
7
DAMPERS ON STOVE PIPES
When burning coal, we recommend a Barometric Dra Damper be
installed at a safe convenient place between chimney and your furnace
preferably less than 3’ from the ue collar.
When you have installed the connector pipe between your furnace
and the chimney, tap the pipe hard with your ngernail. Remember
the sound it makes - it will be a “ting” echoing inside the stove pipe. If
later you tap and hear a mued thud, you are building up soot in the
pipe and should clean it. is pipe should be cleaned at least once or
twice during the heating season.
DO NOT CONNECT TWO HEATERS TO THE SAME CHIMNEY
FLUE. e National Fire Prevention Association recommends that wood
burning appliances vent into a separate ue from gas or oil furnaces. If
such an installation is contemplated, rst check with a local building
inspector to nd out if a separate ue for a wood burner is required.
Use of a Barometric Dra Control (when burning wood) is recommended
ONLY in the event your chimney creates excessive dra leading to an
over-ring condition.
HEATED AIR DISCHARGE
e furnace is designed for use as a supplemental heating source. When
used as a supplementary furnace, it is connected in conjunction with an
oil, gas, or electric furnace to the existing duct work which distributes
the heated air into several rooms and/or areas.
ough United States Stove Company expressly Does Not recommend
CONNECTING HOT AIR DUCT
TO FURNACE
when installed with existing oil or gas furnaces.
INSTALLATION EXAMPLES
INSTALLATION #1
With this installation, a back dra damper (optional) is inserted into
the heat run before the plenum of the existing furnace to prevent air
from the existing furnace to blow back into the furnace when it is not
in use. When a back damper is employed, it should be located as close
to the existing furnace plenum as practical.
IMPORTANT INFORMATION FOR ALL
CONNECTOR PIPES
e connector pipe must be constructed and installed so that it main-
tains clearances, keeps condensation and creosote within the pipe, and
is capable of withstanding a 2100°F degree chimney re.
1. e connector pipe should slant down toward the furnace a mini-
mum of 1/4” to the foot. At no time should the pipe turn downward
toward the chimney or run horizontal.
2. ere should be no more than two 90 degree elbows.
3. e connector pipe should never be longer than six feet. If it is
absolutely necessary to make a run of more than six feet (not
recommended) use extra support brackets every 3 feet.
4. e connector pipe should never be reduced to a smaller size than
ue opening on the furnace.
5. e connector pipe should not block the ue of the chimney or
extend into it in any way.
6. A good airtight thimble should be used to hold the connector pipe
in the chimney. It should be constructed so the connector pipe can
be removed for cleaning.
7. e connector pipe should not leave the heated portion of the
building to reach the chimney.
8. e connector pipe should not pass from one story to the next
before entering the chimney, nor should it pass through any closed
or enclosed space.
9. e connector pipe and any elbows must be of 24 gauge or greater.
10. e connector pipe should not be located near or in a walk way or
well traveled area.
11. All male ends of connector pipe should run or point towards the
furnace.
12. Install a cast iron adjustable damper in the rst joint of the con-
nector pipe, nearest to the ue collar.
the use of its furnaces to be installed and/or used as a free-standing
heater, it is possible to achieve a reasonably safe and functional instal-
lation IF certain standard procedures are followed. e following are
guidelines only and are intended to enable the furnace user to obtain
reasonable eciency from his furnace, and with due respect to safety
when installing as a “free-standing heater”. If installed correctly, and
in accordance with the instructions found in this manual, your warm
air furnace may be installed as a “space heater” within living quarters,
cabins, garage, or workshop. Please adhere to the following:
1. e use of a cold air return and/or lter box is mandatory. is will
not only increase your blower life and provide ltered air, it will
also help prevent the blower or blowers from “capturing” heated air
exiting from the top of the furnace heat outlets.
2. If installed as purchased , without directing the heat away from the
furnace itself, it will simply sit and cycle, turning the blowers o and
on. e thermostat may not function properly.
3. All larger furnaces (or those with multi-speed blowers) absolutely
require BACK PRESSURE to prevent premature motor winding
failure. If allowed to operate at high RPM (As in “FREE AIR” mode
- no duct work or ow restrictions) the windings overheat, insulation
melts and the motor simply burns up - not covered under warranty.
We strongly recommend that the hot air duct work be installed by a
home heating specialist. If doing the installation yourself, before you
decide which installation will best suit your needs, consult a qualied
heating technician and follow his recommendations as to the safest and
most ecient method of installation.
e following illustrations are the ONLY acceptable congurations