
required for high-gas-heat operation. When high-heat-only switch
SW-1 is on, it always causes high-gas-heat operation when R-W1
circuit is closed, regardless of the setting of the low-heat-only
switch SW-2 and regardless of whether R-W2 circuit is closed or
open.
When the wall thermostat ″calls for heat″, R-W/W1 circuit closes
for low-gas heat or R to W1-and-W2 circuits close for high-gas
heat. The furnace control performs a self check, verifies low-heat
and high-heat pressure switch contacts LPS and HPS are open, and
starts inducer motor IDM in low speed or high speed as appropri-
ate.
The start-up and shutdown functions and delays described in item
1 above apply to 2-stage heating mode as well, except for
switching from low- to high-gas heat and vice versa.
a. Switching from low- to high-gas heat—If thermostat
R-W/W1 circuit for low-gas heat is closed and R-W2
circuit for high-gas- heat closes, the control CPU switches
the inducer motor IDM speed from low to high. The
high-heat pressure switch relay HPSR closes. When in-
ducer motor IDM provides sufficient pressure to close
high-heat pressure switch HPS, the high-heat gas valve
solenoid GV is energized. The blower motor BLWM
switches speed for high-gas heat 5 sec after R-W2 circuit
closes.
b. Switching from high- to low-gas heat—If thermostat R-W2
circuit for high-gas heat opens and R to W/W1 circuit for
low-gas heat remains closed, the control CPU will switch
inducer motor IDM speed from high to low. The high-heat
pressure switch relay HPSR will open to de-energize
high-heat gas valve solenoid GV. When inducer motor
IDM reduces pressure sufficiently, the high-heat pressure
switch HPS will open. The low-heat gas valve solenoid GV
remains energized as long as low-heat pressure switch LPS
remains closed. The blower motor BLWM switches speed
for low-gas heat 5 sec after R-W2 circuit opens.
3. Cooling Mode
a. Single-Speed Cooling Outdoor Unit
(See Fig. 12 for thermostat connections.)
(1.) The thermostat closes R to G-and-Y circuits. The R-Y
circuit starts the outdoor unit, and R to G-and-Y
circuits start the furnace blower motor BLWM on
high-cool speed.
(2.) The EAC terminals EAC-1 and EAC-2 are energized
with 115v when blower motor BLWM is operating.
(3.) When thermostat is satisfied, the R to G-and-Y circuits
are opened. The outdoor unit stops, and furnace
blower motor BLWM continues operating on high-
cool speed for an additional 90 sec.
b. Two-Speed Cooling Outdoor Unit
(See Fig. 13 for thermostat connections.)
(1.) The thermostat closes R to G-and-Y1 circuits for low
cooling or closes R to G-and-Y1-and-Y/Y2 circuits for
high cooling. The R to Y1 circuits start the outdoor
unit on low-cooling speed, and the R-G circuit starts
furnace blower motor BLWM on low-cooling speed
(same speed as for low-gas heat). The R to Y1-and-Y2
circuits start the outdoor unit on high-cooling speed,
and the R to G-and-Y2 circuits start furnace blower
motor BLWM on high-cooling speed.
NOTE: Y1 is found in the outdoor unit. The furnace control CPU
controls blower motor BLWM speed by sensing only G for
low-cooling speed and Y/Y2 for high-cooling speed.
(2.) The EAC terminals EAC-1 and EAC-2 are energized
with 115v when blower motor BLWM is operating on
either cooling speed.
(3.) When thermostat is satisfied, the R to G-and-Y1 or R
to G-and-Y1-and-Y/Y2 circuits open. The outdoor
unit stops, and furnace blower continues operating on
cooling speed for an additional 90 sec.
4. Continuous Blower Mode
a. When R to G circuit is closed by thermostat, the blower
motor BLWM operates on low-gas heat speed (identical to
low-cool speed). Terminals EAC-1 and EAC-2 are ener-
gized with 115v as long as blower motor BLWM is
energized.
b. During a ″call for heat,″the blower motor BLWM stops
during ignitor warm-up (17 sec), ignition (7 sec), and
blower on delay (45 sec), allowing furnace heat exchangers
to heat up quickly.
c. The blower motor BLWM reverts to continuous blower
speed after the heating cycle is completed. In high-gas heat,
the furnace control CPU holds the blower motor BLWM at
high-gas-heat speed during the selected blower off delay
period before reverting to continuous blower speed.
(1.) When thermostat ″calls for low-cooling,″the blower
motor BLWM continues to operate on low-cool speed.
When thermostat is satisfied, the blower motor
BLWM continues on continuous blower speed.
(2.) When thermostat ″calls for high-cooling,″the blower
motor BLWM operates on high-cool speed. When the
thermostat is satisfied, the blower motor BLWM
operates an additional 2 sec on high-cool speed before
reverting back to continuous blower speed.
(3.) When R-G circuit is opened, the blower motor BLWM
continues operating for an additional 90 sec if no other
function requires blower motor BLWM operation.
5. Heat Pump Mode
NOTE: An accessory interface kit, Thermidistat control or Dual
Fuel thermostat are required with single-speed heat pumps. See
interface kit Installation Instructions for single-speed heat pump
thermostat and interface connections. No interface kit is needed for
2-speed heat pumps. See 2-speed heat pump Installation Instruc-
tions for thermostat connections.
a. Single-Speed Heat Pump Cooling
(1.) The thermostat and interface kit close the R to
G-and-Y/Y2 circuit to start the furnace blower motor
BLWM on high-cooling speed. The Y/Y2 input to the
furnace control is necessary to provide adequate cool-
ing airflow.
(2.) The EAC terminals EAC-1 and EAC-2 are energized
with 115v when the blower motor BLWM is operat-
ing.
(3.) When thermostat is satisfied, furnace blower motor
BLWM continues operating on high-cool speed for an
additional 90 sec.
b. Two-Speed Heat Pump Cooling
(1.) The thermostat R to G circuits start the furnace blower
motor BLWM on low-cool speed. The thermostat R to
G-and-Y/Y2 circuits start the furnace blower motor
BLWM on high-cool speed.
NOTE: The furnace control CPU controls blower motor BLWM
speed by sensing only G for low-cool speed and Y2 for high-cool
speed.
14
→