NCP S115A-10K10 User manual

Installation
Instructions
Mini Split Air Conditioning
or Heat Pump Systems
Air Conditioning
S115A-10K10
S115A-13K10
S240A-13K11
Heat Pump
S115HP-10K10
S115HP-13K10
S240HP-13K11
950-0004
Rev 7, 28 October 2005

Table of Contents
Specifications..................................................................................................1
Unit Parts & Features..................................................................................... 2
Installation Dimension Diagram...................................................................... 3
Safety Warnings............................................................................................. 4
Select Installation Locations............................. ..............................................5
Indoor Unit Installation....................................................................................7
Outdoor Unit Installation.................................................................................8
Testing............................................................................................................10
Warranty..........................................................................................................11

Specifications
Air Conditioning
S115A-10K10
Indoor replacement S115A-10K10-I; Outdoor replacement S115A-10K10-O
9,500 BTU
10.5 Seer
S115A-13K10
Indoor replacement S115A-13K10-I; Outdoor replacement S115A-13K10-O
12,500 BTU
10.5 Seer
S240A-13K11
Indoor replacement S240A-13K11-I; Outdoor replacement S240A-13K11-O
12,500 BTU
11 Seer
Heat Pump
S115HP-10K10 - 9,500 BTU - 10.5 Seer
Indoor replacement S115HP-10K10-I; Outdoor replacement S115HP-10K10-I
9,500 BTU
10.5 Seer
S115HP-13K10
Indoor Replacement S115HP-13K10-I; Outdoor replacement S115HP-13K10-I
12,500 BTU
10.5 Seer
S240HP-13K11
Indoor replacement S240HP-13K11-I; Outdoor replacement S240HP-13K11-O
12,500 BTU
11 Seer
1

Unit Parts & Features
ONOFF
MODE
SWING FAN
AUTOFAN OPER
F
AIR
AUTO
SWINGHUMID LIGHT SAVE
TIMER
ON/OFF HR
Air in Panel Air filter
Indoor Unit
Outdoor Unit
Air out Louver
Wiring cover
Cover plate of
electric box
Remote control
Drain hose
Connecting pipe
Cooling indicator
Heating
indicator On/Off indicator
Remote control receiver
Air outlet grill
Air out
nir
iA
(side of unit)
(back of unit)
Cover panel
2

Installation Dimension Diagram
Installation must be done by a qualified technician
according to instruction manual and in accordance with
local electrical standards.
Important Note
Piping-hole sleeve
Wrapping tape
11.25 in.
21.25 in.
see spec
sheet
see spec
sheet
see spec
sheet
33.4 in.
long
12.6 in.
deep
21.3 in.
high
Distance to
ceiling should be
6 inches or more
Distance to wall
should be 6
inches or more
Distance to floor
should be 80
inches or more
Distance to wall
should be 6
inches or more
Distance to wall
should be 12
inches or more
Clearance above
should be 20
inches or more
Distance to
wall in back
should be 12
inches or
more
Distance to wall
should be 12
inches or more
Distance in front
should be 80
inches or more
3
Right-positioned
piping hole
Left-positioned
piping hole

Safety Warnings
4
• Use copper wires only for power supply
• Risk of electric shock can cause injury or death. Disconnect all electric power supplies
before servicing or installation.
• Do not use excessive torque on flare nuts during connection of the refrigeration tubes, or
service valve on discharge line may be damaged.
• Do not put indoor unit in a location where it could get wet.
• Electrical installation must be done by a qualified technician according to instruction
manual and in accordance with local electrical standards
• Certified power supply conductors must be used.
INSTALLATION KITS
Installation kits are available for all NCP Mini-Split systems. These kits contain a 20’ line
set appropriate for each model, connecting wires, PVC tape, drainage hose, and wall
sleeve(s).
Contact your local dealer for availability.
Installation Kit Use for Model
2400-1412 S115A-10K10-O (I)
S115HP-10K10-O (I)
S240A-13K11-O (I)
S240HP-13K11-O (I)
S115A-13K10-O (I)
S115HP-13K10-O(I)

Select Installation Locations
5
Indoor Unit:
• The air intake and outlet should not be obstructed.
• The wall the unit is mounted on should allow for a clear hole for the condensation drain
line and the refrigeration lines.
• The wall the unit is mounted on should be strong enough to bear the weight and vibration
of the unit.
• Allow for proper clearances around the unit - see installation dimension diagram (page 3).
• Location should allow easy access for maintenance and removal of air filter.
• Position unit and remote control at least 3 feet from electric appliances such as televi-
sions, radios, etc.
• Keep unit and remote out of direct sunlight and/or flourscent lighting and away from any
excessive heat source, steam, or flammable materials.
Outdoor Unit:
• Allow sufficient ventilation around the unit - see installation dimension diagram (page 3).
• The air intake and outlet should not be obstructed.
• Position unit so that noise and outlet airflow will not inconvenience neightbors.
• Position unit on a solid foundation.
• Location should be able to withstand the full weight and vibration of the unit.
Both Indoor and Outdoor Units:
Installation of either unit in the following locations may cause malfunction. Locations exposed to:
• machine oil
• flammable or corrosive gases
• high-frequency waves (i.e. from radio equipment, medical equipment, etc.)

Indoor Unit Installation
1. Install the Rear Panel (mounting plate)
• Always mount rear panel horizontally.
• Hold the rear panel on the wall where you want the unit to be located and ensure that it is level
using a plumb line or level. Once leveled, mark the screw locations on the wall.
• Fasten the rear panel to the wall at the location marked using the screws supplied with the unit.
• Ensure that the panel has been mounted firmly to withstand the weight of the unit, with the weight
being evenly shared by each screw.
2. Install the Piping Hole
• Select location for piping hole - either left-positioned or right-positioned (see installation dimension
diagram on page 3).
• Make piping hole in the wall approximately 2.5 inches in diameter at a slight downward slant (this
ensures proper drainage).
• Insert a piping-hole sleeve in the hole (i.e. PVC pipe) to prevent the connection piping and wiring
from being damaged
3. Install Drainage Hose Extension (optional)
• Drainage hose extension is included with unit, for use if attached drainage line is not long enough
for your application.
• Please note that the extension can be installed after existing drainage pipe is fed through wall later
in the installation process, if it is determined later that it is necessary.
• Do not wrench or bend drainage hose or extension.
CAUTION! - Failure to connect wiring as indicated below will result in damage to
the unit and/or personal injury. Mis-wiring will also void warranty. DO NOT inter-
change any wiring connections!
4. Wire the Unit.
• Note: All electrical wiring must be done by a qualified technician in accordance with local electrical
standards
• An independent circuit breaker should be used.
WIRE TABLE FOR USE WITH ALL MODELS:
POWER SUPPLY
COOLING INTERCONNECTING WIRE GUAGE CIRCUIT
BTU WIRE GUAGE Terminals (L,N,G) BREAKER
10,00 BTU UL1015 AWG22 (HP only) Terminals 4 & 5 UL1015 AWG12 20AMP
UL1015 AWG16 (Terminals 1,2,& 3)
13,000 BTU UL1015 AWG22 (HP only) Terminals 4 & 5 UL1015 AWG12 25 AMP
115 VAC UL1015 AWG16 (Terminals 1,2,& 3)
13,000 BTU UL1015 AWG22 (HP only) Terminals 4 & 5 UL1015 AWG12 15AMP
240 VAC UL1015 AWG16 (Terminals 1,2, & 3)
6
Terminals (L1,L2,G)

Indoor Unit Installation (cont.)
Right piping Right rear piping
Left rear piping
Left piping
5. Prepare Refrigeration Lines
• Refrigeration lines and wiring can be routed from the indoor unit to the outdoor unit sev-
eral different ways, using the cut-out access pieces on the back of the unit.
• Bend the refrigeration lines carefully to the position needed to align with the drilled piping
hole.
•
7
8 way terminal board
(Outdoor Unit)
2 3
2 3 4
N(1
)
N(1
)
5 way terminal board
(Indoor Unit)
Power
Supply
Connections
115 V Heat Pump Wiring
See Wire
Table
(para 4)
for wir e
sizes
5 L N G
4 5
6 way terminal board
(Outdoor Unit)
2 3
2 3 L N G
N(1)
N(1)
3 way terminal board
(Indoor Unit)
Power Supply
Connections
115 VAC Air Conditioner Wiring
See Wire
Table
(para 4)
for wire
sizes
6 way terminal board
(Outdoor Unit)
2 3
2 3 L1 L2 G
N(1)
N(1)
3 way terminal board
(Indoor Unit)
Power Supply
Connections
240 VAC Air Conditioner
Wiring
INDOOR UNIT
OUTDOOR UNIT
See Wire
Table
(para 4)
for wire
sizes
8 way terminal board
(Outdoor Unit)
2 3
2 3 4
N(1
)
N(1
)
5 way terminal board
(Indoor Unit)
Power
Supply
Connections
240 V Heat Pump Wiring
See Wire
Table
(para 4)
for wir e
sizes
5L1 L2 G
4 5
Note: Grounding between the indoor unit and the outdoor unit is accomplished through the coolant
line set.

Indoor Unit Installation (cont.)
6. Hang Indoor Unit
• Bundle the refrigeration lines, drainage hose, and
wiring conduit attached to the indoor unit and
wrap them securely for enough length to extend
through the piping hole to the exterior of the
building. (Note: leave remainder unwrapped to
allow for remaining steps in installation of the
outdoor unit and connecting the indoor unit to the
outdoor unit.)
• Carefully push bundled lines through the piping
hole.
• Hang the unit on the wall by hooking the mounting
slots of the unit over the upper tabs of the rear
panel.
• Check to make sure the unit is properly secured --
it should feel firmly attached to the wall, and you
should not be able to slide it to the right or left.
Wrapping tape
Control cord
(for heat pump
models only)
Drainage
hose
Power cord
Connection pipes
Wall
Rear panel
Upper tabs
Bundled lines
Indoor unit
Outdoor Unit Installation
1. Connect Refrigeration Lines to Bundled Lines from Indoor Unit
• Use standard A/C practices to attach the connection pipes to the proper pipes of the
bundled lines coming through the wall from the indoor unit.
• Tighten the flare nut of the connection pipes using a spanner
and torque wrench. (see diagram)
• Note: Do not over-tighten flare nuts, or the connection may be
damaged.
2. Insulate/Bundle Refrigeration Lines and Wiring
• Individually insulate all refrigeration lines and condensation drainage hose to ensure that
they do not sweat. This will help to maintain the unit at its proper capacities.
• Once all lines have been properly insulated, bundle the refrigeration lines with the wiring
conduit and wrap securely to complete the run to the outdoor unit.
• Note: The condensation drainage hose should be left free of the bundled lines in order to
drain properly.
3. Install Outdoor Condensation Drainage Hose (Heat Pump Models Only)
• When the heat pump unit is heating or defrosting, wastewater forms in
the outdoor unit. This can be drained off using the outdoor drain elbow
and hose provided.
• Insert the drain elbow into the hole on the base plate as shown.
• Joint the drain hose to the elbow and turn so that the water
drains in the desired location.
Torque wrench
Spanner
Flare nut Joint
Outdoor drain elbow
Base plate
8

Outdoor Unit Installation (cont.)
3. Position Outdoor Unit
• Review page 5 - “Select Installation Location” for “Outdoor Unit” and for “Both Indoor and
Outdoor Units”.
• Make sure unit is positioned solidly and leveled on its foundation. Use leveling feet if
necessary.
• If possible, affix unit to foundation using bolts.
4. Connect Refrigeration Lines to Outdoor Unit
• Remove valve caps on outdoor unit.
• Use standard A/C practices to attach the refrigeration lines bundled in Step 2 to the
outdoor unit.
• Tighten the flare nut of the connection pipes using a spanner
and torque wrench. (see diagram)
• Note: Do not over-tighten flare nuts, or the connection may be
damaged.
2. Wire the Outdoor Unit
• Refer to page 6 for wire sizes.
Refer to page 7, Paragraph 4 for wiring diagrams.
DO NOT INTERCHANGE OR CROSS WIRE any wire leads! Damage and/or personal
injury can occur!
Torque wrench
Spanner
Flare nut Joint
9

Testing
1. Notes:
• Installation MUST be complete prior to testing.
• System MUST be tested prior to operation.
2. Leakage Test
• Use standard A/C practices to properly check refrigeration tubes and connections for any
leaks prior to system start up.
3. Pressure Testing
• Remove bonnet (cover) of gas valve on outdoor unit.
Charge system with Nitrogen to 100 PSI and check for
leaks. Evacuate Nitrogen.
• Connect the gas valves of a vacuum guage, vacuum
pump, and outdoor unit. (see diagram)
• Start the vacuum pump and allow to run for at least 30
minutes at a level of 500 microns or less.
• Shut off the vacuum and continue to monitor vacuum
guage for another 15 minutes. The pressure should not
rise above 800 microns.
• If a vacumm of 500 microns cannot be obtained, or if it
rises above 800 microns during the 15-minute monitoring
period, pressurize the system with nitrogen and look for
leaks. Repair any leaks that are found and repeat the vacuum testing.
• Close the valves to the vacuum pump and guage and disconnect from the outdoor unit.
• Tighten bonnet (cover) of gas valve and open gas and liquid valves completely.
4. System Testing
• Before testing the system, ensure that cut-off valves of the connection pipes are opened
and that all debris (such as packing scraps, thrums, etc.) are cleared from the unit.
• Switch on power to the system and press the “ON/OFF” button on the remote control to
activate the indoor unit.
• Press “MODE” button repeatedly, taking a moment on each setting to ensure that system
functions in all modes. (Note: HEAT mode will only function on
heat pump models.)
• If the remote control is lost, emergency run operation can be
initiated by pressing the the button in the upper right corner of
the indoor unit under the cover panel. (see diagram)
5. Installation Verification
• Have both units been securely and firmly installed?
• Are all piping connections secure?
• Have the refrigeration lines been sufficiently insulated?
• Have you verified the length of the connection pipes and the refrigerant capacity?
• Have you conducted all leakage and system tests?
• Does the unit drain properly?
• Are all electrical connections in compliance with local standards?
• Has the unit been properly grounded?
• Is the power cord specified?
• Are all air inlets and outlets free from obstruction?
Vacuum gauge
Bonnet
Liquid pipe
Gas pipe
Vacuum pump
Emergency
button
10

Warranty
11
NCP warrants the accompanying split air conditioner or heat pump system to be free of defects
in material and workmanship for the applications specified in the operation manual and installa-
tion manual for a period of one (1) year on parts and five (5) years on compressor, valid from the
date of original retail purchase in the United States or Canada. Labor is not covered under
warranty.
If the unit exhibits a defect in normal use and is determined to be within the warranty period,
NCP will, at its option, either repair or replace the unit free of charge within a reasonable time
after the unit is returned.
This warranty DOES NOT cover:
• Damage, accidental or otherwise, to the unit while in possession of the consumer that is
not a result of a defect in material in workmanship.
• Damage caused by consumer misuse, tampering, or failure to follow all care and mainte-
nance instructions in the manuals.
• Damage to the finish of the case or other parts caused by water.
• Damage caused by repairs or alterations to the unit by anyone other than a qualified
technician.
• Filter.
• Freight and insurance cost for the warranty service.
Damage caused by mis-wiring the unit(s).
Warranty Activation Card must be completed and sent in to activate the warranty for the accom-
panying unit.

Specifications
SYSTEM MODEL NUMBER
COMPONENT MODEL NUMBER
Cooling Capacity
Heating Capacity
Seer Rating
HSPF Rating
Mositure Removal (pts/hr)
Air Volume (cfm)
Motor Fan Speed (RPM, L/M/H)
Fan Motor Rating
Sound Rating (db)
Compressor
Compressor Locked Rotor Amps
Compressor Running Load Amps
Design Pressure (High)
Design Pressure (Low)
Operating Range
Electrical Information
Power
Cooling: Watts/Amps
Heating: Watts/Amps
Fuse/Breaker
Fan Motor P/N
Refrigerant Lines
Connections
Liquid Line
Suction Line
Standard (Design) Length of Line Set
Maximum Length
Maximum Height
Installation Kit (Optional)
Dimensions & Weights
Width x Height x Depth
Net Weight
Refrigerant Charge
Refrigerant Charge Over design
len
g
th of Line Set
Outdoor Unit
Catalog Number
Indoor Unit
Catalog Number
S115A-10K10-O S115A-10K10-I
N/A 1070/1000/930
0.065HP/0.9A 0.008HP/0.18A
<55 <32 / 35 / 38
Hitachi SG453EA1NC N/A
40A N/A
8.8A N/A
313 Psig 313 Psig
144 Psig 144 Psig
N/A MP24GA
33" x 12" x 22" 32" x 7" x 11"
73 lbs 24 lbs
Catalog Number 2400-1412, 20 Ft (6
meters
)
Air Conditioning Only
S115A-10K10
9,500 BTU
N/A
10.5
N/A
2.3
300 / 370 / 450
61°F to 86°F
115 VAC
900 / 8.2
N/A
20 AMP
Flare
1/4"
1/2"
50'
32'
R22 / 1.6 lbs (25.6 oz)
0.26 oz per foot
13'
Outdoor Unit
Catalog Number
Indoor Unit
Catalog Number
S115AHP10K10-O S115HP-10K10-I
1070/1000/930
0.065HP/0.9A 0.008HP/0.18A
<55 <32 / 35 / 38
Hitachi SG453EA1NC N/A
40A N/A
8.8A N/A
313 Psig 313 Psig
144 Psig 144 Psig
N/A MP24GA
33" x 12" x 22" 32" x 7" x 11"
73 lbs 24 lbs
Catalog Number 2400-1412, 20 Ft (6
meters
)
Heat Pump
S115HP10K10
9,500 BTU
10,500 BTU
10.5
7.5 / 6.2
2.3
300/370/450
61°F to 86°F
115 VAC
900 / 8.2
870 / 7.9
20 AMP
Flare
1/4"
1/2"
50'
32'
R22 / 1.8 lbs (28.8 oz)
0.26 oz per foot
13'

Specifications
SYSTEM MODEL NUMBER
COMPONENT MODEL NUMBER
Cooling Capacity
Heating Capacity
Seer Rating
HSPF Rating
Mositure Removal (pts/hr)
Air Volume (cfm)
Motor Fan Speed (RPM, L/M/H)
Fan Motor Rating
Sound Rating (db)
Compressor
Compressor Locked Rotor Amps
Compressor Running Load Amps
Design Pressure (High)
Design Pressure (Low)
Operating Range
Electrical Information
Power
Cooling: Watts/Amps
Heating: Watts/Amps
Fuse/Breaker
Fan Motor P/N
Refrigerant Lines
Connections
Liquid Line
Suction Line
Standard (Design) Length of Line Set
Maximum Length
Maximum Height
Installation Kit (Optional)
Dimensions & Weights
Width x Height x Depth
Net Weight
Refrigerant Charge
Refrigerant Charge Over design
len
g
th of Line Set
Outdoor Unit
Catalog Number
Indoor Unit
Catalog Number
S240A-13K11-O S240A-13K11-I
N/A 1100 / 1200 / 1350
0.064HP/0.56 Amps 0.03HP/0.16 Amps
<57 <39 / 41 / 44
PANISONIC
2P19S236A1J N/A
33 A N/A
5.7 A N/A
384 Psig 384 Psig
144Psig 144 Psig
N/A MP24GA
33" x 12" x 22" 32" x 7" x 11"
79 lbs 24 lbs
Catalog Number 2400-1412, 20 Ft (6
meters
)
Air Conditioning Only
S240A-13K11
12,500 BTU
N/A
11
N/A
2.9
340 / 450 / 520
61°F to 86°F
208 / 240 VAC
1250 / 5.5
N/A
15 AMP
Flare
1/4"
1/2"
50'
32'
R22 / 2.8 lbs (44.6 oz)
0.26 oz per foot
13'
Outdoor Unit
Catalog Number
Indoor Unit
Catalog Number
S240AHP13K11-O S240HP-13K11-I
N/A 1100/1200/1350
0.064HP/0.56 Amps 0.03HP/0.16 Amps
<57 <39 / 41 / 44
PANISONIC
2P19S236A1J N/A
33 A N/A
5.7 A N/A
384Psig 384 Psig
144 Psig 144 Psig
N/A MP24GA
33" x 12" x 22" 32" x 7" x 11"
79 lbs 24 lbs
Catalog Number 2400-1412, 20 Ft (6
meters
)
Heat Pump
S240HP-13K11
12,500 BTU
13,000 BTU
11
7.5/6.3
2.9
340 / 450 / 520
61°F to 86°F
208 / 240 VAC
1250 / 5.5
1250 / 5.5
15 AMP
Flare
1/4"
1/2"
50'
32'
R22 / 2.8 lbs (44.6 oz)
0.26 oz per foot
13'

Specifications
SYSTEM MODEL NUMBER
COMPONENT MODEL NUMBER
Cooling Capacity
Heating Capacity
Seer Rating
HSPF Rating
Mositure Removal (pts/hr)
Air Volume (cfm)
Motor Fan Speed (RPM, L/M/H)
Fan Motor Rating
Sound Rating (db)
Compressor
Compressor Locked Rotor Amps
Compressor Running Load Amps
Design Pressure (High)
Design Pressure (Low)
Operating Range
Electrical Information
Power
Cooling: Watts/Amps
Heating: Watts/Amps
Fuse/Breaker
Fan Motor P/N
Refrigerant Lines
Connections
Liquid Line
Suction Line
Standard (Design) Length of Line Set
Maximum Length
Maximum Height
Installation Kit (Optional)
Dimensions & Weights
Width x Height x Depth
Net Weight
Refrigerant Charge
Refrigerant Charge Over design
len
g
th of Line Set
Outdoor Unit
Catalog Number
Indoor Unit
Catalog Number
S115A-13K10-O S115A-13K10-I
1100 / 1200 / 1350
0.064 HP/0.9 Amps 0.29 HP/0.2
Am
p
s
<57 <39 / 41 / 44
Panasonic 2P19S126B1F
N/A
62 A N/A
10.6 A N/A
313 Psig 313 Psig
144 Psig 144 Psig
N/A MP24GA
33" x 12" x 22" 32" x 7" x 11"
79 lbs 24 lbs
Catalog Number 2400-1412, 20 Ft (6
meters
)
Air Conditioning Only
S115A-13K10
12,500 BTU
N/A
10.5
N/A
3.1
340 / 450 / 520
61°F to 86°F
115 VAC
1250 / 10.5
N/A
25 AMP
Flare
1/4"
1/2"
50'
32'
R22 / 2.8 lbs (44.8 oz)
0.32 oz per foot
26'
Outdoor Unit
Catalog Number
Indoor Unit
Catalog Number
S115HP-13K10-O S115HP-13K10-I
1100 / 1200 / 1350
0.064 HP/0.9 Amps 0.029 HP/0.2
Am
p
s
<57 <39 / 41 / 44
Panasonic 2P19S126B1F
N/A
62 A N/A
10.6 A N/A
313 Psig 313 Psig
144 Psig 144 Psig
N/A MP24GA
33" x 12" x 22" 32" x 7" x 11"
79 lbs 24 lbs
Catalog Number 2400-1412, 20 Ft (6
meters
)
Heat Pump
S115HP-13K10
12,500 BTU
13,000 BTU
10.5
6.36
3.1
340 / 450 / 520
61°F to 86°F
115 VAC
1250 / 10.5
1250 / 10.5
25 AMP
Flare
1/4"
1/2"
50'
32'
R22 / 2.8 lbs (44.8 oz)
0.32 oz per foot
26'
This manual suits for next models
5
Table of contents
Popular Air Conditioner manuals by other brands

Mitsubishi Electric
Mitsubishi Electric Mr.Slim MSZ-A24NA operating instructions

CH
CH CH-PDH12AC1 owner's manual

Webasto
Webasto Frigo Top 25 DS Instructions for use

Haier
Haier AB052MAERA Operation & installation manual

Samsung
Samsung AR**HV5D series User's installation guide

Sanyo
Sanyo STB0811C1-S parts list

Mitsubishi Electric
Mitsubishi Electric Mr. SLIM PKA-M-LAL Series installation manual

Honeywell
Honeywell CL48PM user manual

Hisense
Hisense APC09 Use and Installation Instructions

Mitsubishi Electric
Mitsubishi Electric MSZ-GS25VFD installation manual

LG
LG AS-W186C2U1 Svc manual

Rasonic
Rasonic RC-X7 operating instructions