Aalborg i/o 232 User manual

CAUTION:
THIS PRODUCT DOES NOT PROVIDE GALVANIC ISOLATION. DO NOT ATTEMPT USE OF
THIS PRODUCT WHERE COMMON MODE VOLTAGES EXIST BETWEEN INPUTS, OUTPUTS,
POWER SUPPLY, OR THE SERIAL COMMUNICATIONS TERMINALS.
OPERATING MANUAL
I/O SIGNAL
CONDITIONER
Technical Data Sheet No. TD9809M Rev. F
Date of Issue: December 9, 2009
+7(77172)727-132 (844)278-03-48 (473)204-51-73 (343)384-55-89
(843)206-01-48 (861)203-40-90 (391)204-63-61 (495)268-04-70
(831)429-08-12 (383)227-86-73 -- (863)308-18-15
(846)206-03-16 - (812)309-46-40 (845)249-38-78 (347)229-48-12
: [email protected] -: aalborg.nt-rt.ru

TABLE OF CONTENTS
(a) UNPACKING THE I/O SIGNAL CONDITIONER................................
a.1 Inspect Package for External Damage.....................................
a.2 Unpack the Signal Conditioner...............................................
a.3 Returning Merchandise for Repair..........................................
(b) DESCRIPTION......................................................................
(c) FEATURES..........................................................................
(d) SPECIFICATIONS..................................................................
d.1 General Attributes....................................................................
d.2 CE Compliance.........................................................................
(e) ELECTRICAL CONNECTIONS....................................................
e.1 Connector Pin Assignments....................................................
e.2 Jumper Assignments...............................................................
(f) PROGRAMMING..................................................................
(g) CALIBRATION PROCEDURES...................................................
g.1 Equipment Required for Calibration........................................
g.2 Calibration..............................................................................
(h) SELECTING THE MODE OF OPERATION.......................................
(i) COMMANDS......................................................................
(j) TROUBLESHOOTING GUIDE.....................................................
(k) TECHNICAL ASSISTANCE.......................................................
APPENDIX 1 COMPONENT DIAGRAM
APPENDIX 2 DIMENSIONS
APPENDIX 3 CONNECTION DIAGRAM FOR RS232 and RS485
APPENDIX 4 WARRANTY
1
1
1
1
2
2
2
2
3
3
3
4
4
5
5
5
6
6
9
9

(a) UNPACKING THE I/O SIGNAL CONDITIONER
a.1 Inspect Package for External Damage
Your I/O Signal Conditioner was carefully packed in a sturdy cardboard
carton, with anti-static cushioning materials to withstand shipping shock.
Upon receipt, inspect the package for possible external damage. In case
of external damage to the package contact the shipping company imme-
diately.
a.2 Unpack the I/O Signal Conditioner
Open the carton carefully from the top and inspect for any sign of con-
cealed shipping damage. In addition to contacting the shipping carrier
please forward a copy of any damage report to your distributor or Aalborg
directly.
When unpacking the instrument please make sure that you have all the
items indicated on the Packing List. Please report any shortages promptly.
a.3 Returning Merchandise for Repair
Please contact the customer service representative of your distributor or
Aalborg if you purchased your I/O directly, and request a Return
Authorization Number (RAN). Equipment returned without an RAN
will not be accepted. Aalborg reserves the right to charge a fee to the
customer for equipment returned under warranty claims if the instruments
are tested to be free from warrantied defects.
Shipping charges are borne by the customer. Items returned "collect"
will not be accepted!
It is mandatory that any equipment returned for servicing be purged and
neutralized of any dangerous contents including but not limited to toxic,
bacterially infectious, corrosive or radioactive substances. No work shall
be performed on a returned product unless the customer submits a fully
executed, signed SAFETY CERTIFICATE. Please request form from the
Service Manager.
1

(b) DESCRIPTION
This Signal Conditioner allows analog voltage levels to be set and read
via its RS-232 serial port. Commands are provided to perform various
functions: an analog output, read an analog input, verify the communica-
tions link, programming, and enter calibration mode.
(c) FEATURES
The I/O is capable of operating in a voltage output mode or a current out-
put mode. When operating in the voltage mode the analog input and out-
put range is 0.00 to 5.00 volts. In the current mode the analog input and
output range is 4.00 to 20.0 milliamps. See Selecting the Operating Mode.
(d) SPECIFICATIONS
d.1 General Attributes
INPUT AND OUTPUT ANALOG RANGE: 0 - 5 Vdc or 4 - 20 mA, jumpers selectable.
INPUT OVERVOLTAGE/OVERCORRECT PROTECTION: 15 Vdc, 50 mA.
MINIMUM OUTPUT VOLTAGE COMPLIANCE IN 4-20 mA MODE: 8 Vdc.
MAXIMUM INPUT VOLTAGE DROP IN 4-20 mA MODE: 5 Vdc.
POWER SUPPLY REQUIREMENTS: 10 to 30 Vdc, less than 0.75 watts (OPTIONAL).
OPERATING TEMPERATURE RANGE: 0 FC to 70 FC.
ALTITUDE: to 10,000 feet.
DIGITAL VOLTAGE STANDARD: RS-232 or RS-485 (not galvanically isolated).
COMMUNICATIONS PARAMETERS: 8 bits, one stop bit no parity (N,8,1).
RS-232 COMMON MODE CAPABILITY: +10 volts.
RESOLUTION: 10 bits (0.1%).
DATA FORMAT: ASCII.
DATA TRANSFER RATE: 300 baud to 9600 baud.
MODULE CONNECTION METHOD: Pinch Type terminals.
2

d.2 CE Compliance
Any model I/O Signal Conditioner bearing a CE marking on it, is in com-
pliance with the below stated test standards currently accepted.
EMC Compliance with 89/336/EEC as amended;
Emission Standard: EN 55011:1991, Group 1, Class B
Immunity Standard: EN 55082 1:1992
Environmental (per IEC 664): Installation Level II; Pollution Degree II
(e) ELECTRICAL CONNECTIONS
e.1 Connector Pin Assignments
All connections are made at connector J1. This is a pinch type connector.
Insert a small flat blade screwdriver into the slot along the top of J1 and
press down. This will cause the pinch clamp to open allowing the stripped
wire to be inserted. Remove the screwdriver and the connection is made.
Pin 1 - Analog input from sensor IN+
Pin 2 - Analog input from sensor IN-
Pin 3 - Analog output to sensor OUT+
Pin 4 - Analog output to sensor OUT-
Pin 5 - Data output from module TX (-)
Pin 6 - Data input to module RX (+)
Pin 7 - Power supply input to module 10VDC - 30VDC
Pin 8 - Power supply return (GND)
3
Terminal Number Maximum Voltage VDC) Mode
1
1
15
10
voltage input
current input
3
3
(see note)
(see note)
voltage output
current output
5
5
(see note)
15
RS-232
RS-485
6
6
15
15
RS-232
RS-485
733all
CAUTION: Exceeding the following voltages will cause device
failure and/or hazardous conditions to exist.
Note: The applicable terminals are utilized as outputs. Do not
apply any external voltage or current sources to these terminals.

The power input is protected by a 1A re-settable fuse. If a shorting con-
dition or polarity reversal occurs, the fuse will cut power to the flow trans-
ducer circuit. Disconnect the power to the unit, remove the faulty condi-
tion, and reconnect the power. The fuse will reset once the faulty condi-
tion has been removed.
e.2 Jumper Assignments
JP1 - Program mode jumper
Pins 1 and 2 select Run mode
Pins 2 and 3 select Program mode
JP3 - Input mode jumper
Pins 1 and 2 select 0 - 5VDC mode (factory default)
Pins 2 and three select 4 - 20 mA mode
JP2, JP4, JP5 - Output mode jumpers
Pins 1 and 2 select 0 - 5VDC mode (factory default)
Pins 2 and 3 select 4 - 20mA mode
(f) PROGRAMMING
Programming the module allows the user to set the communications baud
rate, module address and, whether to use error checking. Note that the
address is included only for compatibility with the RS-485 version of this unit.
Connect a dumb terminal or PC running a communications program,
such as Procomm, to the unit.
RS232 APPLICATION:
Connect the unit TX line to the terminal RX line, connect the unit RX line
to the terminal TX line. Connect the I/O GND (pin 8) to SG Terminal.
4
CAUTION: Make sure power is OFF when connecting or
disconnecting any cables in the system.
CAUTION: Improper setting of jumpers may result in incorrect
operation of the unit and could cause damage to the connected
equipment.
Note: All I/O conditioners are programmed on the factory by
default settings: address 1, baud rate 9600, and error checking
OFF.

RS485 APPLICATION:
Make sure RS485 Terminal Equipment (RS-485 to RS232 Converter) is con-
figured for bidirectional Multi drops Two-Wire Half-Duplex operation (TX+ is
connected to RX+ and TX- is connected to RX-). Connect the unit TX(-) line
(pin 5) to the terminal TX- line, connect the unit RX+ line (pin 6) to the termi-
nal TX+ line. Connect the I/O GND (pin 8) to terminal GND (if applicable).
To program the module remove power from the unit and install the short-
ing plug on jumper JP1 between pins 2 and 3.
Apply power to the unit and follow the on screen instructions. When pro-
gramming is completed turn the unit off, place the shorting plug on jumper
JP1 on pins 1 and 2 to return the module to run mode, the new settings will
take affect when the unit is powered on. The initial power on defaults are
9600 baud, 8 data bits, 1 stop bit, no parity, error checking off, address 0.
(g) CALIBRATION PROCEDURE
g.1 Equipment Required for Calibration
You will need a 3-1/2 digit DMM set to the selected analog output range
(see Selecting Operating Mode), a power supply and, a dumb terminal or
PC running a communications program, such as Procomm.
g.2 Calibration
Connect the dumb terminal or PC.
RS232 APPLICATION: Connect the unit TX line to the terminal RX line,
connect the unit RX line to the terminal TX line. Connect the I/O GND (pin
8) to the SG line terminal.
RS485 APPLICATION: Make sure RS485 Terminal Equipment (RS-485
to RS232 Converter) is configured for bidirectional Multi drops Two-Wire
Half-Duplex operation (TX+ is connected to RX+ and TX- is connected to
RX-). Connect the unit TX(-) line (pin 5) to the terminal TX- line, connect
the unit RX+ line (pin 6) to the terminal TX+ line. Connect the I/O GND
(pin 8) to terminal GND (if applicable).
Apply power to the I/O, issue the calibrate command and follow the on
screen instructions. See Host C command for format.
5
Note: All I/O conditioners are calibrated on the factory for
0 - 5V mode. Usually it is not necessary to calibrate unit,
unless 4 to 20 mA mode is required.

(h) SELECTING THE MODE OF OPERATION
Before operating in the desired mode the I/O has to be calibrated in the
same mode.
To set the unit to operate in 0 - 5V mode install shorting plugs between
pins 1 and 2 on JP2, JP3, JP4 and, JP5. If 4 - 20mA current mode is
desired install the shorting plugs between pins 2 and 3 on JP2, JP3, JP4
and, JP5. See Jumper Definitions for more detail.
(i) COMMANDS
The following is a list of the valid commands, command format and, unit
response.
Host Command format:
> address command X X X X crc CR
Where: > message start character
Address unit address is any single printable ASCII
command character one of the commands from below
X X X X optional four ASCII characters, used by the unit to set
the analog output
crc optional error checking characters, the crc is composed
of two ASCII characters
CR ASCII carriage return character
There are no spaces in the transmitted command, spaces are inserted here only to
make the command easier to read. If a crc is not used it is not sent in the com-
mand line. Commands sent by the host are preceded with a start character sym-
bol, >. All commands are terminated with a CR. If data bytes are not required by
the command they are not included in the command line.
I/O Module Response format:
# X X X X X crc CR
Where: # message start character
command one of the commands listed below
X X X X X up to five ASCII characters, used to report
the analog input of the unit back to the host
crc optional error checking characters, the crc is
composed of two ASCII characters
CR ASCII carriage return character
There are no spaces in the transmitted response, spaces are inserted here only to
6

make the response easier to read. If a crc is not required it is not sent in the
response line. Responses sent by the I/O Module are preceded with a start char-
acter symbol, #. All responses are terminated with a CR. Only the number of data
bytes required by the response are sent. Leading zeroes are stripped.
Host S Command:
S or s - This command queries the I/O Module for its communication status.
If the communications line is intact the I/O Module responds to the host
with an “OK”.
An example of a valid command to a unit with address M:
> M S crc CR
> M s crc CR
The reply format is:
#OK crc CR
If the command is not recognized, the I/O Module responds with “Bad Command”.
An example of an invalid command:
> M x crc CR
The reply format is:
#Bad Command crc CR
If the command is not received no response is sent.
Host T Command:
T or t - This command tells the I/O Module to transmit its current reading. Up
to five ASCII characters are sent by the I/O Module. The returned data is in
millivolts if the module is operating in a 0 - 5V mode. If the module is
operating in a 4 - 20mA mode the data is in microamps.
An example of a valid command to a unit with address 5:
> 5 T crc CR
> 5 t crc CR
The reply format is:
#1000 crc CR which corresponds to 1000 mV
or
#19500 crc CR which corresponds to 19500uA
If the command is not recognized “Bad Command” is returned.
An example of an invalid command to a unit with address 5:
> 5 x crc CR
The reply format is:
#Bad Command crc CR
If the command is not received no response is sent. The module returns the ana-
log input data if the command was received and understood.
7

Host R Command:
R or r - This command tells the I/O Module to receive a new set point. Four
characters must be sent and one of these characters is always a decimal point.
If the set point does not fill all four characters trailing zeroes are added. A crc
is added if error checking is enabled, otherwise it is not sent. If the command
is not recognized “Bad Command” is returned.
An example of a valid command to a unit with address >:
> > R 1.00 crc CR
> > r 1.00 crc CR
An example of an invalid command to a unit with address r:
> r W 1.00 crc CR
The reply format is:
#Bad Command crc CR
If the command is not received no response is sent. The module sends “OK”
if the command was received and understood.
The reply format is:
#OK crc CR
Host C Command:
C or c - This command tells the I/O Module to enter calibration mode.
Calibration instructions are sent to the terminal display. See Calibrating the I/O
Module for calibration procedure. If the command is received and understood
the unit enters calibration mode.
An example of a valid command to a unit with address @:
> @C crc CR
> @c crc CR
If the command is not recognized “Bad Command” is returned.
An example of an invalid command to a unit with address @:
> @q crc CR
The reply format is:
#Bad Command crc CR
Host G Command:
G or g - This command tells the I/O Module to accept a global command. This
is included for compatibility with the RS-485 version of this unit. The syntax is
the same as the R command except the address is 0 and no response is sent
by the module.
An example of a valid command is:
> 0 G crc CR
> 0 g c crc CR
8

(j) TROUBLE SHOOTING
Your I/O Signal Conditioner was thoroughly checked at numerous quality
control points during and after manufacturing and assembly operations. It
was calibrated in accordance to conditions for a given.
It was carefully packed to prevent damage during shipment. Should you
feel that the instrument is not functioning properly please check for the fol-
lowing common conditions first:
Are all cables connected correctly?
Is the power supply correctly selected according to requirements?
When several meters are used a power supply with appropriate
current rating should be selected.
Were the connector pinouts matched properly?
When interchanging with other manufacturers' equipment, cables
and connectors must be carefully wired for correct.
For best results it is recommended that instruments are returned to the
factory for servicing. See section a.3 for return procedures.
9
CAUTION: Use of the I/O Signal Conditioner in a manner other
than that specified in this manual or in writing from Aalborg,
may impair the protection provided by the equipment.

10
APPENDIX 1
Components Diagram
NOTE: Aalborg7reserves the right to change designs and dimensions at its sole discretion at any
time without notice. For certified dimensions please contact Aalborg7.

APPENDIX 2
Dimensions
I/O Signal Conditioner
11
NOTE: Aalborg7reserves the right to change designs and dimensions at its sole discretion at any
time without notice. For certified dimensions please contact Aalborg7.
3.000 [76.2]
4.166 [105.8]
1.750 [44.5]
1.031 [26.2]
1.151 [29.2] DIMENSIONS: INCH [mm]
Ø0.187 [Ø4.7]

12
COMMON
+(10-30) VDC
RX(+)
TX(-)
OUT-
OUT+
IN-
IN+
8
7
6
5
4
3
2
1
SIGNAL CONDITIONER
5
9
4
8
3
7
2
6
1
GFM
HOST PC
RS232 PORT
Fig. 1 Connection diagram GFM to I/O232
5
9
4
8
3
7
2
6
1
COMMON
+(10-30) VDC
RX(+)
TX(-)
OUT-
OUT+
IN-
IN+
8
7
6
5
4
3
2
1
SIGNAL CONDITIONER
8
15
7
14
6
13
5
12
4
11
3
10
2
9
1
5
9
4
8
3
7
2
6
1
HOST PC
RS232 PORT
Fig. 2 Connection diagram GFC to I/O232
GFC
APPENDIX 3

13
APPENDIX 4
Note: Follow Return Procedures In Section a.3.
Warranty
Aalborg electronics products are warranted against defects in parts
and workmanship for a period of one year from the date of purchase.
Proper product selection is the responsibility of the customer. It is
deemed the responsibility of the customer that only operators with at
least basic knowledge of the equipment and it’s limitations are
permitted to control and operate the equipment covered by this
warranty. Anything to the contrary will automatically void the liability of
Aalborg and the provisions of this warranty. Defective products will be
repaired or replaced solely at the discretion of Aalborg at no charge.
Shipping charges
are borne by the customer.
This warranty is void if the equipment is damaged by accident or mis-
use, or has been repaired or modified by anyone other than Aalborg or
factory authorized service facility. This warranty defines the obligation of
Aalborg and no other warranties expressed or implied are recognized.
+7(77172)727-132 (844)278-03-48 (473)204-51-73 (343)384-55-89
(843)206-01-48 (861)203-40-90 (391)204-63-61 (495)268-04-70
(831)429-08-12 (383)227-86-73 -- (863)308-18-15
(846)206-03-16 - (812)309-46-40 (845)249-38-78 (347)229-48-12
: [email protected] -: aalborg.nt-rt.ru
Table of contents
Other Aalborg I/O System manuals
Popular I/O System manuals by other brands

M-system
M-system R7G4HEIP-6-DC16A instruction manual

INTELLIGENT CONTROL
INTELLIGENT CONTROL IOTRouter ZHC4013 Application guide

Allen-Bradley
Allen-Bradley Micro800 installation instructions

Siemens
Siemens SIMATIC PROFINET Function manual

MG
MG R1M-GH instruction manual

National Instruments
National Instruments NI-9361 Getting started guide

BVM
BVM PMCDIO64 user manual

National Instruments
National Instruments SC Express PXIe-4309 CALIBRATION PROCEDURE

M-system
M-system Devicenet R7F4DD-DA16B-C instruction manual

ADLINK Technology
ADLINK Technology NuDAQ user manual

MG
MG Devicenet R7F4HD-DC32B instruction manual

Keithley
Keithley DAS-1800HC Series user guide