hat rails (DIN, Th35).
● KSI-01U works without external power supply.
KSI-01U's ETS database entries are available for ETS4 and later.●
● No specific USB driver needed due to USB HID Profile.
(With all KSC couplers and UIM interfaces long messages e.g. for energy metering
setting parameters, visualization, protocolling and diagnostics.
applications and visualization purposes can be processed.)
● In the case of damage (at storage, transport) no repairs may be carried out by
unauthorized personnel.
2 Operational Description
In KNX network installations the KSI-01U can be used as KNX USB interface. After
establishing the USB connection, KSI-01U operates with its default settings. Setting
the correct physical address is necessary to include KSI-01U in the KNX bus
system.
Both LEDs lighting green show proper working of KNX bus connection and USB
connection. Lightning green means the connection is established. Blinking green
indicates the telegram traffic extent. In Microsoft Windows the KSI-01U is
recognized as HID (Human Interface Device). So, no extra drivers have to be
installed or downloaded.
The KSI-01U's ETS (dummy) database entry, e.g. for connecting a visualization
device, is available for ETS4 and upward. The database without parameters and
without communication objects can be added to an ETS project as usual.
Note: It is recommended to use USB cables that do not exceed 5 m.
Note: All screen shots are related to the KSI-01U database file in ETS5.

4
Figure 3: ETS Bus Connection Interface Window
2.2 Physical Address Assignment
The device is supplied with the individual physical address 0.2.255. With the ETS
the physical address can be assigned to the device by setting the desired address in
the Individual Address field of the Bus Connections window of the ETS. To download
the desired physical address the KSI-01U has to be chosen as the Current Interface.
Then type in the Individual Address and press the Test button.
Note: In this document only the term “physical address” is used. The term “physical
address” means the KNX physical address as well as the ETS individual
address. Both terms are used by the KNX organisation interchangeably.
2.1 KNX Programming Interface
To use KSI-01U for ETS programming it has to be chosen as the Current Interface in
the ETS Bus Connections window or alternatively during editing a project, at the
bottom line (“Name and state of current connection”) of the ETS window.

5
2.3 Project Physical Address
For i.e. connecting a visualization device to KNX, the KSI-01U must be contained in
the ETS project. The necessary product database entry can be downloaded from the
MEANWELL web site and from the KNX Online Catalog.
Figure 4: Physical Address Assignment
Figure 4: Physical Address Assignment
Figure 4: Physical Address Assignment
Figure 5: MEANWELL USB Interfaces in the ETS Catalog
With the ETS, the project physical address can be assigned by setting the desired
address in the properties window of the ETS.

6
2.4 Group Associations
To establish a connection between a device of interest and its visualization
application the KSI-01U can be used as the connecting interface. To enable group
communication the group objects have to be entered to the Group Associations of
KSI-01U per drag & drop (see following figure).
Figure 6: ETS Properties Window
Figure 7: USB Interface Group Address Associations

7
Note: Interfaces used in KNX Secure installations must know the type of access to
the corresponding Group Associations. To allow communication for the
regarded interface, the combination of PA/IA + GA is stored as position
information in relevant devices. GAs are added to coupler filter tables by ETS
automatically.
Note: Visualization of KNX Secure devices can only be done with using secured
Group Associations.
3 State of Delivery
3.1 General Factory Setting
3.2 Technical Datasheet
General
Product KNX USB Interface
Order Number KSI-01U
Application -----
ETS Name KNX USB-Interface
Physical Address
Marking/Design
Current consumption
LED Display elements
Mounting
Protection type
Pollution degree
Protection class
Overvoltage category
Approbation
Housing colour
Housing dimensions
Voltage supply
Standards
CE Marking
Connections
0.2.255
KSC-01U
KNX TP: < 5mA and USB: < 20 mA
State (USB and KNX)
35 mm top-hat rail (TH35) according to IEC60715
IP20 according to IEC60529
2 according to IEC60664-1
III according to IEC61140
III according to IEC60664-1
KNX-certified according to ISO/IEC14543-3
Plastic PA66 housing, grey
H = 90 mm, W = 36 mm (2 modules), D = 71 mm
KNX: 21…30V DC (SELV)
USB: 5 V DC (SELV)
EN50491-5-1, EN50491-5-2, EN50491-5-3,
EN50581,EN61000-6-2, EN61000-6-3
In compliance with directives 2014/35/EU (LVD),
2014/30/EU(EMC), 2011/65/EU (RoHS)
USB:USB2.0 connector (Type B, female)
KNX TP line:KNX TP connector (red/black),
screwless, for single-core cable Ø 0.6…0.8 mm

8
3.3 Technical Drawings
Note :All dimensions shown here are specified in mm.
Note :The total device width is 2 modules at 18 mm.
Weight
Operating temperature
Storage temperature
Ambient humidity
USB cable length
USB driver
62 g
-5…45 °C
-20…60 °C
5…93 %, non-condensing
Max. 5 m
HID Device, standard driver included in Windows/Linux
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
35
+
-
+
-
36
90
44.9
22.55
12.2
50.9
71
4
37.6
USB
KNX
Unit:mm
Mounting depth 64 mm

No.28, Wuquan 3rd Rd., Wugu Dist., NewTaipei City 248, Taiwan
Table of contents
Popular USB Interface manuals by other brands

Velleman
Velleman KSR10/USB user manual

Mastervolt
Mastervolt USB Interface for Solar ChargeMaster user manual

Analog Devices
Analog Devices Dust Networks DC9006A user guide

CIRCUIT DESIGN
CIRCUIT DESIGN MU1-UIK Operation guide

SOMFY
SOMFY KNX USB Interface Operation and installation manual

MFJ
MFJ 1204 instruction manual