aci AIM2 Installation instructions

Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 1
Version: 9.0
I0000585
FIGURE 1: DIMENSIONS
INTERFACE SERIES
Installation & Operation Instructions
AIM2
Phone: 1-888-967-5224
Website: workaci.com
GENERAL INFORMATION
The AIM2 optically isolates an analog (voltage
or current) input signal from its
corresponding output signal. It will accept
any input signal between 0 and 20 VDC, or 0
and 20 mA, and output any signal within
those ranges. The AIM2 has preset or
adjustable inputs and preset or adjustable
outputs that can be either voltage or current.
The current signals on the input or output can
be either sink or source. The AIM2 requires
one external 24 VAC isolation transformer
with oating secondary for power. It has an
onboard 24 VAC isolation transformer to
supply power to the isolated output. The
AIM2 is eld calibratable, however, factory
calibration is available upon request for an
additional charge. This will speed up
installation time for the end user.
MOUNTING INSTRUCTIONS
Ground yourself to discharge static electricity
before touching any electronic equipment, as
some components are static sensitive. The
interface device can be mounted in any position. If circuit board slides out of snap track, a non-conductive
“stop”may be required. Use only ngers to remove board from snap track. Slide out of snap track or push
up against side of snap track and lift that side of the circuit board to remove. Do not flex board. Do not
use tools.
WIRING INSTRUCTIONS
PRECAUTIONS
• Remove power before wiring. Never connect or disconnect wiring with power applied.
• When using a shielded cable, ground the shield only at the controller end. Grounding both
ends can cause a ground loop.
• This device needs to have its own Isolated Transformer. This transformer cannot be
connected/or shared with any other device. It is recommended you use an isolated UL-listed class
2 transformer.
• All wiring must comply with all local and National Electric Codes.
I
4.60” (116.84mm)
3.23”
(81.90mm)
3.25”
(8255mm)
4.69” (119.13mm)
0.70”
(17.78mm)

FIGURE 2: WIRING
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 2
Version: 9.0
I0000585
(+)
(-)
Source Current or
Voltage Input Signal
(+)
(-)
Power
24 VAC
Source Current or
Voltage Output Signal
(+)
(-)
Sink (Loop Powered) Current Input
Connections using Internal VDC Supply
Sink Current
Output
Two Wire
Loop
Powered
Device
(+)
(-)
Sink (Loop Powered) Current Output
Connections using External VDC Supply
Input Sink
Current
Connections
24VDC
In
Set Jumper
For Sink Current
Sink (Loop Powered) Current Output
Connections using Internal VDC Supply
Controller
(+)
(-)

TABLE 1: VOLTAGE INPUT RANGE
FIGURE 3: JUMPER SETTINGS
TABLE 2: CURRENT INPUT RANGE
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 3
Version: 9.0
I0000585
INPUT DIP SWITCH
1, 6 ON………………… all others o
1,4,6 ON………………..all others o
1,5,6 ON………………..all others o
1,4,5,6 ON.....................all others o
1,7 ON………………….all others o
1,4,7 ON………………..all others o
1,5,7 ON………………..all others o
1,4,5,7 ON……………...all others o
2,6 ON………………….all others o
3,8 ON………………….all others o
3,4,5,8 ON……………..all others o
VOLTAGE INPUT
0 – 5 V
0 – 10 V
0 – 15 V
0 – 20 V
1 – 5 V
2 – 10 V
3 – 15 V
4 – 20 V
0 – 1 V
Adj. 1 – 9 V
Adj. 9 – 20 V
INPUT DIP SWITCH
1, 6 ON………………… all others o
1,7 ON………………..all others o
2, 6 ON………………..all others o
3, 8 ON.....................all others o
CURRENT INPUT
0 – 20 mA
4 - 20 mA
0 - 1 mA
Adj. 4 -20 mA
Figure A Figure B
The AIM2 is factory set as follows, unless otherwise specied: All DIP switches are set to OFF and will not
produce a proper signal output. Be sure to set switches to your required input and output ranges before
powering. See “SETTING AIM2 INPUT” below.
The AIM2 can be eld calibrated to your specications using the “adjustable” setting on the DIP switches.
See “SETTING AIM2 INPUT” below.
STEP 1) WIRING CONNECTIONS
With the power OFF, make the following connections:
Connect a 24 VAC power supply to the 24VAC terminals of the AIM2. Connect the input signal common (-)
to the COM input terminal of the AIM2, and the input signal positive (+) to the IN input terminal of the
AIM2.
Connect the output signal common (COM) and the output signal positive (OUT) to their respective
terminals on the controlled device.
SETTING AIM2 INPUT
DIP switches determine input ranges. Jumper block J2 is selectable for input voltage (E), current low 0 -
1mA (IL), or current high 0 – 20mA (IH) input signal. A current input can be either sinking or sourcing signal.
Explanation of “Source” and “Sink”:
Source – A signal where the positive (+) modulates and uses the negative (-) as the common. (Most
prevalent in the industry)
Sink – A signal where the negative (-) modulates
and uses the positive (+) as the common.
FOR PRESET VOLTAGE INPUT RANGES: Make
the following switch settings on input DIP switch.
Put Jumper J2 in (E) position (or Horz.) for voltage.
See Table 1.
FOR PRESET CURRENT INPUT RANGES: Make
the following switch settings on input DIP switch.
Put Jumper J2 in (IH) position for current. See
Table 2.
J2 Jumper Settings
For Inputs
J4 & J5 Jumper
Settings For Outputs
J3 Jumper Setting For Direct Or
Reverse Acting
Output
Source
Current
Voltage
Sink
Current
Direct
Acting
Reverse
Acting
0 - 1mA
(Sink or Source)
0 - 20mA
(Sink or Source)
Voltage

TABLE 3: VOLTAGE OUTPUT RANGE
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 4
Version: 9.0
I0000585
OUTPUT DIP SWITCH
1, 2, 4, 5 ON…………… all others o
1, 3, 4,6 ON……………..all others o
4, 5 ON………………..all others o
1,4, 7 ON.....................all others o
VOLTAGE OUTPUT
0 – 5 V
1 – 5 V
0 - 10 V
2 – 10 V
TABLE 5: PRESET OUTPUT SPANS
OUTPUT DIP SWITCH
1,2,3,4 ON…………… 1, 2, 3, 4 ON
2,3,4 ON…………….. 1 OFF
1,3,4 ON……………… 2 OFF
1,2,4 ON..................... 3 OFF
3,4 ON……………...1,2 OFF
2,4 ON……………...1,3 OFF
1,4 ON……………...2,3 OFF
4 ON………………..1,2,3 OFF
1,2,3 ON…………...4 OFF
None ON…………..1,2,3,4 OFF
1,2,3 ON…………...4 OFF
VOLTAGE OUTPUT
1V or 4mA
3V or 12mA
4V or 16mA
5V or 20mA
6V
7V
8V
10V
Adj. 1 – 11V
Adj. 10 – 20V
Adj. 4 – 20mA
TABLE 4: CURRENT OUTPUT RANGE
OUTPUT DIP SWITCH
1, 2, 4, 5 ON…………… all others o
1, 3, 4,6 ON……………..all others o
VOLTAGE OUTPUT
0 – 20 mA
4 - 20 mA
CALIBRATIONS OF INPUT SIGNAL OTHER THAN PRESETS SHOWN ON TABLE
1.) If you have an input range other than any presets shown above, set the input DIP switches to one of the
three Adj. settings. See inputs above in bold type.
2.) Apply the maximum of the input signal to terminals IN and COM. With a volt meter measure the voltage
from TP1 to the AIM2’s input side common (COM). Turn the input Max. pot until the meter reads 5.00 ± 0.00
V. The maximum of the input signal is now calibrated.
3.) If the minimum of the input signal is zero, set input DIP switches 7 and 8 OFF and 6 ON.
4.) If the minimum of the input signal is other than zero, set maximum as in step 2, and use the following
steps to set the minimum:
A.) Set switch 8 ON and 6 and 7 OFF.
B.) Produce the minimum signal value at the input terminal (IN).
C.) Measure the voltage between the TP1 test point and COM. Record or remember.
D.) Now measure voltage between the TP3 test point and COM. Adjust the input MIN pot until the
voltage at TP3 is equal to the voltage recorded at TP1. The minimum and maximum input signals are
now calibrated.
SETTING AIM2 OUTPUT
FOR PRESET VOLTAGE OUTPUT RANGES: Make the following switch settings on output DIP switches.
Set jumper J4 for E/Isnk (voltage/current sink), and J5 for SRC (source) output signal. See Table 3.
FOR PRESET CURRENT OUTPUT RANGES: Make the following switch settings on output DIP switch. If
Source, set Jumper J4 to I and J5 to SRC. If Sink, set J4 to E/Isnk, and J5 to SNK. See Table 4.
FOR CALIBRATION OF AN ODD OUTPUT SIGNAL
Before proceeding, you must have already set up the
input signal. If not, return to page 3 and “SETTING
AIM2 INPUT”.
Output ranges are selectable on the output DIP
switch by setting oset (minimum signal) and spans
available (maximum minus oset) are shown below.
Find out if you can use a preset range by subtracting
the minimum output signal (or oset) from the
maximum. For example, a 3.4 to 9.4 V signal output
equals a 6 volt range, which is available as a preset,
and the 3.4 volt oset can be adjusted. Any span not
listed below will have to be set from one of the
adjustable range switch settings.
TO SET PRESET OUTPUT SPANS (Reference only
switches 1 through 4, others are for OFFSET - See
Table 5).

Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 5
Version: 9.0
I0000585
TABLE 6: PRESET OUTPUT OFFSETS
OUTPUT DIP SWITCH
5 ON…………… 6, 7, 8 OFF
6 ON……………..5, 7, 8 OFF
7 ON……………..5, 6, 8 OFF
VOLTAGE OUTPUT
0V or 0mA
1V or 4mA
2V or 8mA
TO SET ADJUSTABLE OUTPUT SPANS
If your output span is not a listed preset, set the span
DIP switches 1 through 4 to one of the three
adjustable ranges (just above in bold), and the oset
switches to the adjustable range by placing switch 8
ON, and 5,6,7 OFF. Give the AIM2 the maximum input
signal and adjust the SPAN pot until the required span is reached on the output terminals.
Three preset output signal osets are available. These will raise the entire span by the amount indicated,
above zero. For example, an 8V span with a 2V oset will give you a 2 – 10V output signal. If your oset (or
minimum output) is zero, set switch 5 ON and switches 6,7,8 OFF. See Table 6.
ADJUSTABLE OUTPUT OFFSETS
If your oset is not 0, 1, or 2 volts, you will need to adjust for your oset. The oset can be adjusted from 0
to approximately 10V.
Adjustable: 8 ON………………...5,6,7 OFF
Generate the minimum input signal at the input terminals IN and COM and calibrate the output OFFSET
pot until the oset required is reached (check with a voltmeter at output terminals OUT and COM).
From this point on, no further DIP switch changes are necessary. Toggle back and forth between the
maximum and minimum to check the accuracy of the calibration. If the span (or maximum of the output)
needs adjustment, turn the span pot. If the oset (or minimum) needs adjustment, turn the oset pot.
Repeat until calibrated correctly.
POWER UP AND CHECKOUT
STEP 2) POWER UP
Turn on the 24 VAC power supply. Both power indicators on the AIM2 will light.
STEP 3) OPERATION
The AIM2 will now operate to your specications, or the standard settings from the factory. If no eld
calibrations were made, then the AIM2 will accept a 0 to 5 volt DC input signal and produce an isolated and
proportional 0 to 5 volt DC output signal. For example, a 3.50 volt input signal will produce a 3.50 volt DC
output signal.

PRODUCT SPECIFICATIONS
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 6
Version: 9.0
I0000585
WARRANTY
The AIM2 Series is covered by ACI’s Two (2) Year Limited Warranty, which is located in the front of ACI’S SENSORS &
TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com.
24 VAC (+/- 10%), 50/60 Hz
200 mA maximum
0-5V, 0-10V, 0-15V, 0-20V, 1-5V, 2-10V, 3-15V, 4-20V, 0-1V
0-20 mA, 4-20 mA, 0-1 mA
1 VDC (Minimum) to 20 VDC (Maximum)
From 0 to 20 VDC
4 mA (Minimum) to 20 mA (Maximum)
From 0 to 20 mA
9,500
250 +/-1%
0-5 VDC, 1-5 VDC, 0-10 VDC, 2-10 VDC
0-20 mA, 4-20 mA
1 VDC (Minimum) to 20 VDC +/- 1 VDC (Maximum)
From 0 to 10 VDC
0 mA (Minimum) to 20 mA (Maximum)
From 0 to 20 mA
5,000
500
+/- 3%
+/- 1%
45° Captive screw Terminal Blocks
12 (3.31 mm) to 22 AWG (0.33 mm)
0.5 Nm (Minimum); 0.6 Nm (Maximum)
35 to 120°F (1.7 to 48.9°C)
10 to 95% non-condensing
-20 to 150°F (-28.9 to 65.5°C)
NON-SPECIFIC INFORMATION
Supply Voltage:
Supply Current:
Input Voltage Signal Preset Ranges:
Input Current Signal Preset Ranges:
Input Signal Adjustable Voltage
Span:
Input Signal Adjustable Voltage
Offset:
Input Signal Adjustable Current
Span:
Current Offset:
Input Voltage Impedance:
Input Current Impedance:
Output Voltage Signal Preset
Ranges:
Output Current Signal Preset
Ranges:
Output Signal Adjustable Voltage
Span:
Output Signal Adjustable Voltage
Offset:
Output Signal Adjustable Current
Span:
Output Signal Adjustable Current
Offset:
Output Voltage Impedance:
Output Current Impedance:
Accuracy:
Linearity:
Connections:
Wire Size:
Terminal Block Torque Rating:
Operating Temperature Range:
Operating Humidity Range:
Storage Temperature:

NOTES
Page 7
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Version: 9.0
I0000585

Page 8
Automation Components, Inc.
2305 Pleasant View Road
Middleton, WI 53562
Phone: 1-888-967-5224
Website: workaci.com
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Version: 9.0
I0000585
This manual suits for next models
1
Table of contents
Other aci I/O System manuals
Popular I/O System manuals by other brands

National Instruments
National Instruments NI-9228 CALIBRATION PROCEDURE

M-system
M-system Devicenet R7F4DD-DA16A-C instruction manual

Creative
Creative CT4800 manual

audiopraise
audiopraise AVARICE user manual

Atop
Atop IO5202 Series Hardware installation guide

Gage
Gage CompuScope 85GC Hardware Manual and Driver Installation Guide