5
If the water temperature reached 200°,
due to a failure of the perating Control
Limit, for example, the High Limit safety
will shut off all elements at once.
The High Limit Safety is set at 200°
Do not attempt to change the High
Limit setting. Do not set the Operating
Control Limit a ove 180°. Remem er,
this is not a low temperature set point
like on an oil or gas fired oiler. There
is no low set point and, if there is a call
for heat, the circulator will run and the
elements will e energized as long as
the thermostat calls for heat and the
Operating Control Limit and High
Safety limit are not reached.
Refer to the instruction sheet for the
control when making adjustments.
MAINTENANCE
A trained and experienced service per-
son should check the system prior to
each heating season. The supply break-
er to the electric boiler should be off
prior to performing any service.
If a component is changed in the sys-
tem, follow the start-up procedure in
this manual prior to operating the unit.
Check for leaks after every mainte-
nance, once per year and if there is any
visual evidence of a leak. To check for
leaks, shut the water supply valve and
observe the pressure gauge. Any loss of
pressure indicates a leak in the system
that must be repaired.
Frequent heater element failures or
short heater element life is an indication
that there is air in the system. Follow
the start-up procedure to make sure
that all air is eliminated from the sys-
tem and verify that the system is leak-
free to prevent introduction of air dur-
ing operation.
Staging
The TDE-15, 20, 25 and 30 can be
“staged” using a second thermostat or
a dual thermostat. Staging may be a
valuable feature if the user’s electric bill
is based on peak demand. Staging pre-
vents the timed elements from energiz-
ing unless the temperature set point of
a second or third thermostat is reached.
A careful heat balance is required to set
the TDE for effective staged operation.
The staging terminals shown in the
wiring diagrams have a factory installed
jumper when delivered. When the ther-
mostat closes on a call for heat, the first
two heater elements are energized
immediately. The remaining elements
are energized, two at a time at one
minute intervals. To stage the TDE,
remove the factory installed jumper and
install a thermostat or outdoor stat (Not
provided) wired to the same terminals
where the jumper was removed. The
thermostat may be located outdoors, or
in a zoned space and set or selected so
that if the temperature is above the
thermostat set point, heater elements
that are time delayed will not turn on. If
the outside temperature or a separate
zone temperature is below the second
thermostat set point, the time delayed
heater elements will be energized after
the appropriate time delay. The TDE-25
and 30 have two staging terminal sets.
The second factory installed jumper can
be used so that the first two heaters are
energized by a call for heat from the
interior thermostat and the remaining
heater elements are energized only if
the second thermostat set points are
reached. Both sets of staging terminals
can be connected to thermostats to