SEFRAM SEQUENCER SET18DP User manual

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 1 / 25
Outputs SV AC version
PLACE GUTENBERG - 59175 TEMPLEMARS (France)
Tel: +33(0)3 20 60 49 49 - Fax: +33(0)3 20 95 59 62
Email: contact@sefram.eu Web: www.sefram.eu
Electronics dedicated to dedusting and air
quality

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 2 / 25
S
UMMARY
:
DESCRIPTION
:
SET18DP is an adjustable device for control and full
automatization of dedusting equipments, whose declogging is done
by pressured air injections.
Permanent control of differential pressure allows an optimal
efficiency according to the whole parameters, for any type of
exploitation and product.
It is equiped of a sequencer and a differential pressure switch or
relative pressure switch (load loss dP).
It has 18 outputs to be linked to solenoïd valves with electric
default check, 1 loop control input (I1), 1 relay output for default or
alarm report, and in option, 1 analogic output 4-20mA for report of
loss pressure measure dP information.
The device is adjustable, according to the use of it, with several
levels, protected by passwords.
All the running parameters can be seen and adjusted on the
front panel of the device, thanks to a graphic colour touch screen
Interface is multilingual.
Evolution of the declogging cycle, the running defaults and the
pressure loss measure are clearly displayed and detailed.
A graphic representation of pressure loss allows to easily check
its level.
The device has a counter of cycles which have been done and
records mini and maxi measured pressures.
Remark : this notice is based on a device equipped of pressure
loss measure, with 18 outputs and with a 4-20 mA output. In case
the device is not equipped of 4-20 mA output, functions linked to it
are not taken into consideration. The quantity of outputs defines the
terminals and glands configuration.
Page
- DESCRIPTION 2
- CHARACTERISTICS 3
- DIMENSIONS AND MOUNTING 4
- PROTECTION 6
- CONNECTIONS 7
- USER INTERFACE
Main page
Measure dp page
Sequencer informations page
General menu page
Language page
Safety levels page
Parameters page
Manual running page
System info page
10
10
12
13
14
15
16
17
21
22
- RUNNING 22
- FAULTS 23
- RELAY OUTPUT 23
- WARNING 23
- CALIBRATION 23
- GENERAL INSTRUCTIONS OF
SAFETY, ASSEMBLY,
COMMISSIONNING AND
MAINTENANCE
24
- WARRANTY 25
- CERTIFICATE 25

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 3 / 25
CHARACTERISTICS :
- Supply voltage (nominal voltage) : 115/230V 50-60 Hz
24V/48V 50-60 Hz
- Consumption (nominal current) maxi : 5VA + consumption of solenoïd valves voltage
- Protection : With fuse 5x20mm (see table 1)
- Solenoid valves voltage : According to supply voltage (see table 1)
24V/48V/115V/230V 50-60 Hz – Pmax:25Va
- Characteristics of input (I1): Tension : 24VDC supplied by device
load current +/- 1mA
- Characteristics of relay contact : Dry contact max: 125VAC/0.3A - 30VDC/1A
(to be protected by user)
- Ambient operating temperature : -20°to 60°C
- Storage temperature : -20° to 70° C
- Box : ABS - IP65
- Display : Touch screen / size 4.3inches / resolution 480x272
65536 colours / LED / Buzzer
SEQUENCER :
- Maxi outputs quantity 18
- Time T1 : activation of an output from 3/100th to 255/100th of a second
- Time T2 / T2A : idle between 2 outputs 1 - 255 seconds
- Time T3 : rest time between 2 cycles 0 - 255 minutes
- Time T4 : automatic dust removal cycle 0 - 255 hours
- Number of cycles if fan stopped 0 - 255 cycles
- Number of cycle in manual operation 0 - 255 cycles
DP MEASURE :
- Scale 0-500 daPa
- Maxi pressure ( P+ > P- ) 400 mbar
- precision classe 2on the maxi scale of sensor (100 mbar)
→from 0 to 60°C this class takes into consideration linearity,
hysteresis, temperature and repetitivity effects
- Action time order dP 1 second
- Action time alarm high/low/T2A threshold 5 seconds
- Output 4-20mA Integrated supply, not isolated - Maxi load : <500 Ohms
Table 1 : Supply voltage/Solenoïd valves voltage/Fuse
Supply voltage 230VAC 115VAC
Solenoid valves voltage 230VAC 48VAC 24VAC 115VAC 48VAC 24VAC
Calibre fuse F1 F1A F1A
Calibre fuse F2 F1A F1A
Calibre fuse F3 F1A F1A
Supply voltage 48VAC 24VAC
Solenoid valves voltage 48VAC 24VAC 24VAC
Calibre fuse F1 F1A F1.6A
Calibre fuse F2 F1A F1.6A
Calibre fuse F3 F1A F1A

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 4 / 25
DIMENSION AND MOUNTING :
+ : dirty air side
-
: clean air side
Connection
for pipe
6/8mm
Tightening capacity of glands :
ISO 16 From 4 to 8mm
ISO 20 From 7.5 to13mm
ISO 20b From9.5 to 15mm
If version till 18 SV by multiconductor
cable
(1 common + ground for 6 SV)
+
-
+
-
if version
with output
4-20mA

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 5 / 25
+ : dirty air side
-
: clea
n air side
Connection
for pipe
6/8mm
Tightening capacity of glands :
ISO 16 from 4 to 8mm
ISO 20 from 7.5 to13 mm
If version till 10 SV
by individual cables
(1 common + ground per SV)
+
-
+
-
If version
with output
4-20mA

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 6 / 25
PROTECTION :
Protection fuse of SV outputs is reachable after dismounting the connections cover.
(see table 1 for the calibre of the fuse).
VOLTAGE CHOICE :
It is possible according to the version of the sequencer to set differently the supply voltage and the solenoid valves
voltage of that made by default in factory answering the ordered version.
warning: the device must be switched off.
Remarks:
- The supply choices "115V / 230V" or "24 / 48V" can be made only with order
- If supply voltage "115V / 230V", the voltage choice of solenoid valves " 24V or 48V " can be made only with
order
See on the following table the possible regulations according to the version of the box.
ACCORDING TO THE SUPPLY
VOLTAGE / SOLENOID
VALVES VOLTAGE VERSION
POSITION OF THE JUMPERS :
230VAC / 230VAC
48VAC / 48VAC
Fuse F1 et F2 :
General protection
of the device
Fuse F3 :
Protection of outputs
solenoid valves
Jumper on :
S2 / S3 / S4
Nothing on :
S1 / S5 / S6

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 7 / 25
115VAC / 115VAC
24VAC / 24VAC
230VAC / 24VAC
230VAC / 48VAC
115VAC / 24VAC
115VAC / 48VAC
WARNING: a modification of the supply voltage and/or the solenoid valves voltage requires to update the
descriptive label placed outside of the box.
Jumper on :
S1 / S3 / S4
Nothing on :
S2 / S5 / S6
Jumper on :
S2 / S5 / S6
Nothing on :
S1 / S3 / S4
Jumper on :
S2 / S5 / S6
Nothing on :
S1 / S3 / S4

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 8 / 25
CONNECTIONS :
Connections must be done when power off.
Connections terminals are reachable after opening the transparent front panel and dismounting cover (lower part of
the box).
According to configuration of the device, some terminals may not be included.
Cable strings will be flexible and will have a section between 0.5 and 1.5 mm2.
If version till 18 SV with multiconductor cable (1 common + ground for 6 SV) :
Supply
Depending on
the version
115V/230V
24V/48V
50/60Hz
Connections of outputs
Solenoid valves 1
to
18
Output 4-20mA for register,
indicator, etc.
Maximal load : 500 ohms
Output information
default/alarm
Input I1

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 9 / 25
If version till 10 SV with individual cable (1 common + ground for each SV) :
Supply
Depending on
the version
115V/230V
24V/48V
50/60Hz
Connection of outputs
Solenoid valves
1
to
10
Output 4-20mA for register,
indicator, etc.
Maximal charge : 500 ohms
Output information
default/alarm
Input I1
10x commo
n EV
10x ground SV 1 to 10

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 10 / 25
USER INTERFACE :
User interface is done through the touch screen on front panel of the box.
When the device is switched on, logo of the company is displayed during 3 seconds, then main menu is displayed.
To activate a function or access to adjustment of a parameter: press the corresponding area.
Remark : after 30 seconds without any action, main menu is automatically displayed (unless « dP measure »
screen is displayed ).
Main menu, if no fault :
Main menu, if fault :
1 : Display of load loss dP ( daPa )..
If high dP alarm or low dP alarm is on, the background of this area flashes in red.
If one touches this area : link towards measure display « load loss dP ».
1
3
4
5
6
2
7
11
9
8
10

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 11 / 25
2 : Information about state of declogging cycle.
Display of running time and countdown.
Display of last SV activated and the following SV.
If press this area : link to the display « sequencer informations ».
3 : Display of AON I1 input .
Gray : if input I1=0
Green : if input I1=1
4 : Display of High Alarm dP.
Gray : if measure is below the High Alarm threshold.
Red : if measure is above the High Alarm threshold.
Remarks : High Alarm has a delay of 5 seconds.
High Alarm is not activated if adjusted to 0 value.
5 : Display of Low Alarm dP.
Gray : if measure is above the Low Alarm threshold.
Red : if measure is below the Low Alarm threshold.
Remarks : Low Alarm has a delay of 5 seconds.
Low Alarm is not activated if adjusted to 0 value.
6 : Display of dP running order.
Gray : if dP running order is absent (if measure is below Mini threshold).
Green : if dP running order is present (if measure is above Maxi threshold.
Remarks : the dP order has a delay of 1 second.
The dP order is always present if Mini and Maxi thresholds are adjusted to 0.
7 : If press this area : link towards page « main menu ».
8 : Display of current protection level.
9 : If fault : displays the type of fault
10 : If fault : this red sign « warning » is flashing
11 : If fault : pressing this area will reset the displayed fault.

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 12 / 25
Page measure load loss dP :
1 : Graph of the measure of load loss dP.
Display of the 7.5 last hours of running of the device (1pt every 90 seconds). When device is turned off, the
graph is reset.
The different running thresholds and alarm thresholds are displayed by horizontal lines with colour
corresponding to the legend, on the left part of the screen.
Remark : if one running threshold or one alarm threshold is adjusted to 0, this one will not be displayed.
2 : If press this area : go back to main page.
3 : Display of measure values of load loss dP mini and maxi, which are observed.
Remarks : The mini value is observed two minutes after detection of fan running.
The maxi value is not observed between the start of a declogging shot and 3 seconds after this shot.
4 : Only reachable at level 2.
Pressing this area resets the observed mini and maxi load loss values.
Remarks : the maxi is preset at 0. This value is updated when the first maxi value is observed.
the mini is preset at 999. This value is updated when the first mini value is observed.
5 : Display of immediate load loss measure dP.
6 : Display of current protection level.
1
4
2
5
3
6

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 13 / 25
Page sequencer informations :
1 : Displays the number of the last SV activated.
Remark : if there is not any declogging cycle since the device has been switched on, it indicates 0
2 : Displays the number of the next SV which will be activated.
3 : Information about the state of the declogging cycle.
Displays the running time and its countdown.
4 : Counter of cycles done (user).
5 : Counter of cycles done (manufacturer).
6 : If press this area : return to main page.
7 : Displays the current protection level.
8 : Reachable only at level 1.
If press this area, the counter « number of user cycles » is reset
9 : Reachable only at level 2.
If press this area, the counter « number of manufacturer cycles » is reset.
10 : Value of the set point for maintenance message (nb of thousands of cycles).
If number of manufacturer cycles is reaching this set point value, a message appears in the main
page : « MAINTENANCE REQUIRED ».
If set at 0 : the function is not active. No message.
11 : Reachable only at level 2.
Adjustment of set point for maintenance.
1
2
3
4
5
8
9
7
6
11
10

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 14 / 25
Page main menu :
1 : If press this area : go back to main page.
2 : If press this area : jump to page « safety ».
3 : If press this area : jump to page « language ».
4 : If press this area : jump to page « adjustments ».
5 : If press this area : jump to page « system informations ».
6 : If press this area : jump to page « manual running ».
7 : Displays the current protection level.
1
4
2
5
3
6
7

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 15 / 25
Page language :
1 : If press this area : changes to English language and jumps to main page.
2 : If press this area : changes to French language and jump to main page.
3 : If press this area : go back to page menu.
4 : If press this area : go back to main page.
5 : Displays the current protection level.
1
2
5
3
4

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 16 / 25
Page safety levels :
The users are classified into 3 levels : level 0, level 1 and level 2.
Levels 1 and 2 are protected by password.
Access to some functionalities or modification of some parameters are possible, according to the protection level
we have.
Level 0 : it is not possible to change any parameter, we can only see the parameters.
Reset of faults is possible. Manual running is possible. Change of language is possible.
Level 1 : corresponds to level « user », allowing change of parameters.
Level 2 : corresponds to level « manufacturer ». This level gives access to all possibilities of level 1, with also the
possibility to reset some counters, for instance.
1 : If press this area : request password.
According to the password entered, corresponding level is active.
Remark : if password is not correct, we move to level 0.
When a password is entered, it stays active 10 minutes long. After 10 minutes, we automatically
move to level 0.
At the 1
st
use of the device, the password for level 1 is “0000”.
2 : If press this area : moves to level 0.
Remark : the key is only here when level is different than 0
3 : Display of current protection level.
4 : Allows modification of password of the current level and lower level(s).
5 : Display of current protection level.
6 : If press this area : go back to page menu.
7 : if press this area : go back to main page.
1
2
3
4
5
6
7

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 17 / 25
Page parameters 1/4:
1 : T1 : pulse time on one declogging SV.
Adjustable from 3 to 255 1/100th seconds (reachable at level 1 or above).
2 : T2 : rest time between two pulses of declogging SV.
Adjustable from 1 to 255 seconds (reachable at level 1 and above ).
3 : T2A : second rest between two pulses of declogging SV.
T2A time (shorter than T2) replaces T2 time if accelerated running (pressure>threshold T2A).
Adjustable from 1 to 255 seconds (reachable at level 1 and above ).
4 : T3 : rest time between two declogging cycles.
Adjustable from 0 to 255 minutes (reachable at level 1 and above). If adjusted to 0 : not active.
5 : T4 : maximum time without declogging cycle.
If the device did not have any declogging cycle for the quantity of hours which is adjusted, the ongoing cycle is stopped
(if stop in cycle) and a declogging cycle is launched.
Remark: T4 time is reset at each pulse on any SV.
Adjustable from 0 to 255 hours( reachable at level 1 and above ). If adjusted to 0 : not active.
6 : Quantity of declogging SV.
Adjustable from 1 to 18, according to the quantity of SV which are connected (reachable at level 1 and above).
7 : Adjustment of the type of declogging stop, in case we lose the running order :
« End of cycle » : the ongoing cycle ends up.
« On cycle » : cycle stops during its running (at the SV where cycle is, at the end of the T2 time). It will start
again where it was. (reachable at level 1 and above).
8 : Condition to let the declogging cycle, linked to T4 time, runs.
Two possible choices : « whatever input I1 » or « if I1 Input=1 »
9 : Display of ongoing protection level.
10 : If press this area : go back to page menu.
11 : If press this area : go back to main page.
12 : If press this area : goes to the next adjustments page.
1
9
10
6
7
8
2
3
4
5
11
12

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 18 / 25
Page parameters 2/4:
1 : We choose if dP order is or isn’t taken into consideration to launch declogging cycle (reachable at level 1 and
above). « with dP » : declogging depends on dP order.
« without dP » : declogging does not depend on dP order.
2 : Threshold Maxi dP : if measure dP is above this threshold, more than one second, dP running order moves to
« ON » status (reachable at level 1 and above).
3 : Threshold Mini dP : if measure dP is below this threshold , more than one second, dP running order moves to
“OFF” status (reachable at level 1 and above).
Remark : if threshold Maxi dP=0 and threshold Mini dP=0, then the dP running order is forced on « ON » status.
4 : Threshold T2A : threshold corresponding to accelerated running (reachable at level 1 or above ).
If measure dP is above this threshold more than 5 seconds →accelerated running →T2 = T2A
If measure dP is below this threshold more than 5 seconds →normal running
Note : if threshold T2A is adjusted to 0, the function is not active (always in normal running).
5 : Threshold High Alarm dP (reachable at level 1 or above).
If measure dP is above this threshold more than 5 seconds →High Alarm dP
If measure dP is below this threshold more than 5 seconds →No High Alarm dP
Note : If threshold of High Alarm is adjusted to 0, the function is not active (no High Alarm dP generated)
6 : Threshold Low Alarm dP (reachable at level 1 or above).
If measure dP is below this threshold more than 5 seconds →Low Alarm dP
If measure dP is above this threshold more than 5 seconds →No Low Alarm dP
Note : If threshold of Low Alarm is adjusted to 0, the function is not active (no Low Alarm dP generated)
7 : Display of measure of instantaneous load loss dP.
8 : Adjustment to zero pressure (reachable at level 1 and above).
Allows to make a calibration at 0 pressure. Put the device out of pressure (disconnect the two pressure
connections) and press this area : zero pressure is calibrated.
9 : Display of current protection level.
10 : If press this area : go back to the former adjustments page.
11 : If press this area : go back to main page.
12 : If press this area : goes to the next adjustments page.
9
10
11
12
1
2
3
4
5
6
8
7

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 19 / 25
Page parameters 3/4:
The device can detect a fan stop, by two ways : by I1 input or by measure of load loss dP. When it moves from
running fan state to stop fan state : the quantity of declogging cycles is done.
Remark : if during the achievement of the indicated number of declogging cycles, the fan stops and starts again,
the running declogging cycle stops and we start again with standard running.
1 : Choose the type of detection for fan stop(reachable at level 1 or above) :
«by input I1loss » : the stop of the fan is detected if I1=0.
Remark : the running of the fan is detected if input I1=1
«by dP loss » : the stop of the fan is detected if the load loss measure is lower than the value indicated on the
next parameter (see point 2).
Remark : the running of the fan is detected if the load loss measure dP is higher than the indicated value,
more than 5 seconds.
2 : If the type of detection of fan stop is « by dP loss», this value shows the detection threshold (reachable at level
1 and above). Adjustable from 5 to 20 daPa.
3 : Number of cycles to run when the fan stops.
Adjustable from 0 to 255 cycles (reachable at level 1 or above). If adjusted at 0 : not active.
4 : Display of the current protection level.
5 : If press this area : go back to previous parameter page.
6 : If press this area : go back to main page.
7 : If press this area : moves to the next parameters page.
5
1
4
2
3
6
7

SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0452.0617E
Page 20 / 25
Page parameters 4/4:
If the device is equipped of the 4-20mA output for the report of load loss measure, this page allows to define the
scale of this output.
The output is at 4mA if the load loss measure dP=0 daPa.
The output is at 20mA if the load loss measure dP=indicated value.
Between 4 and 20 mA, the output is linear and proportional to the load loss measure dP.
1 : Adjust the value of load loss measure corresponding to output 20 mA (reachable at level 1 or above) .
2 : Display the current protection level.
3 : If press this area : go back to previous parameters page.
4 : If press this area : go back to main page.
5 : If press this area : moves to page menu.
1
2
3
4
5
This manual suits for next models
1
Table of contents
Popular Switch manuals by other brands

BZB Gear
BZB Gear BG-UHD-KVM41 user manual

Swedstyle
Swedstyle LOGIClink manual

IBM
IBM RedBooks SAN24B-5 Installation, service and user guide

STIEBEL ELTRON
STIEBEL ELTRON DWS 1 installation instructions

Enabling Devices
Enabling Devices 718-S user guide

Grundfos
Grundfos IO 50 SQFlex Installation and operating instructions