MODBUS/RTU CONFIGURATION
Flexible Modbus/RTU addressing is enabled by default on the CIO-EN. This means that when the
CIO-EN is connected and communicating to a 777-P/P1 overload relay, the CIO will automatically
assume and keep the Modbus address of the overload. If the CIO-EN is used as a stand-alone
device, its Modbus address is defaulted to 1.
MODBUS/RTU COMMUNICATIONS
The CIO-EN Module provides the ability to communicate with both an upstream device
(Modbus/RTU master) and a 777-P/P1 (Modbus slave). In order to communicate with the CIO-EN
via an upstream device such as a PLC, DCS, SCADA system or PC, an RS-485 network must exist
between the upstream device and the CIO-EN. The upstream device must be connected to the
CIO-EN using an 18-24 AWG shielded, twisted-pair cable connected to A, B, and Shield of the 5-pin
connector on the front of the CIO-EN module. The CIO-EN can be programmed as device address
01 to 99 and can communicate at baud rates of 9600, 19200, 38400, and 57600. The default
communications settings for the CIO-EN are:
•Baud Rate: 19200
•Parity: Even
•Modbus Address: Flexible when attached to overload; 1 when stand-alone
Terminating Resistors
The RS-485 network may require terminating resistors if the length between the CIO-EN and an
upstream device exceeds 100 feet or if the twisted pair cable is in a noisy environment. When
terminating resistors are required, 120Ωterminating resistors should be connected at both the
CIO-EN (across A and B) and also at the upstream device (also across A and B). SymCom
recommends that terminating resistors be used in all circumstances to optimize RS-485 signals.
E
xisting Network Installations
The CIO-EN can be added to a Model 777-P/P1 overload in an existing network. Flexible addressing
is enabled by default; therefore, the CIO-EN will automatically assume the address of the 777-P/P1
upon being plugged into the overload.
Equipment Setup
1. Connect the CIO-EN to the Modbus network using the communication terminals on the front of
the unit (A, B and Shield).
2. Connect the CIO-EN to the overload using the serial port on the side of the overload.
3. Connect the power supply terminals to V+ and V- of the CIO-EN.
NOTE: Ensure the power supply output is set to 24 VDC, and that it is off while being
connected to the CIO-EN.
4. Power the overload, and then power the CIO-EN.
M
odbus/RTU Network Solutions Setup
1. Open Solutions
2. Click Modbus/RTU in the Select Network Connection Type box.
3. Ensure the network communication settings are correct, and the device connections are correct.
4. Right click the network window and select Auto Detect for Units. All units on the network will
be automatically detected and should appear on the screen—click on a unit to view its
properties.
NOTE: If the unit does not appear on the screen, recheck the device connections and
network communication settings. Reattempt to Auto Detect for Units.