
13
•DRAWINGS FOR ILLUSTRATION PURPOSES ONLY•
Installation
Pleasesee allmethodsofInstallation
inAppendixattherearofthisbooklet.
Thisisafurnace,notafreestandingstove.Youmust
directheatedairfrom12"outletawayfromthefurnace,
or it will not function properly.
1. This installation must be done by a qualified
heatingequipmentinstaller.
2. The installation is to be done in compliance with
National Fire Protection Association installation
standards: No. 89M, 90B, 211, 70 (National Electric
Code) and Uniform Mechanical Code 913, 6-4, in the
stateswhereapplicable.(Theircodeoffersconnecting
smoke pipe connectors into chimney with other fuel
burningappliances.)
3. Rooms large in comparison with size of the
appliances:
a)AWoodBurningFurnaceneedsairfor combus-
tion and circulation to house.
b)Provisionmustbemadetomakeupthisairand
not starve gas or oil furnace of combustion air.
c) Have "Authority Having Jurisdiction"
determinethatairisofadequatemakeup. (Reference
N.F.P.A.Nos.30&54,CodeforInstallationofGas&Oil
Equipment)
4.Have"AuthorityHavingJurisdiction"to inspectall
chimneysandinstallationsforadequateventingandfor
compliance with standard and local codes and regula-
tionsregardinginstallationofwoodburningappliances.
5. Installation of Supplemental Heat Application to
ExistingCentralSystem.(SeeFig.12fortypicalinstal-
lation.)
a) Place Wood Burning Furnace so that the
chimney connector will be as short as possible and
avoiding unnecessary sharp turns in the smoke pipe
connector and the installation of devices that would
create excessive resistance to the flow of flue gases.
b)LocatetheWoodBurningFurnaceascloseas
practical to the existing central hot air heating system,
maintainingclearancesasstatedonthelabellocatedon
the side of the furnace.
c) Clearances from combustible materials must
be complied with as stated on the label below the fuel
door:
Theinstallationmustbemadeonlyonanoncombustible
floor. d)Installthesmokepipeconnectortothechimney
with26-gaugepipeandelbows(tobepurchasedsepa-
rately), maintaining the proper clearances for the spe-
cific model. Make sure that the proper clearances as
stated on the label and earlier in this manual are
maintained. Seal the smoke pipe in the chimney with
furnace cement. (The chimney connector shall be se-
curely supported, and joints fastened with sheet metal
screws or rivets.)
e) Install 8" diameter heat pipe to plenum of the
centralhotairfurnace.Use26-guagepipeand connec-
tors(tobepurchasedseparately).(SeeFig.13)Ifcentral
air conditioning is installed in the plenum, install heat
pipe above the air conditioning unit. Secure heat pipe
connection with supports and sheet metal screws.
f) Connect electrical supply in the electrical
junction box that is mounted on the back of the Wood
Burning Furnace. See Wiring Diagram (Fig. 11). Re-
move the cover from electrical junction box connect
powersupplywirestowiresdesignated,usingwirenuts.
Thepowercordsuppliedmaybeusedforinstallation,if
permitted by local codes and regulations. If the power
cordsuppliedcannotbeused,thepowersupplywiring
must be 90 degrees Centigrade in a metal cable and
shouldbe completed bya qualified installercomplying
with NFPA Standard No. 70 and local codes.
g)OptionalPlenumFanControlSwitch(PartNo.
11PCS) is available for installation on the plenum of
central hot air heating furnace. The purpose of this
switchistoactivatethecirculatingfanofthecentralhot
airheatingfurnacewhenthetemperatureintheplenum
exceeds120°Fahrenheit.Theswitchwouldactivatethe
fanat120°Fahrenheit,andwouldshutoffthecirculating
fan when the temperature in the plenum is reduced to
100°Fahrenheit.Thisavoidsoverheatingtheplenum.
Theelectricalsupplyforoperationofthisfancontrol
switchistobeobtainedfromsameelectricalsupplyas
thecentralhotairheatingsystem.(SeeFig.13)Follow
theinstructions ofthe wiring diagram (Fig.14). Do not
make connections across Limit Control in the furnace.
Make electrical connections in electrical junction
boxpresentlymountedonthefurnace.Makeelectrical
connectionsinaccordancewithNFPAStandardNo.70
and local codes in the power supply junction box (See
Fig.14).Thewiringtocompletetheconnectionsshould
be 18 AWG minimum copper and 90° Centigrade in a
cable.
Unit to Combustible:
Front: 48"
Back: 30"
Sides: 12"
Plenum to Ceiling: 6"
Pipe to Combustible:
Sides: 21"
Back: 18"
NOTE: THE MAXIMUM STATIC PRESSURE AT THE CENTRAL OR COMBINED PLENUM MUST NOT
EXCEED 0.12 INCHES WATER COLUMN.