TERMET ECOCONDENS SILVER PLUS-25 User manual

COMBI BOILERS
SYSTEM BOILERS
ECOCONDENS SILVER PLUS -20
ECOCONDENS SILVER PLUS -25
ECOCONDENS SILVER PLUS -35
ECOCONDENS SILVER PLUS -20
ECOCONDENS SILVER PLUS -25
ECOCONDENS SILVER PLUS -35
1450

DEAR CUSTOMER
Congratulations on having chosen termet product.
We are glad that we can offer you modern, economical and environmentally friendly product, meeting particularly high requirements of European Standards.
Please read this instruction manual carefully as the knowledge of service rules and manufacturer’s recommendations are the conditions of reliable, efficient and safe
operation of the appliance.
Please keep this instruction manual for the whole operation life of the boiler.
We wish you satisfaction in using our product.
termet
IMPORTANT INFORMATION
•Read the instruction manual before you perform the installation and operation of the boiler.
•This instruction manual is an integral equipment of the boiler. It should be kept through the whole operation life of the boiler and carefully read. It contains all the
information and warnings for safety during installation, use and maintenance to be followed.
•The boiler is complicated appliance as it contains numerous precise mechanisms.
•Reliable operation of the boiler depends mainly on appropriate performance of systems that boiler cooperates with such as:
- gas system,
- flue gas-air system,
- central heating system,
- domestic hot water system.
•Flue gas - air installation for C type boilers should be made of separately approved and introduced on the market gas - air system. Adapters connecting the boiler
with a pipe system must have a measuring points. Flue gas – air system must meet the specifications set out in section 3.8 of this manual.
•Flue gas - air system must be tight. Leaks on the connections of flue gas pipes can result in flooding of the boiler by condensate. Manufacturer is not liable for
damage and malfunction of the boiler arising out from above mentioned reason.
•Installation of the boiler should be performed only by a qualified person1). Make sure that the installer has confirmed in writing the tightness of the gas
installation had been checked after connecting the boiler to the system.
•Boiler may be installed and operated only in a room where all building works have been completed. It is not allowed to install and operate the boiler in a room
where building works are still in progress.
•The cleanliness of air in a room where the boiler will be installed must meet the same requirements as for rooms designer for people.
•There should be installed appropriate filters on a central heating system and gas system . Filters are not included in a basic boiler equipment.
•An example of connecting a boiler to these systems is presented on fig. 3.5.1.
•All defects caused by lack of filters on central heating or gas supply will not be repaired under guarantee.
•Central heating system must be thoroughly cleaned and rinsed, the procedure is described on p.3.5.2.
•To avoid malicious calcification process of flue gas - water heat exchanger and also for reduce a risk of other items damage, there should be:
- the proper water preparation in C.H. circuit according to p.3.5.2, Proper water parameters in C.H. system allows for long term operation maintaining its high
efficiency, what leads to lower costs of gas consumption,
- proper tightness of central heating system ensured by avoiding frequent refilling it with water,
•Complaints caused by gas-water heat exchanger calcification will not be repaired under guarantee.
•The initial start-up of the boiler as well as its repairs, adjustments and maintenance works must be performed only by AUTHORISED SERVICE COMPANY.
•The boiler must be operated only by an adult.
•Do not do any repairs and modifications by yourself.
•Do not cover any ventilation grilles.
•Do not keep in the vicinity of the boiler any containers with flammable, aggressive and corrosive liquids and other similar substances.
•Any failures that are result of operation discordant to recommendations included in this instruction manual cannot be subject to warranty claims.
•Manufacturer is not responsible for any failures being the result of faults during the process of installation and inobservance the regulations and instructions given
by the manufacturer.
•Complying with recommendations given in this instruction manual ensures a long, reliable and safe operation of the boiler.
NOTICE!
When you smell gas:
- do not use any electrical switches that could cause any spark,
- open the door and windows,
- shut down the main gas valve,
- immediately contact your gas supplier.
In case of any failure you should:
- disconnect the boiler from a power source,
- shut down the gas supply valve,
- cut off a water supply and drain a water from the boiler and whole central heating system as well (when there is any risk of
freezing of the system),
- drain the water from the system in any case of leakage that could cause a flood ,
- contact the nearest AUTHORISED SERVICE COMPANY or the producer.
1) ‘Qualified person’- person that has all required technical qualifications in an area of doing all the works necessary to connect appliances to the gas mains, central heating
system and flue gas duct, accordingly to local regulations.

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.1
Fig. 3
WARNING!
Operational instruction during the start-up of the condensing boilers
The instruction should be used after every draining water in the boiler
i.e. during the renovation of C.H. installation or repair of the boiler.
Read carefully the instruction manual before filling the boiler with water
1. Fill the heating circuit with water and vent the radiators before start.
2. Check the correctness of connection the electrical cords of boiler (network 230 V/50 Hz) to the network:
L- brown; N – blue; PE – yellow-green. Do not change the cords L and N!
In case of change the cords, the boiler will enter in failure state, on display will occur an error code E01.
Mark the cords properly when connected directly to the electrical box, to eliminate the possibility of
exchange.
3. Close the gas cut-off valve!
4. Open valves which cut-off the boiler from C.H. circuit.
5. Remove the front cover of the boiler by unscrewing the relevant fixing screws (fig. 1).
6. Remove the front cover of the combustion chamber (fig. 2).
7. Loosen the stopper on the automatic air-vent of the pump. In order to protect the pressure transducer from
water, point the outlet of stopper to the right (fig. 3).
8. Turn on the device. Wait until the start procedure, testing the internal subassembly’s and ventilating the
combustion chamber will end (time about 10 – 30 sec.)
9. Fill the boiler with water by using the filling valve (in case of system boilers – the filling valve is mounted on
C.H. installation, in case of combi boilers – the filling valve is on the boiler’s equipment – see p.3.5). Open
the filling valve slowly to protect the boiler’s and the C.H. installation’s components against the results of a
hydraulic shock.
10. During filling the boiler with water control the pressure by using the analogue manometer mounted on the
boiler’s front cover or the electronic manometer by reading the pressure from display of the controller
(depending on the boiler’s type). Shut off the filling valve after reaching the pressure of 1,0 – 1,5 bar.
Note: in some models of boilers, after end of the start procedure, the “support the venting of boiler” function
starts. This function is signalized on the controller display by “Po” and lasts 3 min. Start the “support the
venting” function requires the water pressure above 0,5 bar, that’s why during this procedure check and fill
up the water pressure in the boiler, it is best to maintaining it the range of 1,0-1,5 bar.
11. Set the operating mode on WINTER according to the boiler instruction. If to the boiler controller has been
connected the room thermostat than increase the desired temperature; the boiler should start operating in
C.H. mode.
12. Because the gas valve outside the boiler is closed, the boiler will stop operate (E01 error code – a lack of
gas). It allow for continuous pump operation and for removal of the air flowing in with water from the
installation and for continuous water flow through the heat exchanger. Leave the boiler in this state for 2-3
min.
13. Delete E01 code by “reset” button and set the boiler controller on pressure reading mode (in version without
an analogue manometer). During the first days of boiler operating it is recommended to set the water
pressure in C.H. circuit on 1,8-2,0 bar. It will facilitate the work of the air-vent on the boiler pump and on the
components of C.H. circuit. **
14. Unscrew the gas valve and delete E01 code again.
15. Set the desired operating parameters of the boiler according to the instruction manual. ***
16. Check the water pressure in C.H. circuit and if it’s necessary fill the pressure up to the right level.
* Depending on the size of C.H. circuit time of filling the boiler with water can be different. It is recommended to
earlier fill the C.H. installation with water.
** In home C.H. circuits the nominal operating pressure should be set on 1,2-1,6 bar.
*** Note! The boiler is factory set on operating in the radiator heating. In case of the floor heating, the boiler control
system shall be adapted to other operating parameters. This action is performed by Authorized Service Company.
Fig. 1
Fig. 2

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.2
Table of Contents
1. INTRODUCTION .......................................................................................................................................................................................................................................................................... 3
2. BOILER DESCRIPTION .................................................................................................................................................................................................................................................................. 3
2.1.
T
ECHNICAL SPECIFICATION
........................................................................................................................................................................................................................................................ 3
2.1.1. Technical features...................................................................................................................................................................................................................................................... 3
2.2.
D
ESIGN AND TECHNICAL SPECIFICATIONS OF THE BOILER
.................................................................................................................................................................................................................... 3
2.2.1. Main units of the boiler.............................................................................................................................................................................................................................................. 3
2.2.2. Technical data ........................................................................................................................................................................................................................................................... 5
2.3.
P
ROTECTION EQUIPMENT
.......................................................................................................................................................................................................................................................... 6
2.4.
O
PERATION DESCRIPTION
.......................................................................................................................................................................................................................................................... 6
2.4.1. Way of heating the water for central heating system ................................................................................................................................................................................................ 6
2.4.2. Temperature regulation dependent on e ternal temperature ................................................................................................................................................................................... 6
2.4.3. Method of D.H.W. heating in combi boilers ............................................................................................................................................................................................................... 7
2.4.4. The way of heating the water in system boiler ECOCONDENS SILER PLUS cooperating with domestic water tank. ................................................................................................... 7
2.4.5. Operation of the pump with adjustable speed. ......................................................................................................................................................................................................... 8
3. BOILER INSTALLATION ............................................................................................................................................................................................................................................................... 9
3.1.
R
EQUIREMENTS OF BOILER INSTALLATION
...................................................................................................................................................................................................................................... 9
3.1.1. The regulations on the water installation, gas and the flue gas system ..................................................................................................................................................................... 9
3.1.2. Regulations related to the room ................................................................................................................................................................................................................................ 9
3.1.3. Requirements for electrical installation .................................................................................................................................................................................................................... 9
3.2.
P
RELIMINARY CHECK ACTIVITIES
................................................................................................................................................................................................................................................ 10
3.3.
M
OUNTING THE BOILER ON THE WALL
........................................................................................................................................................................................................................................ 10
Fig. 3.3.1 Installation dimensions of boiler ECOCONDENS SILVER PLUS ............................................................................................................................................................................. 10
3.4.
C
ONNECTION TO THE GAS INSTALLATION
..................................................................................................................................................................................................................................... 10
3.5.
C
ONNECTION OF THE BOILER TO A WATER SYSTEM OF CENTRAL HEATING
............................................................................................................................................................................................. 10
Fig. 3.5.1 Boilers installation requirements ........................................................................................................................................................................................................................ 11
3.5.2 System cleaning and water treatment for the C.H. filling. ......................................................................................................................................................................................... 11
3.6.
C
ONNECTION OF THE BOILER TO A DOMESTIC HOT WATER SYSTEM
.................................................................................................................................................................................................... 12
3.7.
C
ONDENSATE OUTLET
............................................................................................................................................................................................................................................................. 12
3.8.
F
LUE GAS OUTLET
.................................................................................................................................................................................................................................................................. 12
3.8.1. The ways of mounting adapters (elbows connection) to the boiler type .................................................................................................................................................................. 12
3.8.2. Horizontal outlet of air- flue system through the wall or on the roof ....................................................................................................................................................................... 13
3.8.3 Vertical outlet of air- flue gas system through the roof ............................................................................................................................................................................................ 13
3.8.4 Connecting to a common chimney duct system, consisting of a duct for air inlet and flue gas outlet duct ............................................................................................................... 13
3.8.5. Flue gas air outlet and air inlet by two separate tubes ........................................................................................................................................................................................... 14
3.8.6 Reduction of the ma imum length of the air-flue system by changing the flow direction ......................................................................................................................................... 15
3.9.
C
ONNECTION OF ADDITIONAL DEVICES
........................................................................................................................................................................................................................................ 15
Fig.3.9.1 Electrical terminals of controller - a back view .................................................................................................................................................................................................... 15
3.9.2 Connection of a room temperature regulator ........................................................................................................................................................................................................... 15
3.10.
C
ONNECTING THE OUTSIDE TEMPERATURE SENSOR
...................................................................................................................................................................................................................... 15
4. BOILER ADJUSTMENT AND PRELIMINARY SETTING ................................................................................................................................................................................................................ 15
4.1.
I
NTRODUCTORY REMARKS
....................................................................................................................................................................................................................................................... 15
4.2.
A
DJUSTING THE BOILER TO COMBUST ANOTHER TYPE OF GAS
........................................................................................................................................................................................................... 15
4.3.
B
OILER ADJUSTMENT
............................................................................................................................................................................................................................................................. 16
4.3.1. Gas flow regulation in the boiler (without using the flue gas analyzer) ................................................................................................................................................................... 16
4.3.2. Adjustment of the boiler with a gas analyzer .......................................................................................................................................................................................................... 16
4.4.
F
AN CHARACTERISTICS
............................................................................................................................................................................................................................................................ 17
F
IG
.4.4.1.
C
HARACTERISTICS OF THE FAN
-
TYPE
NG40
M
...................................................................................................................................................................................................................... 17
5. STARTUP AND OPERATION OF THE BOILER .............................................................................................................................................................................................................................. 17
5.1.
I
NITIAL STARTUP OF THE BOILER
................................................................................................................................................................................................................................................ 17
5.2.
I
NCLUSION AND OPERATION
..................................................................................................................................................................................................................................................... 17
5.3.
O
PERATING MODES OF THE CONTROLLER
.................................................................................................................................................................................................................................... 18
5.4.
S
IGNALIZATION OF OPERATION STATES AND DIAGNOSIS
................................................................................................................................................................................................................... 18
5.4.1. Signalisation of the start of heating in CH or DHW system ...................................................................................................................................................................................... 19
5.4.2. Signalisation of anti-freezing function operation in STAND BY mode ....................................................................................................................................................................... 19
5.4.3. Displaying the water pressure in CH installation ...................................................................................................................................................................................................... 19
5.4.4. Displaying parameters ............................................................................................................................................................................................................................................. 19
5.4.5 DHW heating blockade indicator for one-function boilers. ....................................................................................................................................................................................... 19
5.4.6 Support the venting of heating system ..................................................................................................................................................................................................................... 19
5.5.
C
HANGING THE
CH
OR
DHW
TEMPERATURE SETTINGS
.................................................................................................................................................................................................................. 19
5.5.1. Temperature settings in CH circuit ........................................................................................................................................................................................................................... 19
5.5.2 Temperature settings in DHW circuit ........................................................................................................................................................................................................................ 20
5.6.
C
ONTROLLER CONFIGURATION
–
BOILER PARAMETERS SETTING
........................................................................................................................................................................................................ 20
5.6.1. Programming Mode entering .................................................................................................................................................................................................................................. 21
5.7.
P
AUSE IN BOILER OPERATION
................................................................................................................................................................................................................................................... 21
5.8.
D
IAGNOSIS
.......................................................................................................................................................................................................................................................................... 21
5.8.1. Signalisation of error codes during the emergency procedures implementation ...................................................................................................................................................... 21
5.8.2. Signalisation of error codes in emergency situations without locking ...................................................................................................................................................................... 21
5.8.3. Signalisation of emergency switching off with locking ............................................................................................................................................................................................. 21
5.8.4. Error list ................................................................................................................................................................................................................................................................... 22
6. MAINTENANCE, INSPECTIONS, CHEC ING OF THE OPERATION ............................................................................................................................................................................................... 23
6.1.I
NSPECTON AND MAINTENANCE
................................................................................................................................................................................................................................................. 23
6.1.1. Maintenance of the combustion chamber, burner, electrode. ................................................................................................................................................................................. 23
6.1.2. Cleaning the condensate siphon .............................................................................................................................................................................................................................. 23
6.1.3. The pressure in the e pansion vessel ....................................................................................................................................................................................................................... 23
6.1.4. Maintenance of the flue water-water heat e changer, item.21 ............................................................................................................................................................................... 24
6.1.5. Checking the temperature sensors ........................................................................................................................................................................................................................... 24
6.1.6. Checking the water pump operation ........................................................................................................................................................................................................................ 24
6.1.7. Ionisation current measurement .............................................................................................................................................................................................................................. 24
6.2.
R
EPLACING A DAMAGED CONTROL BOARD IN THE CONTROL PANEL
.................................................................................................................................................................................................... 25
6.3.
T
HE MAINTENANCE OPERATIONS TO BE PERFORMED BY THE USER
...................................................................................................................................................................................................... 26
6.4.
R
ANGE OF TECHNICAL MAINTENANCE PERFORMED BY SERVICE COMPANY
............................................................................................................................................................................................ 26
7. BOILER EQUIPMENT ................................................................................................................................................................................................................................................................. 26

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.3
1. INTRODUCTION
Combi condensing boiler is designed for supplying central heating systems and for heating domestic water.
In this manual there are described below mentioned types of ECOCONDENS SILVER PLUS - combi boilers designed for supplying a
central heating systems and for heating domestic water in instantaneous water-water heat exchanger:
type ECOCONDENS SILVER PLUS -20
type ECOCONDENS SILVER PLUS -25
type ECOCONDENS SILVER PLUS -35
and ECOCONDENS SILVER PLUS – system boilers designed for supplying a central heating system and heating domestic water in
separately connected water tank.
Adaptation of the following types of boilers to work with the tank needs to be made by AUTHORISED SERVICE COMPANY.
type ECOCONDENS SILVER PLUS -20
type ECOCONDENS SILVER PLUS -25
type ECOCONDENS SILVER PLUS -35
ECOCONDENS SILVER PLUS boilers take the air for combustion process from outside the room (in which combustion circuit is
sealed) with respect to the residential area of the building in which it is installed - type of installation: C
63
, or take the air for combustion
process from the room that meets appropriate conditions (required by law) - type of installation: B
23
.
Further information regarding the type – according section 3.8 and PN-EN 15502-2-1:2013-04
2.
BOILER DESCRIPTION
2.1.
Technical specification
2.1.1.
T
echnic
al f
eatures
2.2.
Design and technical specifications of the boiler
2.2.1.
Main units of the boiler
•
Electronic fluent flame modulation for central heating
system and domestic hot water;
•Electronic ignition with ionization flame control;
•Adjustable boiler power;
•Regulation of heating water and domestic water
temp.;
•Soft ignition function;
•Inlet gas pressure stabilisation;
•Adopted to cooperate with closed circuit in CH
system;
Descriptions for fig.
2.2.1.1 ÷ 2.2.1.
3
5. Fan,
18. NTC sensor of heating water -supply
7. Pump, 19. Heating water pressure transducer,
8. Gas unit 20. Air -vent
10. Flame control/ Ignition
electrode,
21. Plate water-water heat exchanger,
22. Filling valve of installation
11. Burner, 25. Safety valve - 3 bar,
12. 3-way valve, 26. Domestic water flow sensor
13. Flue gas-water heat exchanger 27. NTC sensor of domestic water temperature
15. Temperature limiter as
a
protection against exceeding the
upper limit water temperature
28. NTC temperature sensor of heating water -
return (only in boilers with PWM pumps)
29. Siphon
16. Thermal fuse of flue gas, 30. Mixing unit
17. Expansion vessel 33. Drain valve
30
25
26
7
19
28
11
16
33 22 8
21
27
29
15
5
18
13
17
20
18
10
Fig.2.2.1.1. Location of elements in combi boiler ECOCONDENS SILVER PLUS

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.4
33
29
8
a
5
20
15
18
17
13
7
25
19
28
30
11
16
10
Fig.2.2.1.2. Location of elements in system boiler: ECOCONDENS SILVER PLUS
Only Fig. 2.2.1.
3
.
1.
Swich of boiler function selection
2. Temperature selector (c.h. or d.h.w.)
3
. Heating water, domestic water and static pressure temperature display with error
codes diagnostic
4. Control panel
K1. ON/OFF, reset
Fig.2.2.1.3. Scheme of boiler operation

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.5
2.2.2. Technical data
Parameter Unit SYSTEM BOILER: ECOCONDENS SILVER PLUS COMBI BOILER: ECOCONDENS SILVER PLUS
-20 -25 -35 -20 -25 -35
Size
E n e r g e t i c p a r a m e t e r s
C e n t r a l h e a t i n g c i r c u i t
Boiler thermal power at 80/60
o
C (modulated) kW 2.7 ÷ 20.0 3.9 ÷ 24.0 4.1 ÷ 34.7 2.7 ÷ 20.0 3.9 ÷ 24.0 4.1 ÷ 34.7
Boiler thermal power at 50/30
o
C (modulated) kW 3.0 ÷ 22.0 4.3 ÷ 26.5 4.5 ÷38.2 3.0 ÷ 22.0 4.3 ÷ 26.5 4.5 ÷ 38.2
Heat load kW 2.8 ÷ 20.4 4.0 ÷ 24.6 4.2 ÷ 35.6 2.8 ÷ 20.4 4.0 ÷ 24.6 4.2 ÷ 35.6
The efficiency of the boiler at nominal load
and average boiler water temp. 70 oC
% 97.6 98.0 98.0 97.6 98.0 98.0
The efficiency of the boiler at partial load and
return water temperature 30 oC
% 107.9 108.7 109.0 107.9 108.7 109.0
Modulation range % 13-100 16-100 12-100 13-100 16-100 12-100
Seasonal space heating energy
efficiency
ɳ
s
% 91 92 92 91 92 92
Seasonal space heating energy efficiency
class A
Useful heat output :
- at rated heat output
P4
- at 30% of rated heat output
P
1
kW
kW
20.0
6.0
24.0
7.2
34.7
10.4
20.0
6.0
24.0
7.2
34.7
10.4
Useful efficiency :
-
ɳ
4
-
ɳ
1
%
88.0
97.0
87.9
96.9
87.8
96.5
88.0
97.0
87.9
96.9
87.8
96.5
Nominal kinetic pressure in front of the boiler
for gas:
2E-G20, 2H-G20
3B/P-G30, 3P-G31
Pa (mbar)
2000 (20); 2500 (25); 2000 (20); 1300 (13)
2800 ÷ 3000 (28 ÷ 30); 3000 (30); 3700 (37); 5000 (50)
Maximum water pressure MPa (bar) 0,3 (3)
Max temperature (central heating)
o
C 95
Standard adjustable temperature
Reduced adjustable temperature °C 40 ÷ 80
25 ÷ 55
Lift of the pump at flow 0 kPa (bar) 70 (0,7) 70 (0,7)
D o m e s t i c h o t w a t e r c i r c u i t
Nominal heat output of the boiler
at temp. 80/60oC kW ----- 2.7 ÷ 25 3.9 ÷ 30.0 4.1 ÷ 40.0
Nominal heat load kW ----- 2.8 ÷ 25.6 4.0 ÷ 30.7 4.2 ÷ 41.0
The efficiency of the boiler at nominal load
and average boiler water temperature of
70°C % ----- 97.6 98.0 98.0
Water heating energy efficiency class A A A
Load profile L XL XL
Water pressure MPa (bar) ----- 0.01 (0.1) ÷0.6 (6)
Min water flow l/min ----- 2.0
Max water flow (flow limiter) dm
3
/min ----- ----- ----- ----
Range of water temperature regulation °C 30 - 60
Flow of domestic water for ∆t=30K dm
3
/min 12 14 19
E n v i r o n m e n t a l p r o t e c t i o n
Emissions of nitrogen oxides mg/kWh 21 24 29 21 24 29
Emission of NO
x
(natural gas) class 5
The pH of the condensate natural gas - 5
Sound power level LWA dB 48 48 48 48 48 48
H y d r a u l i c p a r a m e t e r s
Expansion vessel capacity dm
3
6
Water pressure in expansion vessel MPa (bar) 0.08
±
0.02
(0.8
±
0.2
)
E l e c t r i c p a r a m e t e r s
Type and supply voltage V ~ 230 ±10%/ 50Hz
Degree of protection IP44
Power consumption W 110
Standby mode power consumption P
SB
kW 0.005
Electricity consumption :
- at full load elmax
- at part load el
min
kW
kW
0.05
0.02
0.05
0.02
0.05
0.02
0.05
0.02
0.05
0.02
0.05
0.02
Maximum nominal current value of output
terminals A 2
Controller classification according to PN EN
298 F-M-C-L-X-K
Type of flame sensor ionization
T h e p a r a m e t e r s o f f l u e g a s
Fan characteristics section 4.4 of this manual
Flue gas mass flow at full load kg/h 51.4 72.3 90.4 51.4 72.3 90.4
Flue gas mass flow at partial load kg/h 5.4 9.5 9.6 5.4 9.5 9.6
The minimum flue gas temperature at
minimum thermal power °C 44 34.3 34.3 44 34.3 34.3
The maximum flue gas temperature at
maximum thermal power °C 61 66.9 66.7 61 66.9 66.7
T i m e p a r a m e t e r s
Time of central heating pump rundown s 180
Time preventing the anti-cyclical startup of
the boiler (Anti-cycling time) minutes 3-60
Time of domestic hot water pump rundown s 20-180
Protection against pump and valve blocking h /s the pump turns on for 180 seconds every 24 hours
the pump and three way valve turns on for 15 seconds every 48 hours

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.6
A s s e m b l y d i m e n s i o n s
Connection to the chimney duct
(section 3.8. and table 7.1.) mm Coaxial Φ80/Φ125, Coaxial Φ60/Φ100 or 2 separate Φ80 x Φ80
Connection of heating water (CH) and gas inch G3/4
Connection of DHW inch G3/4 G1/2
Dimensions mm 785x400x 334 785x400x 334 785x400x 334 785x400x 334 785x400x 334 785x400x 334
Boiler weight kg 31.5 32.5 37.5 33.5 34.5 39.5
The manufacturer reserves the right to make changes in the construction of the boiler, which are not mentioned herein and have no influence on the technical and functional
characteristics of the product.
2.3. Protection equipment
•Protection against gas outflow
•Protection against explosive gas switching on
•Protection against exceeding the max temperature in the heating water system
•Protection against exceeding the upper limit of heating water temperature
•Protection against water pressure increase (1-st degree)- electronic
•Protection against water pressure increase (2-nd degree)- mechanical
•Protection against drop of water pressure
•Protection against water overheating
•Anti-freezing protection of the boiler
•Protection against the pump blockade
•Monitoring of the correct operation of the fan. Fan failure is detected if the current fan speed is different from that
expected by the driver of the boiler.
•Protection against exceeding the upper limit temperature of flue gas (115°C).
Errors which do not require manual reset will cause return of the boiler to the normal operation after automatic disappearance of failure
section 5.8 - boiler diagnostics.
NOTICE!
In case of noticing repeated emergency boiler shut-down by any of the protection it is necessary to contact an Authorized
Service Company in order to check the reason of boiler switching off and to repair it.
It is forbidden to
make any
unauthorized
modifications in the protection system.
2.4. Operation description
2
.4.1. Way of heating the water for central heating system
The boiler switches on if the heating water temperature drops about 5 degrees below the set temperature - as described in section 5.5.1 and the room
thermostat gives the signal to heat. Then the following conditions occur simultaneously:
•power supply of the three-way valve (item 12 towards the central heating installation),
•pump supply (item 7),
•fan supply (item 5),
•the sequence of ignition,
•then the driver starts the fan speed regulation so as to obtain the desired temperature of heating water
The boiler switches off when the room temperature control unit is signalizing desired temperature in the room or when heating water temperature is
higher than desired (by value of hysteresis see P20). In this case the “L3” is shown on the display. After switching off the burner, pump runs for about
180 s, and fan for 15 s.
Restart of the boiler will be done automatically under the following conditions simultaneously:
•heating water temperature is lower by 5°C than the set temperature,
•room temperature control unit provides the signal "HEAT",
•180 seconds have passed. waiting time determined by parameter P25 have passed (default 3 minutes) if L3 was displayed.
The list of driver parameters according to Table 5.6.
2.4.2. Temperature regulation dependent on external temperature
If an external temperature sensor has been connected the controller detects it automatically and goes to the weather function mode.
Controller adjusts the heating water temperature making it dependent on outside temperature and coefficient of the slope of the heating curve Kt” and
parameter P22 diagram shown on the Fig. 2.4.2.1 and 2.4.2.2
Changing the value of the coefficient Kt is described in Section 5.5.1.1.
Fig.2.4.2.1 Diagram of the heating curve (standard heating)
Fig.2.4.2.2 Diagram of the heating curve (floor heating)
Notice:
1) for value Tout ≥25°C and P22=0 designed temp. Tc.h. is always equa l to Tmin.
2) at max. coefficient Kt and P22=0, Tmax is reached when Tout ≤10°C.
3) Tmax will not exceed 80°C for standard heating a nd 55°C for floor heating regardless of the value P 22
Temperatura zewnętrzna
Temperatura c.o.
-40
50 C
0
Kt= 0
Tm in 40 C
0
60 C
0
Kt= 1
-30 -20 -10
Kt= 1, P22= 10
Tmax 85 C
70 C
0
80 C
0
Kt= 2
0
Kt= 3 K t=4
+200 +10 +25
Kt= 8Kt= 6 K t=10
T em p e ra tu ra z ew n ętrzna
Temperatura c.o.
- 4 0
3 0 C
0
K t = 0
0
3 5 C
0
K t= 1
- 3 0 - 2 0 - 1 0
K t = 1 , P 2 2 = 10
4 0 C
0
4 5 C
0
0
0
5 0 C K t = 2 K t = 3 K t = 4
+ 2 00 + 1 0 + 2 5
K t= 8
K t= 6 K t = 1 0
T m in 2 5 C
T m ax 5 5 C
Temperatura zewnętrzna
Temperatura c.o.
-40
50 C
0
Kt= 0
Tm in 40 C
0
60 C
0
Kt= 1
-30 -20 -10
Kt= 1, P22= 10
Tmax 85 C
70 C
0
80 C
0
Kt= 2
0
Kt= 3 K t=4
+200 +10 +25
Kt= 8Kt= 6 K t=10

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.7
4) In case, when weather regulator works in autonomic mode (parameter P26=2), RT input is treated as an input for choice of time of day: DAY (contact
open) NIGHT (contact closed). During NIGHT time, calculated temp. T
CH
is reduced by the P28 parameter value. Boiler starts heating CH water if the
outdoor temperature is lower than P27 parameter value. Boiler stops heating CH water if the outdoor temperature is higher than P27 parameter value at
least 3 hours.
5) If P26=0, then weather regulator doesn’t work, it is only outdoor temperature measurement.
2.4.3. Method of D.H.W. heating in combi boilers
Combi boiler heats the water in a instantaneous way. Water temperature is set using the buttons +/- (p.5.5.2) in the range 30°C to 60°C. The water
temperature at the outlet depends on water temperature at the inlet.
Water flow shall be determined by draw-off valve in the outlet.
In this mode the water heating demand occurs when the flow sensor turns on at the value above 2.0 l /min (ends at a flow < 1.5 l / min.)
Then follows the sequence:
•switching the power of the 3-way valve (item 12) in direction of the water-water heat exchanger supply for the pump (item 7),
•after flame detection and the end of startup sequence, signal from the NTC sensor (DHW) adjusts the fan speed to reach the desired temperature of
domestic hot water item 27
Central heating hot water flows through the water-water heat exchanger segments and heats the water. The heated water is directed to the point of its
collection.
NOTICE: In the case of a lower fan rotation range caused by low water consumption, there is a water temperature increase. Turning off the gas flow to
the main burner will come when the DHW temperature exceeds 65°C.
50
30
40
35
45
15
25
20
10
2 310
0
5
875 64
±10%
60
55
t [°C]
Q [l/min.]
181312109 11 171514 16 22212019 23
t min.
t max
Domestic water temperature on the inlet t=15°C
Domestic water temperature on the inlet t=5°C
Fig
. 2.4.3.1. Diagram of domestic water temperature at the boiler
outlet at thermal Power of 25kW depending on the water flow rate.
11
50
15
0 1
5
0
10
20
30
25
35
40
45
432 65 97 8 10
t [°C]
55
60
±10%
Q [l/min.]
t min.
1612 13 14 15 1817 19 20 252321 22 24 26 27 28
t max
Domestic water temperature onthe inlet t=15°C
Domestic water temperature onthe inlet t=5°C
Fig. 2.4.3.2. Diagram of domestic water temperature at the boiler
outlet at thermal power of 30kW depending on the water flow rate.
9
50
15
0
10
5
25
30
20
45
40
35
20 1 3 4 65 7 8
60
55
t [°C]
±10%
t min.
t max
28141110 12 13 1615 1817 232119 20 22 2524 26 27 373029 3231 353433 36 Q[l/min.]
3938
Domestic water temperature on the inlet t=15°C
Domestic water temperature on the inlet t=5°C
Fig. 2.4.3.3. Diagram of domestic water temperature at the boiler outlet at thermal power of 40kW depending on the water flow rate.
2.4.4. The way of heating the water in system boiler ECOCONDENS SILER PLUS cooperating with domestic water tank.
The boiler may cooperate with domestic water tank type Termet-120, Termet-140 and ZWU200/N. These water tanks are offered by
TERMET company. Adjustment and display of domestic water temperature are done by the control panel of the boiler. Boilers are factory
designed for cooperation with domestic hot water tanks.
The process of heating the domestic water:
When the water temperature sensor detects the temperature lower by 5°C of the set value
(look p.5.5.2)
then the process of pumping the
water to the central heating system will be stopped. Heating the domestic water with the boiler cooperation with the tank of domestic
hot water is as follows:
•water temperature sensor detects the temperature lower by 5°C of the set value (for example as a result of unscrewing the tap);
•boiler controller switches the three-way valve to pump water to a short circuit, while giving a signal to the spark generator and gas
valve item 8;
•heating water with temperature described by parameter P21 (default 75°C) flows through the coil of tan k (short circuit);
•after exceeding by 1°C set water temperature in the tank the boiler controller switches the 3-way valve for long circuit and after
meeting below mentioned conditions the heating water is pumped into the central heating system:
- heating water temperature is lower by 5°C of the set temperature
- room temperature regulator gives a signal “HEAT”.
The temperature of hot water at the point of consumption may be different from the set value, and therefore it is advisable to
install a mixing valve for domestic hot water systems.
Water heating in the storage tank is active when the electrical bridge is mounted on the TZ input
(Fig.3.9.1.)and when set temperature value is higher or equal to the minimum value. After setting the value lower than the

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.8
minimum, the tank is switched off. This does not apply for frost protection function.
NOTE: To eradicate legionella bacteria in the storage tank, the boiler is turned on every 168h to work with the tank and
heats water to 65°C.
If legionella function does not work in automatic mode, the user at any time can manually initiate a single cycle of tank
heating to 65°C.
2.4.4.1 Manual initiation of disposable tank overheating - Anti-legionella function in manual mode
* (applies to the boilers with tanks):
When the boiler is operating in SUMMER mode:
Press the button twice. After first pressing the button, the display shows (ready to modify) option of CH setting. Next pressing
displays the symbols characteristic of Legionella Function: a flashing key symbol, right field dimmed, in the left field you can see DHW
temperature and the symbol MAX placed above it.
When the boiler is operating in WINTER mode:
Please press the button three times. After first pressing the button, the display shows (ready to modify) option of CH setting. Next
(second) pressing displays the symbols characteristic of Service Function. Next pressing displays the symbols characteristic of
Legionella Function: a flashing key symbol, right field dimmed, in the left field you can see DHW temperature and the symbol MAX
placed above it.
In both modes of operation:
To activate the Legionella Function hold the button ”+” for 2 seconds. After activation Legionella Function the symbol "key" will light up
with solid light. To activate the Legionella you have about 3 seconds. After this time, or when you press the reset button the system
goes to the normal mode characteristic for the selected operation mode.
During the implementation of Legionella Function, the temperature field is dimmed.
Completion of Legionella function is performed automatically or by pressing the reset button or the operation mode change.
2.4.5. Operation of the pump with adjustable speed.
In the boilers equipped with a pump with variable speed (PWM) during the work in DHW mode
- in two-function boilers the pump has maximum speed
- in one-function boilers the speed of the pump is determined by parameter P19
While heating water in C.H. system the controller regulates the pump according to:
For conventional PWM pump operation (parameter P 15 = 0):
PWM Pump (activation by parameter P12) works with a modulated speed in C.H. system activating by signal from RT (room
temperature regulator). The rotational speed is adjusted in such a way that in cooperation with the modulator to achieve the value
of ∆T (defined by parameter P13) between outgoing and return temperature of central heating system. There is maintained a priority to
achieve and hold the set of temperature in central heating system. Minimum allowable rotation speed of the pump is determined by
parameter P14. The maximum allowable rotation speed of the pump is determined by parameter P18
ECO mode (parameter P15 = 1):
PWM Pump (activation by parameter P12) works with a modulated speed in C.H. system activating by signal from RT (room
temperature regulator). The rotational speed is adjusted in such a way that in cooperation with a modulator achieved value ∆T between
outgoing and return temperatures of central heating system calculated on the basis of a preset ratio ECO (p.2.4.5.1). ECO factor is
adjusted on the user interface in the range of 0.1 to 0.9. The default (optimal in most cases) value is 0.5. Selection of lower value
results in lower gas consumption with less heat energy being placed into the room (simplified we decide what part of the radiator has to
be warmed up). The user obtains the possibility of such a regulation of device to get the thermal comfort at minimum cost (less gas
consumption, lower power consumption). The value 0,5 of the coefficient of ECO is the maximum value at which the control regardless
of the temperature setting C.H. water seeks to meet the conditions of condensation (C.H. return temperature <= 55 °C). It is
recommended to work the system at the ECO ratio in the range of 0.1 to 0.5. If increasing the C.H. setting cannot obtain adequate
thermal comfort should gradually increase the value of the ECO. ECO factor equal to 0.9 practically corresponds to the traditional work
of the pump without speed control.
Irrespective of the mode of operation:
Preserved is a priority to achieve and maintain the set temperature C.H. water. Minimum allowable rotation speed of the pump is
determined by parameter P14. The maximum allowable rotation speed of the pump is determined by parameter P18
NOTE:
If the temperature sensor of return central heating water is damaged or is not connected, the pump works with a constant speed.

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.9
2.4.5.1 The expected value of T depending on the setting C.H. water and the coefficient of ECO.
The expected value of T depending on the setting C.H. water and the coefficient of ECO.
Standard heating (P8 = 0): Setting WG
Eco 40°C 45°C 50°C 55°C 60°C 65°C 70°C 75°C 80°C
0,1
24 30 35 35 35 35 35 38 42
0,2
21 26 30 30 30 30 30 33 37
0,3
18 22 26 26 26 26 26 28 31
0,4 15 19 22 22 22 22 22 24 26
0,5
12 15 17 17 17 17 17 19 21
0,6
9 11 13 13 13 13 13 14 15
0,7
6 7 8 8 8 8 8 9 10
0,8
3 3 4 4 4 4 4 4 5
0,9
0 0 0 0 0 0 0 0 0
3. BOILER INSTALLATION
The boiler must be installed by an authorized service company accordingly with local regulations. After the boiler installation check the
tightness of all connections of gas, water and flue gas system. Service company is responsible for the proper installation of the boiler.
Installation of the boiler must be made so as not to cause any tension of the installation that may cause increased volume of work.
After exploitation of the boiler, disassembled product transfer to a specialized unit for utilization.
3.1. Requirements of boiler installation
3.1.1. The regulations on the water installation, gas and the flue gas system
Water, gas and flue gas systems must meet local regulations as well as use of the gas, ventilation and flue gas installation.
Using of gas appliances, flues and ventilation by the user should be consistent with local requirements relating to the technical
conditions of use the residential buildings.
Before installing the boiler the consent from the District Department of Gas, Chimney Sweep Company and Building Administration
must be obtained.
Gas appliances supplied with liquefied gas must not be installed in room with a floor below ground level.
If you use liquefied gas 3B/P it is recommended that the temperature in a room where a gas cylinder will be operated is not
less than 15°C.
3.1.2. Regulations related to the room
Requirements for premises where gas appliances are installed shall be in accordance with local regulations. The room where the boiler
is to be installed should ensure the air supply and venting system necessary for gas combustion in accordance with local regulations.
The location of ventilation should not cause the water freezing. The temperature in the room where the boiler is installed should be
higher than 6°C. The room should be protected against freezing, free from dust and aggressive
gases.
It is forbidden to install the device in a laundry rooms, drying rooms and in
varnish, cleaners, solvents and sprays storages.
Boiler with a thermal capacity above 30 kW should be installed in a technical
room.
Place of installing a boiler in a room equipped with bath or shower with a pool
and the way of connecting it to the electrical system- in accordance with the
requirements of HD 60364-7-701. The device covered by this instruction has a
degree of electrical protection provided by the housing IP44. Boiler equipped
with power cord with a plug can be installed in zone 2 or further - must not be
installed in zone 1.
In zone 1 can be installed only if it is permanently connected to a power source
in accordance with HD 60364-7-701.
Fig. 3.1.2.1. The zones dimensions in areas containing a bath or shower with a pool
3.1.3. Requirements for electrical installation
The boiler has been designed for operation with single-phase alternating current with rated voltage of 230 V/50 Hz.
The boiler has been designed as a “class I“ device and must be connected to an electrical outlet with ground terminal in accordance
with PN- IEC 60364-4-41.
Pay attention on correctly connecting the power cord. If power cord is connected incorrectly:
- the boiler enters in failure state
- on display occurs E01 (item 5.8.4)
In this case change cords “L” and “N” in the socket. When the correct connection is detected, the boiler unlocks automatically.
The boiler ECOCONDENS SILVER PLUS has a degree of electrical protection provided by the housing - IP44.
In case the boiler is permanently connected to the power supply the electrical installation should be equipped with means of
disconnecting the boiler from the power source, it should be execute by junction box. The junction box must be equipped with protection
degree appropriate for the defined assembly zone.
In order to connect the boiler to the junction box, it is recommended to:
- cutthe power cord to a suitable length for connection to the box
- pull off cable insulation
- connect wire ends using soldering or tighten cable-end sleeve with appropriate diameter
Floor heating (P8 = 1): Setting WG
Eco
35°C
40°C
45°C
50°C
55°C
0,1 16 24 30 35 35
0,2
14 21 26 30 30
0,3
12 18 22 26 26
0,4
10 15 19 22 22
0,5 8 12 15 17 17
0,6
6 9 11 13 13
0,7
4 6 7 8 8
0,8
2 3 3 4 4
0,9 0 0 0 0 0
The main socket from which boiler is powered must complies with PN-IEC-60364-6-61:2000
225cm
60 cm
225cm
60 cm
Zone 1 Zone 2
Zone 1
Zone 0
Zone 1 Zone 2
Zone 0
Side view. Bath Side view. Shower

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.10
This prepared cables connectaccording to the following diagram.
Fig 3.1.3.1 Wire colors: L – brown; N – blue; PE – yellow-green
3.2. Preliminary check activities
Before starting the installation work, check:
•whether the boiler is factory designed for the type of gas supplied from the gas system. The type of gas which the boiler is
adjusted to is specified on the rating plate on the cover of the boiler;
•whether the water system and radiators have been properly rinsed with water in order to remove rust, fillings scale, sand and other
dusts that could disturb the proper operation of the boiler (for example increase the water flow resistance in central heating
system) or to pollute the heat exchanger,
•whether the mains voltage has a value of 230V and that the socket has an efficient safety contact (complies with PN-IEC-60 364-6-
61: 2000).
3.3. Mounting the boiler on the wall
Hang the boiler on hooks fastened durably in the wall using a beam placed in upper part of the boiler. The boiler shall be so located as
to permit the eventual repair without any need to dismantling from the installation.
67
60
53
ca100
60
53
334
56
A
G1/2
G3/4
A
A
29
151
712
400
361
ca100
ca2000mm
140
200
Fig. 3.3.1 Installation dimensions of boiler ECOCONDENS SILVER PLUS
3.4. Connection to the gas installation
Connect a gas supply pipe directly to the connector of the boiler gas unit using of connector subassembly no 0696.00.00.00 (in
boiler equipment).
It is necessary to install a gas filter on the gas supply pipe. This filter is not included in the standard boiler equipment.
The gas filter is necessary for a proper operation of a gas unit and a burner.
Install a cut-off valve on the gas pipe in an accessible place.
3.5. Connection of the boiler to a water system of central heating
•Power supply and return connectors of the central heating boiler should be screwed to the installation. Location of the connectors
Figure 3.3.1.
Wire of electric system
Power wire the
device
Junction box

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.11
•Install a water filter on a water return from central heating system (in front of the connection with the pump). The filter is
not included in standard boiler equipment.
•The central heating system should be thoroughly rinsed out before the boiler is connected.
•In the central heating system it is permitted to use as a heat carrier any antifreeze fluids which can be used in central heating
systems.
•The cut-off valves needs to be installed between the boiler and central heating system so that the boiler could be dismounted
without draining the system.
•Do not install any thermostatic valves on radiators in the room where the thermostat is installed. The temperature controller takes
the control over the function of temperature and it cooperates with the boiler.
•On at least one of radiators of the central heating system there shouldn`t be installed a thermostatic valve.
•It is recommended to lead out a water from a safety valve 0,3 MPa (3 bar) (item 25) to a floor drain by a tube or hose otherwise
during the safety valve activation there is a risk of flooding a room what is excluded of producer’s liability.
Selection of expansion vessel
Boilers ECOCONDENS SILVER PLUS are adjusted to be connected to a central heating system with the maximum capacity of 105
liters. The assembly to installation with larger capacity is acceptable only after applying an additional expansion vessel. A proper
expansion vessel should be selected by the designer of central heating system.
Installation of expansion vessel should be made by an installation contractor in accordance with applicable regulations.
NOTICE! : Before installing the boiler thoroughly flush the central heating system to free it from any solid impurities.
It is recommended that after first start up of the boiler and heating up of the installation drain the water from the system to remove
residues of pastes metallurgical and precautionary measures of heaters. These activities would benefit for the operation of the device,
its parameters and components life.
After boiler installation:
•Fill the heating system with water by filling valve item 22 Fig 2.2.1.1. for combi boiler. For system boiler install filling valve from
the installation. Pressure in cold installation should amount 1,0 to 1,5 bar (indicated by manometer).
•Vent the installation of central heating and boiler;
•Check the tightness of boiler connections in central heating system.
Fromthewatersystem
FloordrainFromthewatersystem
Floordrain
Fluegasoutlet
Gasfilter
Waterfilter
Gas
Exhaustventilation
Exhaustventilation
Fluegasoutlet
Gasfilter
Gas
Waterfilter
Fig. 3.5.1 Boilers installation requirements
3.5.2 System cleaning and water treatment for the C.H. filling.
Every component of C.H. system is threatened by limestone deposits, corrosion and other dangerous processes. Boiler is the most
expensive part of C.H. system and it is necessary to protect its components like heat exchanger and other parts against harmful
processes. Correct C.H. circuit preparation for using relies on making two operations: cleaning the CH system and treating the water
that fills the system.
System cleaning
In new installation it is possible to find some remains of industrial process jak soldering and welding remains, flux, oil and grease
residue among others. Older installations usually have products of corrosion in them. It necessary to clean up the systems with a water
to remove the remains before boiler is mounted. Afterwards, system should be cleaned with appropriate chemicals. For example
Cleaner F3 from Fernox in new installations. For old and contaminated systems it is best to use Cleaner F5). Afer that it is necessary to
rinse the installation with water.
Water treatment to fill the system
For filling the system, it is recommended to use water with parameters: pH 6,5- 8,5, hardness < 10 °n (~ 18°F). Do not use
demineralised or destilled water. To ensure protection against rocks despositing, corrosion, it is recommended to use a special
inhibitor, for example Fernox Protector F1. Heat transfer fluid HP-5 or antifreeze liquid can also be used, for example Fernox Alphi 11.
If the water hardness is very high, the HP-5 effectively reduces the risk of heat exchanger calcification.

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.12
Low-temperature circuits
In the low-temperature area, it is recommended to treat the water by using heat transfer fluid HP-5 or Fernox AF10 biocide.
Filtration technique
Additionally, in order to ensure the quality of operation heating system, it is recommended to mount a modern filters, which works on
the principle of the magnetic and cyclone effect, for example Fernox TF1 filter.
Notice:
- method and amount of use specific products for system cleaning and water treatment should be in accordance to the product
manufacturer's instruction.
- above steps should be made by the autorized installer or service technician.
3.6. Connection of the boiler to a domestic hot water system
It is recommended to install cut-off valves on a domestic hot water system what will enable easier maintenance and service.
It is recommended to install a water filter on the connection with the domestic water supply. This filter is not included
in the standard boiler equipment.
3.7. Condensate outlet
Condensate formed during the combustion process must be drained according the following conditions:
•Installation of condensate drain must be made of corrosion-resistant material.
•Connection of draining the condensate cannot be blocked.
•To facilitate to drain the condensate through the flue gas all horizontal flue pipes must be installed with a fall of 3
o
(52mm / m).
3.8. Flue gas outlet
Condensate formed during the combustion process must be drained according the following conditions:
EcoCondens SILVER PLUS boilers could be installed as B-type appliances (where air needed for combustion is taken from the room
where boiler is installed) or as C-type appliances (where air needed for combustion is taken from outside). C-type appliances could be
divided as follows:
Depending on local regulations some types of installations might not be allowed. Always consult your local regulations before making
flue-gas system project.
Before turning on the boiler check if flue-gas system is made according to the project and air- and flue ducts lengths are shorter than
maximum lengths showed in tables 3.8... Make sure flue-gas system is tight.
After turning on the boiler check if it operates correctly. Also check combustion parameters by checking concentration of CO
2
and/or
O
2
in flue-gas.
Ways of connecting the boiler to the air-flue gas system Fig. 3.8...
To ensure proper functioning of the device use the appropriate wire size (diameter, maximum length, resistance on the knees),
depending on the combustion system used. The dimensions of the wires should be adequately compatible as given in table.
Resistance of flue gas flow on each elbow depending on the bending angle and related reduction of the maximum wire length are given
in section 3.8.6.
Each system should be installed with the windproof outlet protecting against external factors.
For condensing boilers ECOCONDENS SILVER PLUS there are provided three types of flue gas-air systems: coaxial system
∅80/∅125 and ∅60/∅100 and 2 separate 2 x ∅80. It is possible to apply air-flue gas pipe made from polypropylene or stainless steel.
The individual components of flue gas- air systems are given in table 7.1
NOTICE:
The boiler is factory adjusted for the coaxial exhaust system Ø60/100 of the maximum pipe length 3m + elbow. Settings O2 – 5%. To
use the other systems and longer pipes it is required to adjust the boiler as specified in point 4.2.
Coaxial reduction ∅60/∅100 x ∅80/∅125 shall be applied when using coaxial air-flue gas pipe ∅80/∅125. Inspection T-piece shall be
applied when using air-flue gas pipe made from stainless steel.
Condensing boilers SILVER PLUS meet the requirements to use in multi-storey air-flue gas systems LAS.
3.8.1. The ways of mounting adapters (elbows connection) to the boiler type
C
o
axial system
(air-flue gas pipe made from polypropylene)

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.13
O60/O100
max
L
~3°
orO80/O125
Adapter
or coaxial reduction O60/100xO80/125
+Coaxial elbow 90°with revision O80/125
Coaxial elbow 90°with revision O60/100
Separate system (air-flue gas pipe made from stainless steel)
3.8.2. Horizontal outlet of air- flue system through the wall or on the roof
Table 3.8.2.1
Type of boiler Coaxial system ∅60/∅100
ECOCONDENS SILVER PLUS-20 Maximum length of chimney flue L
max
=15 m
ECOCONDENS SILVER PLUS -25 Maximum length of chimney flue L
max
=17 m
ECOCONDENS SILVER PLUS -35 Maximum length of chimney flue L
max
=12 m
Coaxial system ∅80/∅125
ECOCONDENS SILVER PLUS -20 Maximum length of chimney flue L
max
=25m
ECOCONDENS SILVER PLUS -25 Maximum length of chimney flue L
max
=25m
ECOCONDENS SILVER PLUS -35 Maximum length of chimney flue L
max
=20m
L
max
60/100
80/125
or coaxial reduction O60/100 x O80/125
Coaxial elbow 90°O60/100
+ Coaxial elbow 90°O80/125
3.8.3 Vertical outlet of air- flue gas system through the roof
Table 3.8.3.1.
Type of boiler Coaxial system ∅60/∅100
ECOCONDENS SILVER PLUS -20
Maximum length of chimney flue
L
max
=15 m
ECOCONDENS SILVER PLUS -25
Maximum length of chimney flue
L
max
=17 m
ECOCONDENS SILVER PLUS -35
Maximum length of chimney flue
L
max
=12 m
Type of boiler Coaxial system ∅80/∅125
ECOCONDENS SILVER PLUS -20
Maximum length of chimney flue
L
max
=25 m
ECOCONDENS SILVER PLUS -25
Maximum length of chimney flue
L
max
=25 m
ECOCONDENS SILVER PLUS -35
Maximum length of chimney flue
L
max
=20 m
3.8.4 Connecting to a common chimney duct system, consisting of a duct for air inlet and flue gas outlet duct
Screw
see table 7.1
see table. 7.1
Gasket
ST 4,2 x 9,5
Gasket
index T9000.00.00.26
index T9000.00.54.00
index T9000.00.41.00
L=H
maxmax

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.14
Table 3.8.4.1.
2
min 140
min 140
H
1
min140
O60
xxx
210
H
O60
or appropriately O80
or appropriately O80
Dimensions
of the chimney duct
Type of boiler Coaxial system ∅60/∅100
ECOCONDENS SILVER PLUS -20
Maximum length of chimney flue
L
max
=15 m
ECOCONDENS SILVER PLUS -25
Maximum length of chimney flue
L
max
=17 m
ECOCONDENS SILVER PLUS -35
Maximum length of chimney flue
L
max
=12 m
Type of boiler Coaxial system ∅80/∅125
ECOCONDENS SILVER PLUS -20
Maximum length of chimney flue
L
max
=25 m
ECOCONDENS SILVER PLUS -25
Maximum length of chimney flue
L
max
=25 m
ECOCONDENS SILVER PLUS -35
Maximum length of chimney flue
L
max
=20 m
3.8.5. Flue gas air outlet and air inlet by two separate tubes
To apply the steel two-pipe system should:
•Unscrew the top cover of the combustion chamber at point of connection of the air supply system to the boiler
•Retain a gasket existing under the cover
•In place of the removed cover screw the adapter (index T9000.00.54.00) sealing the connection with a gasket,
•In place of flue gas outlet after the dismantling of the coaxial adapter ∅60/∅100 and reducing ring ∅60/∅80 the adapter should be
screwed (index T9000.01.11.00). Bottom part of the adapter should be inserted in the boiler flue gas outlet and the connection
should be sealed by the gasket attached to the adapter
To apply the polypropylene two-pipe system should:
•Unscrew the top cover of the combustion chamber at point of connection of the air supply system to the boiler
•Disassemble coaxial adapter ∅60/∅100 and reducing ring ∅60/∅80
•Mount adapter set (index T9000.02.10.00)
Notice: The horizontal air tube should be mounted at an angle of ~ 3°( Figure 3.8.5.1) so that rain water that gets into the pipes
would not flood the boiler and flowed outside the building.
Table 3.8.5.1.
80
1
H
2
80
H
Air
Elements of steel air-flue gas pipes
Fumes
Type of boiler Separate system
∅80 x ∅80
ECOCONDENS SILVER PLUS -20
Maximum length of chimney
flue H
1
+ H
2
L
max
=25 + 25 = 50 m
ECOCONDENS SILVER PLUS -25
Maximum length of chimney
flue H
1
+ H
2
L
max
=25 + 25 = 50 m
ECOCONDENS SILVER PLUS -35
Maximum length of chimney
flue H
1
+ H
2
L
max
=20 + 20 = 40 m

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.15
3.8.6 Reduction of the maximum length of the air-flue system by changing the flow direction
Reduction of the max length of the air-flue system by changing the flow direction
15° 45° 90°
0.25m 0.5m 1m
3.9. Connection of additional devices
On the back of the controller there are two flaps under which there is access to electrical terminals.
To connect an additional device unscrew the appropriate flap, put the cable through the bushing in the flap and connect the ends of the
wire to the correct terminals.
RT/OT – room temperature controller (red wire) AFS – outside temperature sensor (black wire)
in system boilers: CZ – tank temperature sensor TZ- tank time regulator
in boilers with PWM pump: PWM- PWM pump control C1 – return heating water temperature sensor
Fig.3.9.1 Electrical terminals of controller - a back view
3.9.2 Connection of a room temperature regulator
3.9.2.1 Room regulator with contact.
The boiler has been designed to cooperate with a room temperature control unit which has got its own supply source and control
contact free from potential. Connections must be made according to the instructions of regulator manufacturer. In order to connect the
temperature thermostat to the boiler the appropriate length two-core wire is needed. It needs to be connected to terminals 1 and 2
(RT/OT) located under the right flap ( Fig. 3.9.1) - previously separating the electrical bridge.
To connect room temperature regulator to the boiler we advise to contact a qualified person or AUTHORIZED INSTALLER.
3.10. Connecting the outside temperature sensor
To connect the outside temperature sensor use the 2 wire cable (2x0,5mm
2
50m max) and connect it to terminals 3 and 4 (AFS)
located under the right flap Fig. 3.9.1.
Connection must be made in accordance with the instructions provided by the sensor manufacturer. It is the best to place the outside
temperature sensor on the north wall of the building and it should not be exposed to direct sunlight.
4. BOILER ADJUSTMENT AND PRELIMINARY SETTING
4.1. Introductory remarks
Purchased boiler is factory adjusted according parameters for the type of gas that is provided on the rating plate and in and the
documentation of the boiler. Only AUTHORIZED FACTORY SERVICE can do any and parameter settings of the boiler if there is any
need to change the parameters or to adjust the boiler to another type of gas.
4.2. Adjusting the boiler to combust another type of gas
The boiler can be adjusted to combust another type of gas but only for this one which the boiler is certified for. The types of gases are
given on the rating plate - in the index designation:
Categorie
II
2H3+
Group 2 – natural gases:
2H-G20 (2E) Group 3 – liquefied gases
3B/P-G30
3P-G31
Example of completed label:
s.a
After adapting the boiler to combust another type of gas:
•Cross out on a rating plate the type of gas to which the boiler was adapted by the
manufacturer,
•Write down the symbol of the gas, to which the boiler has been adjusted and the set
heat load on the appropriate label that is attached bulk to the user manual. The entry
must be written legibly and indelibly.
•
Label filled in as above should be sticked on the cover near rating plate.
Setting for the
gas:
liquefied
Gas symbol
:
3
B/
P
Gas pressure
[mbar]
3
0
Set the nominal heat load
........................... [kW]

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.16
Adapting the boi
ler to combust another type of gas can be performed only by QUALIFIED SERVICE COMPANY. This
operation is not included in the warranty repairs.
In order to perform above mentioned operations check if:
•the tightness of the gas system connections was checked after the boiler installation and it was confirmed with the signature
and the stamp of the installer,
•the electrical installation was made in accordance with applicable regulations,
•the correctness of connections between the boiler and the chimney was checked and confirmed by a qualified chimney
service.
2. Gas valve coils EV1-EV2,
3. Measuring point of inlet gas pressure,
4. Measuring point of outlet gas pressure,
5. A minimum pressure adjustment screw,
6. A maximum pressure adjustment screw
Fig. 4.2.1 Gas valve
4.3. Boiler adjustment
Below described ways of regulation are applied only for replacement of the gas unit. All regulations must be based on the equipment
listed in Table 4.3.2.1.
4.3.1. Gas flow regulation in the boiler (without using the flue gas analyzer)
Before proceeding to adjustment, activate the service function of the boiler in the following way:
- set the mode: WINTER; p.5.3
- press the button twice
- on the display symbol flashes;
left field shows fan rotation speed and max symbol placed over it, right field show
C.H. temperature.
,
- in time to 5 seconds press the button + for 2 sec.; after service function activation the symbol stops flashing,
- using the button”+” you can turn on maximum fan speed (defined by parameter P05),
- using the button”-” you can turn on minimum fan speed (defined by parameter P04),
- service function is activated for 10 min. Earlier termination - pressing the reset button.
Regul
ation of boilers with power
20kW, 25kW
and
35kW
Maxim
um power adjustment
Minimum power adjustment
•Set the maximum fan speed according to 4.3.1
Check the gas flow rate on the gas meter for compliance
with Table 4.3.2.1. If you need to change the gas flow
turn the screw - pos. 6 (Fig. 4.2.1.).
•Turn the screw to the left to increase the flow, turn the
screw to the right to decrease it. Set value of flow you
can read on the gas meter.
•Set the minimum fan speed according to 4.3.1
•During boiler operation measure the gas inlet pressure on the
measuring point (item.3 Fig. 4.2.1.) The value of pressure
depending on the type of gas are given in Table 4.3.2.1,
•Remove the cap from the measuring point number 5
(Fig.4.2.1.)
•Using the adjusting screw number 5 (Fig. 4.2.1) set the
minimum gas flow according to the values given in Table
4.3.2.1.
•Turn the screw to the right to increase the flow, turn the screw to
the left to decrease it.
4.3.2. Adjustment of the boiler with a gas analyzer
Regulation of boilers with power
20kW, 25kW
and
35kW
Maximum power adjust
ment
Minimum power adjustment
•Set the maximum fan speed according to 4.3.1
•During boiler operation measure the gas inlet pressure
on the measuring point (item.3 Fig. 4.2.1.) The value
of pressure depending on the type of gas are given in
Table 4.3.2.1,
•Connect the flue gas analyzer
•Using the adjusting screw number 6 (Fig.4.2.1) set the
gas flow to obtain the required composition of the flue
gas listed in Table 4.3.2.1.
•Set the minimum fan speed according to . 4.3.1
•During boiler operation measure the gas inlet pressure on the
measuring point (item.3 Fig. 4.2.1.) The value of pressure
depending on the type of gas are given in Table 4.3.2.1,
•Connect the flue gas analyzer
•Remove the cap from the measuring point number 5
(Fig.4.2.1.)
•Using the adjusting screw number 5 (Fig.4.2.1) set the gas
flow to obtain the required composition of the flue gas listed in
Table 4.3.2.1.
NOTICE:
Check the settings for the max and min. gas flow.
If the adjustment is complete, close all measuring points
, then
check t
ightness and re
-
seal them
.
The data specified for gases at normal conditions (15
o
C, pressure 1013 mbar), having regard to boiler efficiency -97.4.
Table 4.3.2.1. The control parameters of the boiler

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.17
Min power Max power
ECOCONDENS SILVER PLUS ECOCONDENS SILVER PLUS
20 25 35 20 25 35
Gas type Inlet pressure
(mbar)
P04=12 P04=12 P04=12 P01= 25 P05=77 P01= 25 P05=76 P01= 25 P05=83
P03= 79 P02=99 P03= 79 P02= 99 P03=85 P02= 99
The content of CO2 in the flue gas [%] The content of CO2 in the flue gas [%]
10.0
±
0.
2
9.5
±0.
2
Gas flow rate [l/min.]** Gas flow rate [l/min]**
2H-G20,
2E-G20 20 ÷ 25 4.8
+0.5
6.9
+0.5
7.3
+0.5
35.3
+1
44.3
+1
42.6
+1
53.1
+1
61.9
+1
71.4
+1
Min power Max power
ECOCONDENS SILVER PLUS ECOCONDENS SILVER PLUS
20 25 35 20 25 35
Gas type Inlet pressure
(mbar)
P04=12 P04=12 P04=12 P01= 35 P05=66 P01= 35 P05=64 P01= 40 P05=63
P03= 77 P02= 99 P03= 79 P02= 99 P03= 86 P02= 99
The content of CO2 in the flue gas [%]
The content of CO2 in the flue gas [%]
11.0
+0.5
11.0
+0.5
Gas flow rate [l/min.]** Gas flow rate [l/min]**
3B/P-G30 37 1.4
+0.5
2.0
+0.5
2.1
+0.5
10.2
+1
12.8
+1
12.3
+1
15.3
+1
17.9
+1
20.5
+1
Min power Max power
ECOCONDENS SILVER PLUS ECOCONDENS SILVER PLUS
20 25 35 20 25 35
Gas type Inlet pressure
(mbar)
P04=12 P04=12 P04=12 P01= 40 P05=74 P01= 40 P05=72 P01= 40 P05=77
P03= 77 P02= 99 P03= 77 P02= 99 P03= 87 P02= 99
The content of CO2 in the flue gas [%] The content of CO2 in the flue gas [%]
11.0
+0.5
11.0
+0.5
Gas flow rate [l/min.]** Gas flow rate [l/min]**
3P-G31 37 1.8
+0.5
2.6
+0.5
2.8
+0.5
13.4
+1
16.9
+1
16.3
+1
20.3
+1
25.6
+1
27.0
+1
*During adjustment the boiler with removed cover of the chamber consider to increase amount of CO
2
given in table 0.2 ÷ 0.3%
**Listed in the table value of gas flow are indicative. Their value depends on the actual content of CO
2
in the flue gas.
***If the system boiler is connected to domestic water tank, set the parameter P02 in accordance with power of tank’s coil.
4.4. Fan characteristics
Fig.4.4.1. Characteristics of the fan
-
type
NG40m
5. STARTUP AND OPERATION OF THE BOILER
5.1. Initial startup of the boiler
After installing the boiler, checking the accuracy and tightness of its connections and preparing for operation in accordance to this
instruction manual and applicable regulations first commissioning and user training for boiler operation and safety devices may be done
only by AUTHORISED SERVICE COMPANY.
5.2. Inclusion and operation
All boiler functions are performed by the boiler electronic control panel. Changing the operating mode and settings is done done by 4
buttons. Current state of the boiler is shown on the LCD display.
Fig. 5.2.1. Control panel

ECOCONDENS SILVER PLUS
ISU-646:2016/GR-H str.18
•Check the pump (item.6.1.6),
•Connect the boiler to the electrical mains,
•Open the gas valve and water valves,
•Turn on controller by using an electric switch, available at the bottom of the boiler through a hole in the bottom tray
(Fig. 2.2.1.1 and 3.9.1)
•Wait until the boilers enters auto-diagnosis mode.
•Set the mode WINTER or SUMMER (item.5.3)
The turning on of the boiler in the heating season
•Set the desired temperature of the heating water using buttons:{+ / - CH} in the range of 40°C to 80°C
•The spark generator will cause ignition of gas outflowing from the burner.
•Set the desired water temperature using buttons (pos.6) in the range of 30°C to 60°C.
Remember! The priority is always to obtain domestic hot water during operation of the boiler
When the room temperature controller is connected, set desired room temperature on the controller.
5.3. Operating modes of the controller
Mode Display Changing the operating mode Performed functions
STAND-
BY
To turn on /turn off the controller
press the RESET button for
about 2 seconds
•
anti-freezing function: the boiler is
switched on when the boiler
water temp. drops below 8°C and
heats
the water as long as the
temperature reaches 20°C
•protection against pump blocking
(pump is switched on 180 sec
every 24 hours)
•3-way valve blocking protection
(valve is switched on 15sec.
every 48 hours)
WINTER
Press button
for about 1 second -
changing the operating mode
to mode WINTER
•CH and DHW heating,
•Service function,
•Anti-legionella function - active
only for boilers with tanks
SUMMER
Press button
for about 1 second -
changing the operating mode to
mode SUMMER
•D.H.W. heating,
•Anti-legionella function - active
only for boilers with tanks,
5.4. Signalization of operation states and diagnosis
When the controller starts the operation after power loss (restart) the display shows a flashing symbol . The symbol disappears if the
control system will be ready to accept user commands.
Symbol
on the
display
Signalization Remarks
BURNER IS OPERATING Left flame: DHW mode operation.
Right flame: CH mode operation.
WEATHER FUNCTION
IS ACTIVE
During the CH setting changing, instead of the temperature the value of Kt parameter
is displayed
for example: 5.2 without symbol: °C.
CHANGING C.H. SETTING
During changing the CH setting symbol flashes with the set value.
CHANGING DHW SETTING
During changing the DHW temperature setting symbol flashes with the set
value.
MAX
MAXIMUM SETTINGS Maximum setting value is reached. If you exit the setting changes mode the symbol is
blanked.
MIN
MINIMUM SETTINGS Minimum setting value is reached. If you exit the setting changes mode the symbol is
blanked.
L3
PAUSE IN C.H. HEATING
Displayed
L3
symbol means a pause in C.H. heating in time determined by parameter
P25 (default 3 min) for heat exchanger cooling when C.H. temperature exceedes the
hysteresis value (parameter P20, default 5°C) of th e setting. Pump operation will be
stopped if the following conditions are met:
• no signal „HEAT” from room temperature regulator,
• heating water temperature dropped by 5°C from the the set value
• 180 sec. have passed after burner switching off.
r
e
s
e
t
r
e
s
e
t
r
e
s
e
t
This manual suits for next models
2
Table of contents
Other TERMET Boiler manuals
Popular Boiler manuals by other brands

Biasi
Biasi Delta User manual and installation instructions

REMEHA
REMEHA Gas 210 ECO technical information

Sime
Sime SOLO 25-35 BF TS instructions

HydroTherm
HydroTherm PB Installation and operating instructions

Chaffoteaux & Maury
Chaffoteaux & Maury Moduloflame 140 Installation and Servicing Manual

Sime
Sime ECOMFORT PLUS 25 HE User instructions