Rice Lake SCT-2200 User manual

SCT-2200 Fieldbus
DeviceNet™ Quick Setup Guide
Electrical Diagram
Module Connection to SCT-2200 Transmitters
Use the RJ45 and RS-485 directional ports to connect the DeviceNet Fieldbus Module to one or more SCT-2200
RJ45 B (-) 5
RS-485 A (+) 4
+-
12/24 VDC
EARTH
GND
+Vdc
GND
CANL
NC
CANH
NC 1
8
1
8
ERR STS PWR
RJ45 B (-) 5
RS-485 A (+) 4
Note
CONSUMPTION:
50W max
Note
It is recommended
equipment be powered
by a 12-24 VDC LPS or a
Class 3 power source
FIELDBUS
SCT-2200 01
SCT-2200 02
SCT-2200 n
DeviceNet
Up to 16 SCT-2200
units can be
connected.
1
4
5
8
1
4
5
8
B(-)
A(+)
B(-)
A(+)
1
4
5
8
1
4
5
8
B(-)
A(+)
B(-)
A(+)
1
4
5
8
1
4
5
8
B(-)
A(+)
B(-)
A(+)
FIELDBUS
DeviceNet
SCT-2200 01 SCT-2200 n
B(-) B(-)
A(+) A(+)
B(-) B(-)
A(+) A(+)
RJ45
RS-485
RJ45
RS-485
RJ45
RS-485
RJ45
RS-485
RJ45
RS-485
RJ45
RS-485
PN 192847
July 12, 2019

DeviceNet Quick Setup Guide
2 Visit our website www.RiceLake.com
Configuration
The weight transmitter menu is used to configure the DeviceNet Module.
1. Reboot the weight transmitter.
2. Press the key while the display check is in progress to access the menu:
Parameter Descriptions
Enables HUB mode Sets the of the module
In HUB mode, identifies the primary scale in the network to set the Parameters
Selects the baud rate (10 Kb/s to 1 Mb/s)
If = or , RS-485 baud rate is automatically set to 115,200 and scale address = .
Functioning Modes
Single Scale Mode Hub Mode
Single Scale Mode Configuration Hub Mode Configuration
In hub mode all of the parameters must be configured for the primary
unit (scale 01). Secondary units need only a few parameters
Scale Primary Scale 1 Secondary Scale 02 Scale 03
',9'(&
&$3$&
)/'%86
35L0$5 1R 6&$$''
<(6 1806&$
%867<3
GHYQHW 0DFLG
EDXGU
KXE
\HV
QR
Refer to the SCT-2200 Fieldbus technical manual (PN183523) for full
parameter details.
Note
KXE
0DFLG
35L0$5
EDXGU
Note
FIELDBUS
SCALE
DeviceNet
FIELDBUS
SCALE 01
SCALE 02
SCALE 03
Secondary Unit
Secondary Unit
Primary Unit
DeviceNet
Up to 16 SCT-2200
units can be
connected.

DeviceNet Quick Setup Guide
© Rice Lake Weighing Systems ● All Rights Reserved 3
Input Data (for data reading) - Single Scale Mode
Data Byte DESCRIPTION EXAMPLE
Gross :eight
1(MSB)
Bytes 1, 2, 3 and 4 contain the gross weight value
Gross weight value examples
1000 6000 15000 350000
1(MSB) 00 Hex 00 Hex 00 Hex 00 Hex
200 Hex 00 Hex 00 Hex 05 Hex
303 Hex 17 Hex 3A Hex 57 Hex
4(LSB) E8 Hex 70 Hex 98 Hex 30 Hex
2
3
4(LSB)
Net :eight
5(MSB)
Bytes 5, 6, 7 and 8 contain the net weight value
Net weight value examples
1000 6000 15000 350000
5(MSB) 00 Hex 00 Hex 00 Hex 00 Hex
600 Hex 00 Hex 00 Hex 05 Hex
703 Hex 17 Hex 3A Hex 57 Hex
8(LSB) E8 Hex 70 Hex 98 Hex 30 Hex
6
7
8(LSB)
Input Status
9(MSB)
Bit 7(LSB)
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0(LSB)
No function
No function
No function
No function
No function
No function
Status of input n.2 (0 = OFF; 1 = ON)
Status of input n.1 (0 = OFF; 1 = ON)
Input status
IN1 = OFF
IN2 = OFF
IN1 = ON
IN2 = OFF
IN1 = OFF
IN2 = ON
IN1 = ON
IN2 = ON
9(MSB) 00 Hex 01 Hex 02 Hex 03 Hex
10
(LSB)
----
10(LSB)
Bit 7(MSB)
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0(LSB)
1 = Scale unloaded (gross weight = 0)
Tare PT (1 = PT tare is active)
Tare (1 = Tare is active)
Overload condition (0 = No; 1 = Overload)
Underload condition (0 = No; 1 = Underload)
Weight Stability (0 = Unstable; 1 = Stable)
Gross Weight Polarity (0 =“+”; 1 = “-”)
Net Weight Polarity (0 = “+”; 1 = “-”)
If BYTE 10(LSB) = 45 HEX:
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 1100101
Bit 0 = Net weight is negative
Bit 1 = Gross weight is positive
Bit 2 = Weight is stable
Bit 5/6 = A Preset Tare is in memory
-11(MSB) %LW +HDUWEHDWVWDWXVELWWRJJOHVIURPWRHYHU\VHFRQG
Command Status Register
12(LSB)
Bit 7(MSB)
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0 (LSB)
Last command result
Last command result
Last command result
Last command result
Counting of processed commands
Counting of processed commands
Counting of processed commands
Counting of processed commands
Bit 0 to Bit 3 are used to count received commands, from 0
(0000) to 15 (1111).
Bit 4 to Bit 7 are used to indicate the result of the last received
command:
Bit 7 Bit 6 Bit 5 Bit 4 Result
0 0 0 0 Command OK
0 0 0 1 Incorrect command
0 0 1 0 Incorrect command data
0 0 1 1 Command not allowed
0 1 0 0 Non-existent command
-
13(MSB) No Function Output status
IN1 = OFF
IN2 = OFF
IN1 = ON
IN2 = OFF
IN1 = OFF
IN2 = ON
IN1 = ON
IN2 = ON
13(MSB) ----
14(LSB) 00 Hex 01 Hex 02 Hex 03 Hex
Output 6tatus
register
14(LSB)
Bit 7(MSB)
...
Bit 2
Bit 1
Bit 0(LSB)
No function
...
No function
Digital output 2 status (0 = OFF; 1 = ON)
Digital output 1 status (0 = OFF; 1 = ON)
-
15
--
...
32

DeviceNet Quick Setup Guide
4 Visit our website www.RiceLake.com
Input Data (for data reading) - Hub Mode
DATA* 1 2 3 4 ... 16 DESCRIPTION/EXAMPLE
In/Out 6tatus
191725 ...121
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
00000000
Bit 7
Bit 6/5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Scale present bit (Fixed value = 1)
Progressive command loop counter;
Values: 0 (00), 1 (01), 2 (10), 3 (11)
Last command result (0 = OK; 1 = ERROR)
Status of output n.2 (0 = OFF; 1 = ON)
Status of output n.1 (0 = OFF; 1 = ON)
Status of input n.2 (0 = OFF; 1 = ON)
Status of input n.1 (0 = OFF; 1 = ON)
EXAMPLE:
If Byte 1 = 13 Hex:
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
00001101
Bit 0 = Input 1 is ON
Bit 2 = Output 1 is ON
Bit 3 = Output 2 is ON
Gross :eight
2(MSB)
10
(MSB)
18
(MSB)
26
(MSB)
...
122
(MSB) For each scale there are three bytes containing the gross weight value
1
3000 kg
2(MSB) 00 Hex
30B Hex
4(LSB) B8 Hex
3 11 19 27 ... 123
4(LSB)
12
(LSB)
20
(LSB)
28
(LSB)
...
124
(LSB)
Scale 6tatus
5 132129 ...125
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
00000000
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
1 = Scale unloaded (gross weight = 0)
Tare PT (1 = PT tare is active)
Tare (1 = Tare is active)
Overload condition (0 = No; 1 = Overload)
Underload condition (0 = No; 1 = Underload)
Weight Stability ( 0= Unstable; 1 = Stable)
Gross Weight Polarity (0 = “+”; 1 = “-”)
Net Weight Polarity (0 = “+”; 1 = “-”)
EXAMPLE:
If BYTE 5 = 45 HEX:
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
01100101
Bit 0 = Net weight is negative
Bit 1 = Gross weight is positive
Bit 2 = Weight is stable
Bit 5/6 = A Preset Tare is in memory
Net Weight
6
(MSB)
14
(MSB)
22
(MSB)
30
(MSB)
...
126
(MSB) For each scale there are three bytes containing the net weight value
3
1000 kg
22(MSB) 00 Hex
23 03 Hex
24(LSB) E8 Hex
7 152331 ...127
8
(LSB)
16
(LSB)
24
(LSB)
32
(LSB)
...
128
(LSB)

DeviceNet Quick Setup Guide
© Rice Lake Weighing Systems ● All Rights Reserved 5
Output Data (for sending commands)
Command Byte Description Example
Transmitter ID
1
Select the transmitter to receive the command:
Transmitter
Value
Transmitter 01 01 Hex
Transmitter 02 02 Hex
Transmitter 03 03 Hex
... ... Hex
Transmitter 16 10 Hex
NOTE: Transmitter ID must be set for each command.
To zero the weight of transmitter number 4:
Byte
Value
104 Hex
201 Hex
Command
2
Main available commands:
Value
Command
00 Hex
No command
01 Hex
Scale zeroing
02 Hex
Tare
03 Hex
Preset Tare
0A Hex
Setpoint 1 setting
0B Hex
Setpoint 2 setting
19 Hex
Digital output setting
22 Hex
Reboot the weight transmitter
23 Hex
Read the calibration data
24 Hex
Write the calibration data
25 Hex
Calibration point acquisition
26 Hex
Abort the calibration procedure
28 Hex
Lock keyboard (parameter 1 = 0);
Unlock keyboard (parameter 1 = 1)
NOTE: To repeat the last command, set the command to “No
command” value (0000 Hex) then repeat the command.
EXAMPLE 1
For setting a preset tare of 1000 kg:
1. Set the transmitter address in byte 1
2. Set the command in byte 2
3. Set the tare value in parameter 1
(byte 3, 4, 5, 6)
Byte
Value
101 Hex
203 Hex
3(MSB) 00 Hex
400 Hex
503 Hex
6(LSB) E8 Hex
EXAMPLE 2
For setting the setpoint n. 1 of the scale n. 2 to 1000 kg:
1. Set the transmitter address in byte 1
2. Set the command in byte 2
3. Set the setpoint value in parameter 1
(byte 3, 4, 5, 6)
Byte
Value
102 Hex
20A Hex
3(MSB) 00 Hex
400 Hex
503 Hex
6(LSB) E8 Hex
Parameter 1
3
(MSB)
First parameter of the command.
Parameter is always expressed in absolute mode (no decimals, no
sign).
4
5
6
(LSB)
Parameter 2
7
(MSB)
Second parameter of the command.
Parameter is always expressed in absolute mode (no decimals, no
sign).
8
9
10
(LSB)
-
11
-
-
...
32

DeviceNet Quick Setup Guide
6 Visit our website www.RiceLake.com
Calibration Procedure
DESCRIPTION EXAMPLE
1. Send command 23 Hex to the transmitter to adjust calibration (transmitter ID has to
EHVSHFL¿HGLQE\WH
Byte Value Description
103 Hex Transmitter n. 3
223 Hex Command
2. Select SDJH 5001 for calibration using the CHANGE PAGE
FRPPDQG'+H[
Byte Value Description
103 Hex Transmitter n. 3
21D Hex Change page
3(MSB) 00 Hex
+H[
400 Hex
513 Hex
6(LSB) 89 Hex
6HWWKHVSDQDGMXVWPHQWZHLJKWRQSDJHIURPE\WHWRLIGLIIHUHQWIURP
WKHRQHXVHGGXULQJWKHODVWFDOLEUDWLRQ
Weight value examples
1000 6000 15000 350000
19(MSB) 00 Hex 00 Hex 00 Hex 00 Hex
20 00 Hex 00 Hex 00 Hex 05 Hex
21 03 Hex 17 Hex 3A Hex 57 Hex
22(LSB) E8 Hex 70 Hex 98 Hex 30 Hex
4. Send “WRITE CALIBRATION”FRPPDQG+H[ZLWK
SDUDPHWHU +H[
6HHH[DPSOHRISRLQWEXWE\WH +H[
:ULWH&DOLEUDWLRQ
=HURFDSWXUHXQORDGWKHVFDOHDQGZULWHWKH³ACQUISITION POINT”
FRPPDQG+H[ZLWKSDUDPHWHU
Byte Value Description
103 Hex Transmitter n. 3
225 Hex Acquisition point
3(MSB) 00 Hex Zero point
acquisition
4/5 00 Hex
6(LSB) 00 Hex
5HDGWKHFDOLEUDWLRQVWDWXVLQWRSDJHE\WH
If acquisition is OK, then proceed with step 7; otherwise check the load cell mV/V
PXVWEHVWDEOHDQGUHSHDWVWHS
3006% 31/6%
00 Hex 00 Hex Calibration not started
00 Hex 01 Hex $FTXLVLWLRQXQGHUZD\
00 Hex 02 Hex Acquisition OK
00 Hex 03 Hex Acquisition error
00 Hex 04 Hex Calibration OK
00 Hex 05 Hex Calibration error
6SDQFDSWXUHORDGWKHVFDOHZith span weight and write the
“ACQUISITION POINT”FRPPDQG+H[ZLWKSDUDPHWHU ³´
If acquisition is OK, proceed to step 8; if not check the load cell mV/V (must be stable
DQGJUHDWHUWKHQ]HURSRLQWDQGUHSHDWVWHS
Byte Value Description
103 Hex Transmitter n. 3
225 Hex Acquisition point
3(MSB) 00 Hex
Span acquisition4/5 00 Hex
6(LSB) 01 Hex
8. Store calibration using the “WRITE CALIBRATION”FRPPDQG+H[ZLWK
parameter 1 = 0
Byte Value Description
103 Hex Transmitter n. 3
224 Hex Write calibration
3(MSB) 00 Hex
Store calibration
4/5 00 Hex
6(LSB) 00 Hex

DeviceNet Quick Setup Guide
© Rice Lake Weighing Systems ● All Rights Reserved 7
Messages
Hub Module Error Codes
Network Error Codes
Annunciators
All LED annunciators turn on during the fieldbus module start-up to verify correct functioning.
Message Description
No connection received from module Hub after 30 seconds
Firmware version of the module hub
Start the Communication between hub module and scale
Communication on fieldbus network configured and running
+code Error state, see table error codes
Fieldbus initialization
Code Description
1000 Fatal error in hub module
1001 Inconsistency between protocol type selected and the one managed by the Hub module, e.g. Hub type DeviceNet module
with Profinet protocol selected on SCT
1-18 Other fatal error in Hub module
000001 and the following Unrecoverable error module Hub
Code Description
000140 General network error
000141 Connection closed
000142 Time-out connection
000143 Isolated network
000144 Duplicated node
000145 Network cable disconnected
Annunciator Descriptions
Blinking green – initializing fieldbus module
Solid green – fieldbus module is ready
STATE
Indicates the RS-485 communication state between fieldbus module and weight transmitter:
Solid yellow – initializing communication
Rapid blinking yellow – fieldbus module is communicating correctly
Slow blinking yellow – fieldbus module is attempting to communicate with the wieght transmitter (no communication)
ERROR Off – communication is OK
Solid or blinking red – no communication with the fieldbus master; check the cable connection, protocol and the PLC configuration
STATE
ERROR
Note

230 W. Coleman St. • Rice Lake, WI 54868 • USA
U.S. 800-472-6703 • Canada/Mexico 800-321-6703 • International 715-234-9171 • Europe +31 (0)26 472 1319
Rice Lake Weighing Systems is an ISO 9001 registered company.
© Rice Lake Weighing Systems Specifications subject to change without notice.
www.ricelake.com
PN 192847
July 12, 2019
Other manuals for SCT-2200
5
Table of contents