manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Carrier
  6. •
  7. Furnace
  8. •
  9. Carrier GAS FURNACE 58MTA Instructions and recipes

Carrier GAS FURNACE 58MTA Instructions and recipes

HEATING & COOLING
58MTA
Deluxe 4-Way Multipoise 2-Stage
Direct Vent Condensing Gas Furnace
Visit www.carrier.com
Installation, Start-up, and Operating Instructions
Sizes 060-120
NOTE: Read the entire instruction manual before starting the
installation.
This symbol + indicates a change since the last issue.
A93040
TABLE OF CONTENTS
SAFETY CONSIDERATIONS ..................................................... 2
INTRODUCTION .......................................................................... 2
CODES AND STANDARDS ........................................................ 3
Safety ......................................................................................... 3
General Installation ................................................................... 3
Combustion and Ventilation Air .............................................. 3
Duct Systems ............................................................................ 3
Acoustical Lining and Fibrous Glass Duct .............................. 3
Gas Piping and Gas Pipe Pressure Testing .............................. 3
Electrical Connections .............................................................. 5
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS ........ 5
APPLICATIONS ............................................................................ 6
General ...................................................................................... 6
Upflow Applications ................................................................. 6
Condensate Trap Location (Factury-Shipped
Orientation) .......................................................................... 6
Condensate Trap Tubing fEactory-Shipped
Orientation) .......................................................................... 6
Condensate Trap Location tAlternate Upflow
Orientation/ .......................................................................... 7
Condensate Trap Tubing (Alternate Upflow Orientation/.7
Condensate Trap Field Drain Attachment .......................... 8
Pressure Switch Tubing ....................................................... g
Upper. Collector Box and Inducer Housing (Unused)
Drain Connections ............................................................... 8
Condensate Trap Freeze Protection .................................... 8
Downflow Applications ............................................................ 8
Condensate Trap Location .................................................. 8
Condensate Trap Tubing ..................................................... 8
Condensate Trap Field Drain Attachment .......................... 9
Pressure Switch Tubing ....................................................... 9
Condensate Trap Freeze Protection .................................... 9
Horizontal Left (Supply-Air Discharge) Applications ............ 9
Condensate Trap Location .................................................. 9
Condensate Trap Tubing ................................................... 10
Condensate Trap Field Drain Attachments ...................... 10
Pressure Switch Tubing ..................................................... l0
Condensate Trap Freeze Protection .................................. I1
Constrnct a Working Platform .......................................... 11
Horizontal Right (Supply-Air Discharge) Applications ........ 1I
Condensate Trap Location ................................................ I 1
Condensate Trap Tubing ................................................... I 1
Condensate Trap Field Drain Attachment ........................ 12
Pressure Switch Tubing ..................................................... 12
Condensate Trap Freeze Protection .................................. 12
Construct a Working Platform .......................................... 12
LOCATION .................................................................................. 13
General .................................................................................... 13
Furnace Location Relative to Cooling
Equipment ............................................................................... 13
Hazardous Locations ............................................................... 14
INSTALLATION ......................................................................... 14
Leveling Legs (If Desired) ..................................................... 14
Installation in Upflow and Downflow
Applications ............................................................................ 14
Installation in Horizontal Applications .................................. 16
Air Ducts ................................................................................. 16
General Requirements ....................................................... 16
Ductwork Acoustical Treatment ....................................... 16
Supply Air Connections .................................................... 16
Return Air Connections ..................................................... t6
Filter Arrangement .................................................................. 17
Bottom Closure Panel ............................................................. 18
Gas Piping ............................................................................... 18
Electrical Connections ............................................................ 19
115-V Wiring ..................................................................... 19
24-V Wiring ....................................................................... 2l
Accessories ........................................................................ 21
Direct Venting ......................................................................... 23
Remov,'d of Existing Furnaces from Common Vent
Systems .............................................................................. 23
Combustion-Air and Vent Piping ..................................... 24
Concentric Vent and Combustion-Air Ternlination
Kit Installation ................................................................... 28
Multiventing and Vent Terminations ................................ 32
Condensate Drain .................................................................... 32
General ............................................................................... 33
Application ......................................................................... 33
Condensation Drain Protection ......................................... 34
START-UP ADJUSTMENT AND SAFETY CHECK .............. 34
General .................................................................................... 34
Sequence of Operation ............................................................ 35
Two-Stage Heating With Single-Stage Thermostat
(Adaptive Model ................................................................ 35
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 101 Catalog No. 535-80042 Printed in U.S.A. Form 58MTA-3SI Pg 1 7-02 Replaces: 58MTA-1SI
Two-Stage Heating With Two-Stage Thermostat
(Non-Adaptive Heating Model ......................................... 36
Cooling Mode .................................................................... 36
Thermidistat Mode ............................................................ 39
Continuous Blower Mode ................................................. 39
Heat Pump ......................................................................... 40
Start-Up Procedures ................................................................ 40
Purge G_L_ Lines ................................................................ 40
Component Self-Test ......................................................... 40
Prime Condensate Trap With Water ................................. 40
Operate Furnace ................................................................. 41
Furnace Restart .................................................................. 4 I
Adjustments ............................................................................. 4 I
Set Gas Input Rate ............................................................ 41
Set Temperature Rise ........................................................ 45
Adjust Blower Off Delay (Heat Mode) ............................ 46
Set Thermostat Heat Anticipator ...................................... 46
Check Safety Controls ............................................................ 47
Checklist .................................................................................. 47
RATING
CERTIFIED
REGISTERED QUALITY SYSTEM
SAFETY CONSIDERATIONS
Application of this furnace should be indoors with special
attention given to vent sizing and material, gas input rate, air
temperature rise, unit leveling, and unit sizing. Improper
installation or misapplication of furnace can require excessive
servicing or cause premature component failure.
Improper installation, adjustment, alteration, service, mainte-
nance, or use can cause carbon monoxide poisoning, explo-
sion. fire. electrical shock, or other conditions which may
cause personal injury or property damage. Consult a qualified
installer, service agency, local gas supplier, or your distribu
tot or branch for information or :Lssistance. The qualified
installer or agency must use only factory-authorized and
listed kits or accessories when modifying this product. Failure
to follow this warning could result in electrical shock, fire.
personal injury, or death.
Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations must
be performed by trained service personnel. When working on
2
heating equipment, observe precautions in literature, on tags, and
on labels atlached to or shipped with unit and other safety
precautions that may apply.
These instructions cover the minimum requirements and conform
to existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances,
especially those that may not have kept up with changing residen
tial constt_ction practices. We require these instructions xs a
minimum for a safe installation.
We,u- safety glasses and work glo_es.
--9
Have a fire extinguisher available during start-up and adjustment
procedures and service calls.
Recognize safety information, This is the safety-alert symbol z_,
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand these signal words: DANGER, WARNING, CAU-
TION, and NOTE. These words are used with the safety-alert
symbol. DANGER identifies the moat serious hazards which will
result in severe personal injuD" or death. WARNING sigltifies
hazards which could result in personal injury or death. CAUTION
is used to identify unsafe practices which would result in minor
personal injury or product and property" damage. NOTE is used to
highlight suggestions which will result in enhanced installation,
reliability, or operation.
AIRFLOW
-CY
AIRFLOW
AIRFLOW
A93041
Fig. 1--Multipoise Orientations
INTRODUCTION
The model 58MTA, 2-Stage, 4-way multipoise, Gas-Fired, Cat
egory IV, direct vent condensing furnace is available in model
sizes ranging in high-stage gas input rates of 60,000 to 120.000
Btuh. This furnace is C.S.A. design-certified for natural and
propane gases (see furnace rating plate) and for installation in
alcoves, attics, basements, closets, utility rooms, crawlspaces, and
garages. This furnace is factory-shipped for use with natural gas. A
C.S.A. listed gas conversion kit is required to convert furnace for
use with propane gas.
This furnace shall not be installed directly on ca_eting, tile, or
any other combustible material other than wood flooring. FOC
downflowinstallations,afactoryaccessoryfloorbasemustbe
usedwheninstalledoncombustiblematerialsandwoodflooring.
Specialbaseisnotrequiredwhenthisfurnaceisthstalledonthe
mmmthcturer'scoilassemblyorwhenthemanufacturer'scoilbox
isused.Thedesignofthe5gMTAfurnaceisnotC.S.A,(A.G.A.
andC.G.A.)certifiedforinstallationinmobilehomes,recreational
vehicles,oroutdoors.This furnace is suitable for installation in a
structure built on site or a manufactured budding completed at
final site.
1. Combustion products must be discharged outdoors, Connect
this furnace to an approved vent system only, ,'tqspecified in
the "Venting" section of these instructions
2. Never test for gas leaks with an open flame. Use a commer-
cially available soap solution made specifically for the detec-
tion of leaks to check all connections, as specified in the "Gas
Piping" and "Stari-Up, Adjustment, and Safety Cbeck" sec-
tion.
3. Always install furnace to operate within the furnace's intended
temperature-tise range with a duct system which has an
external static pressure within the allowable range, as speci-
fied in the "Adjustments" section. See furnace rating plate.
4. When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space containing
the furnace, the return air shall also be handled by duct(s)
sealed to the furnace casing and terminating outside the space
containing the furnace.
5. Agas-fired furnace for installation in a residential garage must
be installed as specified in the warning box in the "'Location"
section.
6. The furnace is not to be used for temporary heating of
buildings or structures under construction.
This furnace is designed lk,r continuous return-air minimum
temperature of 60 °F db or intermittent operation down to 55°F db.
Return-air temperature must not exceed 85°F db, See Fig. 4.
This furnace is shipped with the drain and pressure tubes con-
nected for UPFLOW applications. Minor modifications are re-
quired when used in DOWNFLOW, HORIZONTAL RIGHT,
or HORIZONTAL LEFT Isupply-air discharge direction) appli-
cations as shown in Fig. 1. See details in Applications section.
This furnace must be installed with a direct-vent (combustion air
and flue) system and a factory accessory termination kit. In a
direct-vent system, all air for combustion is taken directly from the
outdoor atmosphere and all flue gases are discharged to the
outdoor atmosphere. See furnace and factor,,' accessory vent-air
intake termination kit instructions for proper installation.
This furnace is shipped with the following materials to a,_sist in
proper furnace installation. These materials are shipped in the main
blower compartment.
Installer Packet includes:
Installation, Startup, and Operating Instructions
Service and Maintenance Instructions
User's Information Manual
Warranty Certificate
Loose Parts Bag includes: Quantit
Pressure tube extension 1
Collector Box or condensate trap extension tube t
Inducer housing drain tube 1
l/2qn CPVC street elbow 2
Drain tube coupling 1
Drain tube coupling grommet 1
Vent and combustion-air intake pipe support 2
Condensate trap hole filler plug 3
Vent and combustion-air intake hole filler plug 2
Cornbustioo-air intake pipe podorated disk assembly 1
Vent Pipe Extension 1"
• ONLY supplied with some furnaces.
For accesso_, installation detail, refer to the accessory, installation
instruction.
NOT[:: Remove all shipping materials before operating furnace.
CODES AND STANDARDS
Follow all national and local codes and standards in addition to
these instructions. The installation must comply with regulations
of the serving g_s supplier, local building, heating, plumbing, and
other codes. In absence of local codes, the installation must
comply with the national codes listed below and ,all authorities
having jurisdiction,
In the United States and Canada, follow all codes and standards for
the following:
Step 1--Safety
US: National Fuel Gas Code (NFGC) NFPA 54-1999/ANSI
Z223.1-1999 and the Installation Standards, Warm Air Heating
and Air Conditioning Systems ANSI/NFPA 90B
• CANADA: CSA B149.1-00 National Standard of Canada,
Natural Gas and Propane Installation Code (NSCNGP1C)
Step 2--General Installation
US: current edition of the NFGC and the NFPA 90B. For
copies, contact the National Fire Protection Association Inc.,
Battery, march Park, Quincy, MA 02269: or for only the NFGC
contact the American Gag Association, 400 N. Capitol., N.W.,
Washington DC 20001
• CANADA: NSCNGPIC. For a copy. contact Standard Sales,
CSA International, 178 Rexdale Boulevard. Etobicoke (Tor-
ontoh Ontario, M9W IR3, Canada.
Step 3---Combustion and Ventilation Air
•US: Section 5.3 of the NFGC. Air for Combustion and
Ventilation
• CANADA: part 7 of the NSCNGPIC. Venting Systems and Air
Supply for Appliances
Step 4--Duct Systems
US and CANADA: Air Conditioning Contractors Association
IACCA! Manual D, Sheet Metal and Air Conditioning Con-
tractors National Association (SMACNA), or American Soci
ety of Heating, Refrigeration, and Air Conditioning Engineers
(ASHRAEI 2001 Fundamentals Handbook Chapter 34.
Step 5---Acoustical Lining and Fibrous Glass Duct
US and CANADA: current edition of SMACNA, NFPA 90B as
tested by UL Standard 181 for Class 1 Rigid Air Ducts
Step 6--Gas Piping and Gas Pipe Pressure Testing
• US: NFGC; chapters 2, 3.4, and 9 and national plumbing codes
• CANADA: NSCNGPIC Parts 3.4, 5, A. B, E, G, and H.
2-IN. COMBUSTION-
2-IN. VENT SONN
_-IN. DIA THERMOSTAT
ENTRY
!7 ............. *q_
T
14 _ SIDE INLET
TYP
T
I"-D- 23 'a'TYP
SIDE INLET
_'_ 26 _,w TYP
f ONDENSATE DRAIN
TRAP LOCATION
(DOWNFLOW &
HORIZONTAL LEFT)
F hqN DIA
POWER CONN
ACCESSORY
POWER ENTRY
i"-_'-'- CO ND EN SAT E l
DRAIN TRAP
LOCATION
(ALTERNATE 4
UPFLOW)
TYP
CONDENSATE
DRAIN LOCATION
(UPFLOW)
AIRFLOW
TYR
_NLET
tI,i_, 41= _ E ...._.._p
TYP
L
CONDENSATE DRAIN
TRAP LOCATION _
(DOWNFLOW &
Hon{ZONTAL RIGHT) _
OR ALTERNATE
!_-IN, DIA GAS CONN
1
_28_ _1
_26 t_t_ "r--
26 _/_r
22 S'I_¸¸ I_
19_ "_-- I_ ¸
--+ _2-1N CONMNBUSTION- -_-
AIR CO s_la,,
_'-"_ _"zIN DIA
THERMOSTAT ENTRY
,f2-1N VENT CONN
I S_DE INLET
i
397_
_E**+_............ A+
J_I 24 '1' _ _ '1' rr
DIMPLE LOCATORS BOTTOM INLET
FOR HORIZONTAL
HANGING
NOTES: 1. Minimum return-air openings at furnace, based on metal duct. If flex duct is used,
see flex duct manufacturer's recommendations for equivalent diameters.
2. Minimum return-air opening at furnace:
a. For 800 CFM-16-in. round or 14'/_x 12-in. rectangle.
b. For 1200 CFM-20-in, round or 14'/= x 19'/_-in. rectangle.
c. For 1600 CFM-22-in, round or 14% x 23%-in. rectangle,
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data
literature for specific use of single side inlets. The use of both side inlets, a
combination of 1 side and the botlom, or the bottom only will ensure adequate
return air openings for airflow requirements above 1800 CFM at 0.5" W.C. ESP.
UNIT SIZE D E
060-12 15-7/8 16
080-12 15-7/8 16
080-16 15-7/0 16
100-16 19-3/8 19-1/2
100-20 19-3/8 19-1/2
120-20 22-7/8 23
DIMENSIONS (IN,)
A
17-1/2
17-1/2
17-1/2
21
21
24-1/2
Fig. 2--Dimensional Drawing
A02149
INSTALLATION
_sforcedalrfum_c_iseqlJippedfor_w_lna_at;_ltltudes0-10,030ff(0 3,(T_Ont,ex_140sizeFumaces_eo_app_edforaYdbJdeS0 7,000_t(0-2.135m)
_accesso__suppled_ _emz_acturef,sh_beusedtoo0_ to0nX_aneg_ useormay_ _ _ _ _ _ _ .
*i_,sfurnace is forindo_ inst_la_Xl m a I_ildng cons_uctedon site. 1_=s_mac_ rn_y_ _ _ a_(_l_) _ _ _ _ r_ _e _ _ _
au61cr_edk&
_lLsfunitemaybeinsl_le3oncorrl>Jsa_efloodngin_o3_eorct_setalrd_mum_rance fromc_ _
3_isap_iancerequ_esaspeoalv_r_ systemRefertotheinsta_at_ninstnJc_3nsloq_ls listandrrelt_dofinst_ _ _ __ _ _ _ _, _
CP_, or A_pipe._mdst n0(13e,_nledincomrno_wil_o_e_as-flred_oplia_x_5. C_oughwttchv_r __ _24i_
(_O0r//n), nirirnum 3/4 i_c_ (19 ram)It,_ (inditing roo_g _).
Cette foun_se _ _r Dul_ e_t _F_oee pour_l_a_ avec _az nab_el elalludes _ _e 0 3,050m
((3-10,000p_).exc_pt_ c_ f_ d_ 140t_Jle so_tp_J" a_ oomp_ _02.13r_n(0 -7.000 p)
U_liSe:_ne tn_Jssede cor_er_on _un_e pa_le P_, 9our pa_:_r au g_z 10ropal_OUpourcertal_ _ _ _ _d.
Cede fourna_ea a_ p_s$ e_tpou_ins_la_ &I_nt_neu_d,3nsunt_rnent cor_ _Zl_. _ _ _ _ _ _ _ i_ _ _ n_ _
(m_son m0t_le)_i_e_cnt p_"la 13_ 9gnal_t_ et s_I_utd_ une trousses_c_ _ _ _
Cette _n_,se peut Otre _lee surunplan:t_ _e d_s uqer_ =._ ou unI_ac_d en obsen'ant les d_ga_ _p_ _ _ _.
Cotapp_e_l rV_c_e un s'yst_ d _wacu_on speo_. La _d_st_la_on etI_ li_e OesI_CeS _ _ _ _ _ d_e _ _
sd_liseravecbvJvaute_e_snon_mc_tures4OPVC, PVC-Dv_CPVC, ou _et _enepeut pas_e'even_l_econj_r_nent a_ecd'au0_esappa_etsb_z. Em_=_=urdela
O0_ au b-aveesde laque_e il est 13ec=_oleda _re passer los luyal_ d a_ra_on (adrrissloW_): 24 _ (_ _) _ _4 _ (19_) _ (y _ _ t_e).
FO_up_oN and do_ applications, fu_ must be instaJ_=dleve_ or i_ched ',_thn 1_
of level FOr a hor_ 8Dplica_on, the flJ_ nlu_ be pltch_ rclr_rnum 1/4"to
ma_mum of 112"forv_ for 17:operdrainage. See Ir_lafa_n Manual for IMI_RTANT urlt
suppo:tdstals_n_al ap_on_
Pour des ;_oplic_honsde flL_ ascendant _ d_ce_a_t, la f_um_se d_t _tre ir_tall_ _
nive_u o_ in:tir_e a I_ plus de 1/2" du nlv_ Pour une _of_iG_tJ(_ honz(_ltate, ta
fcorna_ dot_treinc_r'eeervrer_ran_m1/4"etrn_ornum1/'Z'cIJrw_aJ0_r teciranage
&Encasdin_tall_nen "on_onzo_de,oo_ulterlesnE_rr_nts
la_3_ANTS surle _cons e_rna_ dinst_la_on.
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
ALL pO_I'I1ONS:
_t _,lnimumflontclearancef_-serv,,ce30inches(762mm).
1_)Nzefurnacesrequre1inchbackdeetancetocontJustiUerr_e_ais
As_t:_y,Part NO.CD5c_CKS,_ C_ICasing,PadNo,KCAKC.
Linecc_tact _pen'tis_iNe onty I_ lines fc_n'_d by intefs_<;ns of top and t_.o s_:_esof furnac_
§ _earancesho_nisf_r_ir_et and_r o_e_end_
DEGAGEMENTMINIMUMENPOUCESAVECELEMENTSDECONSTRUCTIONCOMBUSTIBLES
POUR TOIJS LES POSITIONS:
_t [_g_m'_ a'_"tmr"raur_de7mmmI_0P°)linerre_r_Jm"
Fr_H_s fo_ de t40 taille. I po (25ram) de_age_T_nt des rmd_ _e6t requ_
LA9o_moNCQURA_TDE_CENOANT:
F_rli_taflatio_s_le combu_il_es4_ulementonutiliselabase "1 e,l:_ce
noK_L_OIALL _eserpefllir_ pie_en °_CKS,_ulecarter_n, piece
noKCAKC
POURLAPOSfllONHORIZONTALE:
Le cc_tact n'e_t _ent re les lignesfomt_ par les intemec1_onsdu desks et des d_es de la
<3_s_ _ I__i_e, _ d_ _iw_, desrnor_ <_delaCf_te duI_ment.
La _stance indquee co_ceme I'ext_wt e du d'ardvee d'air etr e_h_Tite du tuyau de sodie d'_r.
Pourlosfc_na_s de120el140lalle,1po(l_) degagerne_desmatena_o0rd0us_t_estrec@s
_, 324999-201 REV.D {LITTOP)
L_VEL (0") ,, MIN 114"
TO TO
1/2" MA _ ! i ,q
_RONT I r --
UPFLOWOR _"_ FFRONT _[
11 _ HORIZONTAL
DOWNFLOW L_
_lls lumace is aporoved for UPR_OW, DOVe, FLOWaed
C_te foun_se e_ al_oev_e pc_ 1ins_la_n HOFI;_ONTALE
ena circui_f!_ d air V_ LE HAUT etVERS LEBAS.
JA02148
--) Fig. 3_Clearances to Combustibles
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE
"_ _ MAX 851=
>_
FRONT
RETURN
AIR MIN 55°F
A93042
Fig. 4_Return-Air Temperature
Step 7--Electrical Connections
•US: National Electrical Code (NEC) ANSI/NFPA 70-2002
•CANADA: Canadian Electrical Code CSA C22.1
Use this procedure for ,all installed ,and aninstalled furnaces. An
ESD service kit _available from commercial sources) may be used
to prevent ESD damage.
Electrostatic discharge can affect electronic components.
Follow the Electronic Discharge Precautions Procedure listed
below during furnace inLstallation and servicing to protect the
furnace electronic control. Precautions will prevent electro-
static discharges from personnel and hand tools which are
held during the procedure. These precautions will help to
avoid exposing the control to electrostatic discharge by
putting the furnace, the control and the person at the same
electrostatic potential.
I. Disconnect all power to the furnace. Multiple disconnects may
be required, DO NOT TOUCH THE CONTROL OR ANY
WIRE CONNECTED TO THE CONTROL PRIOR TO DIS-
CHARGING YOUR BODY'S ELECTROSTATIC CHARGE
TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the furnace
chassis which is close to the control. Tools held in hand during
grounding will be discharged.
FBLOWERSHELF FURNACE
_[_ _)R FCONDENSATE
CONDENSATE TRAP
f--TRAP (INSIDE FURNACE
SIDE
FIELD 26¼ t'/2
DRAIN
LALTERNATEDRAIN CONN
TUBE LOCATION
CONDENSATETRAP _ SIDE VIEW FRONT VIEW
DRAINTUBE LOCATION DOWNFLOW AND ALTERNATE
UPFLOW APPLICATIONS EXTERNAL UPFLOW APPLICATIONS
FURNACE
OOO_ _ FURNACE
SIDE
4
_../ 26 ¼ ¾
FIELD
DRAIN
CONN
END VIEW FRONT VIEW
HORIZONTAL
APPLICATIONS
SLOT O 2gN%7
APPLICATION
(OPTIONAL)
(WHEN USED)
FRONT VIEW
1/40D
COLLECTOR BOX TO
TRAP RELIEF PORT
I_OD
INDUCER HOUSING
"'L_.- DRAIN CONNECTION
s/aO D
iCOLLECTOR BOX
' DRAIN CONNECTION
SCREW HOLE FOR
_ UPFLOW OR DOWN-
'FLOW APPLICATIONS
(OPTIONAL)
21/4 _ _ _/_IN. PVC OR CPVC
SIDE VIEW
Fig. 5_Condensate Trap
A93026
3. You may proceed to service the control or connecting wires as
long as you do nothing to recharge your body (moving or
shuffling feet, touching ungrounded objects, etc./.
4. If you touch ungrounded objects, firmly touch a clean,
unpainted metal surface again before touching control or
wires.
5. Before removing a new control I?om its container, discharge
your body's charge to ground. If the control is to be installed
in a furnace, follow items 1 through 4 before bringing the
control or yourself in contact with the furnace. Put all used and
new controls into containers before touching ungrounded
objects.
APPLICATIONS
Step l_General
Some assembly and modifications are required for furnaces
installed in any of the 4 applications shown in Fig. 1. All drain and
pressure rubes are connected as shown in Fig. 6. See appropriate
application instructions for these procedures.
Step 2--Upflow Applications
In an upflow application, the blower is located below the burner
section, and conditioned air is discharged upwards.
CONDENSATE TRAP LOCATION (FACTORY-SHIPPED
ORIENTATION)
The condensate trap is factory installed in the blower shelf and
factory connected for UPFLOW applications. A factory-supplied
tube is used to extend the condensate trap drain connection to the
desired furnace side for field drain attachment. See Condensate
Trap Tubing (Factory-Shipped Orientation) section for drain tube
extension details. (See Fig. 5.)
CONDENSATE TRAP TUBING (FACTORY-SHIPPED
ORIENTATION)
NOTE: See Fig. 6 or tube routing label on main furnace door to
confirm location of these tubes.
1. Collector Box Drain, Inducer Housing Drain, Relief Port, and
Pressure Switch Tubes
These tubes should be factory attached to condensate trap and
pressure switch ready for use in upflow applications. These
tubes can be identified by their connection location and ,also
by a color label on each tube. These tubes _e identified as
follows: collector box drain tube (blue label Linducer housing
drain tube (violet label or moldedL relief port robe (green
label), and pressure switch tube (pink label).
2. Condensate Trap Drain Tube
The condensate trap drain connection must be extended for
field attachment by doing the following:
a. Determine location of field drain connection. (See Fig. 2 or
6.)
NOTE: If iaternal filter or side Filter/Media Cabinet is used, drain
tube should be located to opposite side of casing of return duct
attachment to assist in filter removal.
6
O /
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX --'_
TUBE (PINK)
TUBE (GREEN)
(MOLDED) DRAIN
TUBE (BEHIND
COLLECTOR BOX
DRAIN TUBE)
DRAIN TUBE (BLUE)
DRAIN TUBE (BLUE
& WHITE STRIPED)
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
DRAIN TUBE (BLUE)
TRAP
FACTORY-SUPPLIED
DRAIN TUBE
COUPLING (LEFT
DRAIN OPTION)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
FIELD-INSTALLED
FACTORY-SUPPLIED
lf2qN. CPVC STREET
ELBOWS (2) FOR
LEFT DRAIN OPTION
FIELD-INSTALLE[
FACTORY-SUPPLIED
DRAIN TUBE
COUPLING (RIGHT
BRAIN OPTION) A01030
Fig. 6--Factory-Shipped Upflow Tube
Configuration
(Shown with Blower Access Panel Removed)
b. Remove and discard casing drain hole plug button from
desired side.
c. Install drain tube coupling grommet (factory-supplied in
loose parts bag) in selected casing hole.
d. Slide drain tube coupling (factory-supplied in loose parts
bag) through _ommet ensuring long end of coupling faces
blower.
e. Cement 2 factory-supplied l/2-in, street CPVC elbows to
the rigid drain tube connection on the condensate trap. (See
Fig. 6.) These elbows must be cemented together and
cemented to condensate trap drain connection.
NOTE: Failure to use CPVC elbows may allow drain to kink and
prevent draining.
f. Connect larger diameter drain tube and clamp (factory-
supplied in loose parts bag) to condensate trap and clamp
securely.
g. Route tube to coupling and cut to appropriate length.
h. Attach tube to coupling and clamp securely.
CONDENSATE TRAP LOCATION (ALTERNATE UPFLOW
ORIENTATION)
An alternate location for the condensate trap is the left-hand side
of casing. (See Fig, 2 and 7.)
HOUSING
DRAIN TUBE
(VIOLET)
7
Fig. 7--Alternate Upflow Configuration and Trap
Location
NOTE: If the alternate left-hand side of casing location is used,
the factory-connected drain and relief port tubes must be discon-
nected and modified for attachment. See Condensate Trap Tubing
/Ahernate Upflow Orientation) section for tubing attachment. To
relocate condensate trap to the left-hand side. perform the follow-
ing:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward
and rotating trap.
3, Install casing hole filler cap (factory-supplied in loose parts
bag) into blower shelf hole where trap was removed.
4, Install condensate trap into left-hand side casing hole by
inserting tube connection stubs through casing hole and
rotating undl tabs snap into locking position.
5, Fill unused condensate trap casing holes with plastic filler
caps (factory-supplied in loose parts bag).
CONDENSATE TRAP TUBING (ALTERNATE UPFLOW ORI
ENTATION)
NOTE: See Fig. 7 or tube routing label on main furnace door to
confirm location of these tubes.
I, Collector Box Drain Tube
Connect collector box drain tube (blue label) to condensate
trap.
NOTE: On 17-1/2 in. wide furnaces ONLY. cut tube between
corrugated sections to prevent kinks from occmring.
2. Inducer Housing Drain Tube
a. Remove and discard LOWER (molded) inducer housing
drain tube which wa._ previously connected to condensate
trap.
b.Useinducerhousingdrainextensiontube (violet label and
factory'-supplied in loose parts bagl to connect LOWER
inducer housing drain connection to the condensate trap.
c. Determine appropriate length, cut, and connect tube.
d. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube
a. Connect relief port tube (_een label) to condensate trap.
b. Extend this tube (if required) by splicing to small diameter
tube (factory-supplied in loose parts bag).
c. Determine appropriate length, cut, and connect tube.
CONDENSATE TRAP FIELD DRAIN ATTACHMENT
Refer to Condensate Drain section for recommendations and
procedures.
PRESSURE SWITCH TUBING
The LOWER collector box pressure tube /piak label) is factory,
connected to the High Pressure Switch and should not require any
modification.
NOTE: See Fig. 6 or 7 or tube routing label on main furnace door
to check for proper connections.
UPPER COLLECTOR BOX AND INDUCER HOUSING (UN
USED) DRAIN CONNECTIONS
1. Upper collector box drain connection
Attached to the UPPER collector box drain connection is a
factory-installed corrugated, plugged tube (blue and white
striped label). This tube is plugged to prevent condensate
leakage in this application. Ensure this tube is plugged.
NOTE: See Fig. 6 or 7 or tube routing label on main furnace door
to check for proper connections.
2. Upper inducer housing drain connection
Attached to the UPPER (unused) inducer housing drain
connection is a cap and clamp. This cap is used to prevent
condensate leakage in this application. Ensure this connection
is capped.
NOTE:: See Fig. 6 or 7or tube routing label on main furnace door
to check for proper connections.
CONDENSATE TRAP FREEZE PROTECTION
Refer to Condensate Drain Protection section for recommenda-
tions and procedures.
Step 3_Downflow Applications
In a downflow furnace application, the blower is located above the
burner section, and conditioned air is discharged downwards.
CONDENSATE TRAP LOCATION
The condensate trap must be removed from the factory-installed
blower shelf location and relocated in selected application location
as shown in Fig. 2, 8, or 9.
To relocate condensate trap from the blower shelf to desil_d
location, perform the following:
l. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inw,'u-d
and rotating trap.
3. Remove casing hole filler cap from casing hole./See Fig. 2, 8,
or 9.)
4. Install casing hole filler cap into blower shelf hole where trap
was removed.
5. Install condensate trap into desired casing hole by inserting
tube connection stubs through casing hole and rotating until
tabs snap into locking position.
DRAIN TUBE (BLUE)
TUBE (GREEN)
COLLECTOR BOX -_.
EXTENSION TUBE
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX-_,
EXTENSION TUBE
TRAP ©
INDUCER HOUSING-
DRAIN TUBE (VIOLET)
Fig. 8---Downflow Tube Configuration
(Left-Hand Trap Installation)
©©
©
A01023
_" PLUG
F CAP
COLLECTOR BOX
F DRAIN TUBE (BLUE)
COLLECTORBOX
f TUBE(PINK)
COLLECTORBOX
TUBE(GREEN)
COLLECTORBOX
EXTENSIONTUBE
-- COLLECTORBOX
DRAINTUBE (BLUE
&WHITESTRIPED)
"_ COLLECTORBOX
EXTENSIONTUBE
INDUCERHOUSING
DRAINTUBE
_ _VIR(_LET)
.F O ENSATE
_'_"-- COLLECTOR BOX
EXTENSION
DRAINTUBE
A01024
Fig. 9_Downflow Tube Configuration
(Right-Hand Trap Installation)
CONDENSATE TRAP TUBING
NOTE: See Fig. 8 or 9 or tube routing label on main furnace door
to check tbr proper connections.
Relocaterobesasdescribedbelow.
1.CollectorBoxDrainTube
a.Removefactory-installedplugfromLOWER collector box
drain tube tblue and white striped label).
b. Install rentoved cl,-mlp and plug into UPPER collector box
drain tube (blue labell which wa_ connected 1o condensate
trap.
c. Connect LOWER collector box drain connection to con-
densate trap.
(I.) Condensate Trap Located on Left Side of Casing
(a3 Connect LOWER collector box drain tube !blue
and white striped label! to condensate trap. Tube
does not need to be cut.
(b.) Clamp tube to prevent any condensate leakage.
(2.) Condensate Trap Located on Right Side of Casing
(a.! Install drain robe coupling (factory-supplied in
loose parts bag) into collector box drain tube
Iblue and white striped label) which was previ-
ously plugged.
(b.) Connect larger diameter drain tube Ifactory-
supplied in loose parts bag! to drain tube cou-
pling, extending collector box drain tube tbr
connection to condensate trap.
(c.) Route extended collector box drain tube directly
from collector box drain to condensate trap as
shown in Fig. 9.
(d.) Determine appropriate length and cut.
(e.) Connect to condensate trap.
(f.) Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube
a. Remove factory-installed cap ,and champ from LOWER
inducer housing drain connection.
b. Remove and discard UPPER (molded) inducer housing
drain tube which was previously connected to condensate
trap.
c. Install cap and clamp on UPPER inducer housing drain
connection where molded drain tube was removed.
d. Use inducer housing drain tube (violet label and factory.-
supplied in loose parts bag) to connect LOWER inducer
housing drain connection to the condensate trap.
e. Connect inducer housing drain connection to condensate
trap.
(13 Condensate Trap Located on Left Side of Casing
(a.) Determine appropriate length and cut.
lb.) Connect tube to condensate trap.
(c.I Clan_p tube to prevent any condensate leakage.
(2.) Condensate Trap Located on Right Side of Casing
{a.I Route inducer housing drain tube (violet label)
directly from inducer housing to condensate trap
as shown in Fig. 9.
lb.) Determine appropriate length and cut.
(c.) Connect tube to condensate trap.
(d./ Clamp tube to prevent any condensate leakage.
3. Relief Port Tube
Refer to Pressure Switch Tubing section for connection
procedure.
CONDENSATE TRAP FIELD DRAIN ATTACHMENT
Refer to Condensate Drain section for recommendations and
procedures.
PRESSURE SWITCH TUBING
One collector box pressure tube {pink label) is factory connected to
the High Pressure Switch for use when furnace is installed in
upflow applications. This tube MUST be disconnected and used
for the condensate trap relief port tube. The other collector box
pressure tube (green labell which was factory connected to the
condensate trap relief port connection MUST be connected to the
High Pressure Switch in DOWNFLOW or HORIZONTAL
RIGHT applications
NOTE: See Fig. 8 or qor tube routing label on main furnace door
to check for proper connections.
I. Disconnect collector box pressure tube (pink label) attached to
High Pressure Switch.
2. Extend collector box pressure tube (_m'een label) which was
previously connected to condensate trap relief port connection
by splicing to small diameter tube (factory-supplied in loose
paa_s bag).
3. Connect collector box pressure tube (green label) to High
Pressure Switch connection labeled COLLECTOR BOX.
4. Extend collector box pressure tube (pink label) which was
previously connected to High Pressure Switch by splicing to
remaining small diameter tube (factory-supplied in loose parts
bag).
5. Route this extended tube (pink label) to condensate trap relief
port connection.
6. Determine appropriate length, cut, and connect tube.
7. Clamp tube to relief port connection.
CONDENSATE TRAP FREEZE PROTECTION
Refer to Condensatu Drain Protection section for recommenda-
tions and procedures.
Step 4_Horizontal Left (Supply-Air Discharge)
Applications
In a horizontal left furnace application, the blower is located to the
right of the burner section, and conditioned air is discharged to the
left.
NOTE: In Canada, installations shall be in accordance with
current NSCNGPIC and/or local codes.
CONDENSATE TRAP LOCATION
The condensate trap must be removed from the factory-installed
blower shelf location and relocated in selected application location
as shown in Fig. 2 or 10.
To relocate condensate trap from the blower shelf to desired
location, perform the following:
I. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward
and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose parts
bag) into blower shelf hole where trap wos removed.
4. Install condensate trap into left-hand side ca.sing hole by
inserting tube connection stubs through casing hole and
rotating until tabs snap into locking position.
PLUG
AUXILIARY "J" BOX "__
BOX
DRAIN TUBE
(BLUE AND WHITE STRIPED)
CONDENSATE
TRAP COLLECTOR BOX
TUBE(GREEN)
BOX EXTENSION
DRAIN TUBE
COLLECTOR BOX
EXTENStON TUBE
;ERHOUSING
DRAINTUBE(VIOLET)
DRAIN TUBE (BLUE)
DRAIN TUBE COUPLING \
\
COLLECTOR BOX TUBE (PINK) "_"
RELOCATE TUBE BETWEEN BLOWER SHELF AND INDUCER HOUSING FOR
040, 060, AND 080 HEATING INPUT FURNACES A01029
Fig. 10--Horizontal Left Tube Configuration
5. Fill unused condensate trap casing holes with plastic filler
caps (factory-supplied in loose parts bag).
CONDENSATE TRAP TUBING
NOTE: See Fig. 10 or tube routing label on main furnace door to
check for proper connections.
1. Collector Box Drain Tube
a. Install drain tube coupling (factory-supplied in loose parts
bag) into collector box drain tube tblue label) which was
previously connected to condensate trap.
b. Connect large diatueter drain tube and clamp (factory-
supplied in loose parts bag) to drain tube coupling, extend-
ing collector box drain tube.
c. Route extended tube (blue label) to condensate trap and cut
to appropriate length.
d. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube
a. Remove and disc,'u-d LOWER (molded) inducer housing
drain tube which was previously connected to condensate
trap.
b. Use inducer housing drain extension tube (violet label and
factory-supplied in loose parts bag) to connect LOWER
inducer housing drain connection to the condensate trap,
c. Determine appropriate length, cut. and connect tube.
d. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube
a. Extend collector box tube (green label) which was previ-
ously connected to the condensate trap by splicing to small
diameter tube (factory-supplied in loose parts bag).
b. Route extended collector box pressure tube to relief port
connection on the condensate trap.
c. Determine appropriate length, cut, and connect tube.
d. Clanlp tube to prevent any condensate leakage.
CONDENSATE TRAP FIELD DRAIN ATTACHMENTS
Refer to Condensate Drain section for recommendations and
procedures.
PRESSURE SWITCH TUBING
The LOWER collector box pressure tube (pink label) is factory
connected to the High Pressure Switch for use when furnace is
installed in UPFLOW applications. This tube MUST be discon-
nected, extended, rerouted, and then reconnected to the pressure
switch in HORIZONTAL LEFT applications for 060 and 080
heating input furnaces.
NOTE: See Fig. 10 or tube routing label on main furnace door to
check for proper connections.
Modify tube as described below:
1. Disconnect collector box pressure tube (pink label) attached to
High Pressure Switch.
2. Use smaller diameter tube I,factory-supplied in loose parts
bag) to extend tube disconnected in item i.
3. Route extended tube:
4.
a. Behind inducer housing.
b. Between blower shelf and inducer housing.
Determine appropriate length, cut. and reconnect tube to High
Pressure Switch connection labeled COLLECTOR BOX.
10
INTAKE
30_MIN
A 12-1N. MIN HORIZONTAL PIPE
SECTION IS RECOMMENDED WITH
SHORT (5 TO B FT) VENT SYSTEMS
TO REDUCE EXCESSIVE
CONDENSATE DROPLETS FROM
EXITING THE VENT PIPE.
SHUTOFF
GAS VALVE
3EDIMENT
TRAP
TRAP
DRAIN
ACCESS OPENING
FOR TRAP
NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE
FURNACE AND CONDENSATE TRAP WHEN A CONDENSING
FURNACE IS INSTALLED ABOVE FINISHED CEILINGS. A9_31
Fig. 11_Attic Location and Working Platform
CONDENSATE TRAP FREEZE PROTECTION
Refer to Condensate Drain Protection section for recommenda-
tions and procedures.
CONSTRUCT A WORKING PLATFORM
Cons_uct working platform where all required furnace clearances
are met. (See Fig. 3 and 113
NOTE: Combustion-air and vent pipes are restricted to a mini-
mum length of 5 ft, (See Table 7.)
NOTE: A 12-in. minimum offset pipe section is recommended
with short (5 to 8 It) vent systems. This recommendation is to
reduce excessive condensate droplets from exiting the vent pipe.
(See Fig. 11 or 35.)
Step 5_Horizontal Right (Supply-Air Discharge)
Applications
In a horizontal right furnace application, the blower is located to
the left of th_ burner section, and conditioned air is discharged to
the right.
NOTE: In Canada. installations shall be in accordance with
current NSCNGPIC Installation Codes and/or local codes.
NOTE: The auxiliary junction box O-Box) MUST be relocated to
opposite side of furnace casing, (See Fig. 12.) See Electrical
Connection section for J-Box relocation.
CONDENSATE TRAP LOCATION
The condensate trap must be removed from the factory-installed
blower shelf location and relocated in selected application location
as shown in Fig. 2 or 12.
To relocate condensate trap from the blower shelf to desired
location, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward
and rotating trap
3. Install casing hole filler cap (factory-supplied in loose parts
bag) into blower shelf hole where trap was removed.
4. Install condensate trap into left-hand side casing hole by
inserting tube connection stubs through casing hole and
rotating until tabs snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler
caps (facto_-_upplied in loose parts bag).
CONDENSATE TRAP TUBING
NOTE: See Fig. 12 or tube routing label on main furnace door to
check for proper connections.
1. Collector Box Drain Tube:
a. Remove factury-installed plug from LOWER collector box
drain tube (blue and white striped labell.
b. Install removed clamp and plug into UPPER collector box
drain tube (blue label) which was previously connected to
condensate trap.
11
CAP _/_ COLLECTOR BOX DRAIN TUBE (BLUE)
\// /-- COLLECTOR BOXTUBE (GREEN)
COLLECTOR BOX DRAIN TUBE "--1/
(BLUEAN INV_E:_I I;I)G S//
D =AIN_L_;OI_ET)ox S
EXTENSION TUBE
Fig. 12--Horizontal Right Tube Configuration
A01028
c. Connect LOWER collector box drain tube (blue and white
sniped label) to condensate trap. Tube does not need to be
cut.
d. Clan/p tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube:
a. Remove factory-installed plug from LOWER collector box
drain tube (blue and white striped label).
b. Remove and discard UPPER (molded) inducer housing
drain tube which was previously connected to condensate
trap.
c. Install cap and clamp on UPPER inducer housing drain
connection where molded drain tube was removed.
d. Use inducer housing drain extension tube (violet label and
factory supplied in loose parts bag) to connect LOWER
inducer housing drain connection to condensate trap.
e. Determine appropriate length, cut. and connect tube to
condensate trap.
f. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube:
Refer to Pressure Switch Tubing section for connection
procedure.
CONDENSATE TRAP FIELD DRAIN ATTACHMENT
Reler to Condensate Drain section for recommendations and
procedures.
PRESSURE SWITCH TUBING
One collector box pressure tube (pink label) is factory, connected to
the High Pressure Switch for use when furnace is installed in
UPFLOW applications. This tube MUST be disconnected and used
for the condensate trap relief port tube. The other collector box
pressure tube _,green label) which was factory connected to the
condensate trap relief port connection MUST be connected to the
High Pressure switch in DOWNFLOW or HORIZONTAL RIGHT
applications.
NOTI=: See Fig. 12 or tube routing label on main furnace door to
check for proper connections.
Relocate tubes as described below.
1. Disconnect collector box pressure tube (pink label) attached to
High Pressure Switch.
2. Extend collector box pressure tube (green label) which was
previously connected to condensate trap relief port connection
by splicing to small diameter tube (factory-supplied in loose
parts bag).
3. Connect collector box pressure tube (green label) to High
Pressure Switch connection labeled COLLECTOR BOX.
4. Use remaining smaller diameter tube (factory-supplied in
loose parts bagl to extend collector box pressure tube (pink
label) which was previously connected to High Pressure
Switch. Route this extended tube (pink label) to condensate
trap relief port connection.
5. Determine appropriate length, cut, and connect tube.
6. Clamp tube to relief poll connection.
CONDENSATE TRAP FREEZE PROTECTION
Refer to Condensate Drain Protection section for recommenda-
tions and procedures
CONSTRUCT A WORKING PLATFORM
Construct working platform where all required furnace clearances
are met. (See Fig. 3 and 11.1
12
NOTE: Combustion-air and vent pipes are restricted to a mini-
mum length of 5 ft. (See Table 7.)
NOTE: A12qn. minmium offset pipe section is recommended
with short _5 tu 8 flJ vent systems. This recommendation is to
reduce excessive condensate droplets from exiting the vent pipe.
(See Fig. 11 or 35.)
LOCATION
Step 1---General
This furnace must
be installed so the electrical components are protected from
water.
not be installed directly on any combustible material other than
wood flooring (refer to SAFETY CONSIDERATIONS),
be located so combustion-air and vent pipe maximum lengths
are not exceeded. Refer to Table 7.
be located where available electric power and gas supplies meet
specifications on the furnace rating plate.
be attached to an air distribution system and be located as close
to the center of the distribution system ms possible. Refer to Air
Ducts section.
be provided with ample space tot servicing and cleaning.
Always comply with minimum t'u'e protection clearances
shown on the furnace clearance to combustible label.
This furnace may be located in a confined space without special
provisions for dilution or ventilation air.
LEVEL (0") I
,o,,o xL ,7o;:;
UPFLOW OR DOWNFLOW HORIZONTAL A02146
r!1 t7, 1
____> Fig. 13_Proper Condensate Drainage
NOTE: For upflow/downflow applications install furnace so that
it is level or pitched forward within l/2-in, for proper furnace
operation. For horizontal applications pitch l/4-in, minimum to
l/2-in, maximum to ensure proper condensate drainage from
secondary, heat exchangers. (See Fig. 13.)
When afurnace is installed so that supply ducts carry air to areas
outside the space containing the furnace, return air must also be
handled by ducts sealed to furnace casing. The ducts terminate
outside the space containing the furnace to ensure there will not be
a negative 13ressure condition will not occur within equipment
room or space.
Do not install furnace on its back. (See Fig. 14.) Safety
control operation will be adversely affected. Never connect
return-air ducts to back of furnace. Failure to follow this
warning could result in fire, personal injury, or death.
13
BACK
L0
Fig. 14---Prohibit Installation on Back
A93043
/\
32°F MINIMUM INSTALLED
AMBIENT OR FREEZE
PROTECTION REQUIRED
Fig. 15--Freeze Protection
A93058
Do not operate this furnace during construction. If the furnace
is required for temporary heating of buildings or structures
under construction, use clean outside air free of chlorine and
fluorine compounds for combustion and ventilation. These
compounds form acids that corrode the heat exchangers.
These compounds are found in paneling and dry wall adhe-
sives, paints, thinners, masonry cleaning materials, and many
other materials.
Step 2--Furnace Location Relative to Cooling
Equipment
The cooling coil must be installed parallel with or on downstream
side of furnace to avoid condensation in heat exchanger. When
installed parallel with a furnace, dampers or other means used to
control flow of air shall be adequate to prevent chilled air from
entering furnace. If dampers are manually operated, they must be
equipped with a means to prevent operation of either unit unless
the danlper is in full-heat or full-cool position.
18-IN. MINIMUM
TO BURNERS
Fig. 16--Installation in a Garage
Step 3_Hazardous Locations
A93044
2. For each hole, install nut on bolt and then install bolt and nut
in hole. (Install flat washer if desired. )
3. InstMl another nut on other side of furnace base. (Install flat
washer if desired, )
4. Adjust outside nut to provide desired height, and tighten inside
nut to secure ,arrangement.
NOTE: Bottom closure must be used when leveling legs are used.
See Bottom Closme Panel section.
Step 2--Installation in Opflow and Downflow
Applications
NOTE: For downflow applications, this furnace is approved for
use on combustible floonng when special base (available fiom
manufacturer) Part No. KGASBO201ALL is used. Special b_e is
not required when this furnace is installed on manufacturer's Coil
Assembly P,'u't No. CD5 or CK5. or Coil Box Part No. KCAKC is
used.
When the furnace is installed in a residential garage, the
burners and ignition sources must be located at least 18 in.
above the Boor. The furnace must be located or protected to
avoid physical danlage by vehicles. When the furnace is
installed in a public garage, airplane hangar, or other building
having a hazardous atmosphere, the furnace must be installed
in accordance with the NFGC or NSCNGP1C, (See Fig. 16.)
INSTALLATION
Step 1--Leveling Legs (If Desired)
When furnace is used in upflow position with side inlet(s), leveling
legs may be desired. (See Fig. 17.) Install field-supplied,
corrnsion-resistant 5/16-in. machine bolts and nuts.
A96283
Fig. 18---Floor and Plenum Opening Dimensions
1. Determine application being installed from Table 1.
2. Construct hole in floor per dimensions specified in Table 1
and Fig. 18.
3. Construct plenum to dimensions specified in Table 1 and Fig.
18.
4. If downflow subbase (KGASB) is used, install as shown in
Fig. 19. If Coil Assembly Part No. CD5 or CK5 or Coil Box
part No, KCAKC is used, install as shown in Fig. 20.
NOTE: Remove furnace perforated, supply alrduct flanges when
they interfere with mating flanges on coil or downflow subbase, To
remove perforated, supply-air duct flanges, use wide duct pliers.
duct flange tool. or hand seamers to bend fl,'mge back and forth
until it brealcs off. Be careful of sharp edges. (See Fig. 21.!
A89014
Fig. 17--Leveling Legs
NOTE: The maximum length of bolt should not exceed 1-1/2 in.
1. Position furnace on its back. Locate and drill a 5/16-in.
diameter hole in each bottom comer of furnace. (See Fig. 17.)
Holes in bottom closure panel may be used as guide locations.
14
FURNACE
CASING
WIDTH
17-1/2
21
24-1/2
TABLE 1--OPENING DIMENSIONS (IN.)
APPLICATION
Upflow Applications
Downflow Applications on Non-Combustible Flooring
Downflow Applications on Combustible Flooring Using
KGASB Subbase
Furnace with or without CD5 or CK5 Coil Assembly or
KCAKC Coil Box
Downflow Applications on Combustible Flooring NOT Using
KGASB Subbase
Furnace with or without CD5 or CK5 Coil Assembly or
KCAKC Coil Box
Upflow Applications
Downflow Applications on Non-Combustible Flooring
Downflow Applications on Combustible Flooring Using
KGASB Subbase
Furnace with or without CD5 or CK5 Coil Assembly or
KCAKC Coil Box
Downflow Applications on Combustible Flooring NOT Using
KGASB Subbase
Furnace with or without CD5 or CK5 Coil Assembly or
KCAKC Coil Box
Upflow Applications
Downflow Applications on Non-Combustible Flooring
Downflow Applications on Combustible Flooring Using
KGASB Subbase
Furnace with or without CD5 or CK5 Coil Assembly or
KCAKC Coil Box
Downflow Applications on Combustible Flooring NOT Using
KGASB Subbase
Furnace with or without CD5 or CK5 Coil Assembly or
KCAKC Coil Box
PLENUM OPENING
A B
16 24-1/8
15-7/8 19
15-1/8 19
15-1/2 19
19-1/2 24-1/8
19-3/8 19
18-5/8 19
19 19
23 24-1/8
22-7/8 19
22-1/8 19
22-1/2 19
FLOOR OPENING
C D
16-5/8 24-3/4
16-1/2 19-5/8
16-3/4 20-3/8
16-1/2 20
20-1/8 24-3/4
20 19-5/8
20-1/4 20-3/8
20 20
23-5/8 24-3/4
23-1/2 19-5/8
23-3/4 20-3/8
23-1/2 20
FURNACE
(OR COIL CASING
WHEN USED)
FLOORING
SUBBASE
SHEET METAL
PLENUM
__ FLOOR __
OPENING
A96285
Fig. 19---Furnace, Plenum, and Subbase Installed
on a Combustible Floor
FURNACE
CD5 OR CK5
COIL ASSEMBLY
OR KCAKC
COIL BOX
COMBUSTIBLE --
FLOORING
_SHEETpLENuMMETAL._.b i_
FLOOR __
OPENING "_
A96284
Fig. 20---Furnace, Plenum, and Coil Assembly or
Coil Box Installed on a Combustible Floor
15
DISCHARGE DUCT
FLANGE
NO
210°
MIN
f
Fig. 21--Duct Flanges
YES
YES
A93029
Do not bend duct flanges inward as shown in Fig. 21. This
will affect airflow across heat exchangers and may cause limit
cycling or premature heat exchanger failure. Remove duct
flange completely or bend it inward a minimum of 210 ° as
shown in Fig. 21.
Step 3--Installation in Horizontal Applications
These furnaces can be installed horizontally in either horizontai
left or right discharge position. In a crawlspace, the funmce can
either be hung from floor joist or installed on suitable blocks or
pad. Furnace can be suspended from each corner by hanger bolts
and angle iron supports. (See Fig. 22.) Cut hanger bolts (4 each
318-in. all-thread rod) to desired length. Use 1 X 3/8-in. fiat
washers, 3/8-in. lock washers, and 3/g-in. nuts on hanger rods as
shown in Fig. 22. Dimples are provided for hole locations. (See
Fig. 2.)
The entire length of furnace MUST be supported when
furnace is used in a horizontal position to ensure proper
draining. When suspended, bottom brace supports sides and
center blower shelf. When unit is supported from the ground.
blocks or pad should support sides and center blower shelf
area.
Step 4_Air Ducts
GENERAL REQUIREMENTS
The duct system should be designed and sized according to
accepted national standards such a.s those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and
Air Conditioning Contractors National Association (SMACNAI or
American Society of Heating, Refrigerating ,-rod Air Conditioning
Engineers (ASHRAE), or consult The Air Systems Design Guide-
lines reference tables available from your Iocai distributor. The
duct system should be sized to handle the required system design
CFM at the design static pressure.
When a furnace is installed so that the supply ducts carry air
circulated by the furnace to areas outside the space containing the
furnace, the return air must also be handled by a duct(s) sealed to
the furnace ca_ing and terminating outside the space containing the
furnace.
Secure ductwork with proper fasteners lot type of ductwork used.
Seal supply- and return-duct connections to furnace with code
approved tape or duct sealer.
Flexible connections should be used between ductwork and
furnace to prevent transmission of vibration. Ductwork passing
through unconditioned space should be insulated to enhance
system peffornlance. When air conditioning is used, a vapor
barrier is recommended.
Maintain a l-in. clearance from combustible materials to supply air
ductwork for a distance of 36 in. horizontally from the furnace. See
NFPA gOB or local code for further requirements.
For a furnace not equipped with acooling coil. the outlet duct shall
be provided with a removable access panel. This opening shall be
accessible when the furnace is installed and shall be of such a size
that the heat exchanger can be viewed for possible openings using
light assistance or a probe can be inserted for sampling the air
stream. The cover attachment shall present leaks.
DUCTWORK ACOUSTICAL TREATMENT
Metal duct systems that do not have a 90 degree elbow and 10 ft
of main duct to the first branch take-off may require internal
acoustical lining. As an alternative, fibrous ductwork may be used
if constructed and installed in accordance with the latest edition of
SMACNA construction standard on fibrous ghtss ducts. Both
acoustical lining and fibrous ductwork shall comply with NFPA
90B as tested by UL Standard 181 for Class I Rigid air ducts.
SUPPLY AIR CONNECTIONS
Upflow Furnaces
Connect supply-air duct to 314-in. flange on furnace supply-air
outlet. The supply-air duct attachment must ONLY be connected
to furnace supply-/outlet-air duct flanges or ,'airconditioning coil
casing (when used). DO NOT cut main furnace casing to attach
supply side air duct, humidifier, or other accessories. All accesso-
ries MUST be connected external to furnace main casing.
Down fiow Furnaces
Connect supply-air duct to supply-ah- opening on furnace. The
supply-air duct attachment must ONLY be connected to furnace
supply/outlet or air conditioning coil ca.sing (when used), when
installed on non-combustible material. When installed on combus-
tible material, supply-air duct attachment must ONLY be con-
nected to an accessory subbase or facto_ approved air condition-
ing coil casing. DO NOT cut main furnace casing to attach supply
side air duet, humidifier, or other accessories. All accessories
MUST be connected external to furnace main casing. Supply air
opening duct flanges must be modified per Fig. 21.
Horizontal Furnaces
Connect supply-air duct to supply air opening on furnace. The
supply-air duct attachment must ONLY be connected to furnace
supply/outlet or air conditioning coil casing (when used). DO NOT
cut main furnace c_._ing to attach supply side air duct, humidifier,
or other accessories. All accessories MUST be connected external
to furnace main casing.
RETURN AIR CONNECTIONS
F.,_1'_21-.I_rs[
16
Never connect return-air ducts to the back of the furnace.
Return-air duct connections on furnace side(s) permitted in
upftow applications only. Afailure to follow this warning
could result in fire, personal injury, or death.
Upflow Furnaces
The return-air duct must be connected to bottom, sides (left or
right), or a combination of bottom and side(s) of main furnace
ANGLE --_
IRON OR
EQUIVALENT "_ - ALTERNATE SUPPORT
LOCATION 4-IN. MIN
8-IN. MAX
(B)
(A) ROD LOCATION
USING DIMPLE
LOCATORS
(SEE DIMENSIONAL
DWG FOR
LOCATIONS)
3!8-1N.
& WASHER (4)
REQD PER ROD
3/t6-IN. MAX
(B) ALTERNATE SUPPORT
LOCATION FROM BACK
(A) PREFERRED ROD LOCATION
(B) ALTERNATE ROD LOCATION
NOTES: 1. A 1 In. clearance minimum between top of
furnace and combustible material
2. The entire length of furnace must be
supported when furnace is used in horizontal
position to ensure proper drainage. A93304
Fig. 22---Crawlspace Horizontal Application
casing. Bypass humidifier may be attached into unused side return
air portion of the furnace casing. DO NOT connect any portion of
return-air duct to back of furnace casing.
Downflow and Horizontal Furnaces
The return-air duct must be connected to return-air opening
provided. DO NOT cut into casing sides or back to attach any
portion of return-air duct. Bypass humidifier connections should
be made at ductwork or coil casing sides exterior to furnace.
Step 5--Filter Arrangement
The air filter arrangement will vary. due to application, furnace
orientation, ',and filter type. The filter may be installed in an
external Filter/Media cabinet {if provided) or the furnace blower
compartment. Factory supplied washable filters axe shipped in the
blower compartment.
If a factory-supplied external Filter/Media cabinet is provided,
instructions for its application, assembly, and installation are
packaged with the cabinet. The Filter/Media cabinet can be used
with the factory-supplied washable filter or a factory-specified
high-efficiency disposable filter/see cabinet instructions).
If installing the filter in the furnace blower compartment, deter-
mine location for filter and relocate filter retaining wire if
necessary. See Table 2 to determine correct filter size for desired
filter location. Table 2 indicates filter size, location, and quantity
shipped with this furnace. See Fig. 2 for location and size of
bottom ,and side return-air openings.
Table 2--FILTER INFORMATION
AIR FILTER LOCATED IN BLOWER COMPARTMENT
FURNACE FILTER SIZE (IN,)* FILTER
CASING
WIDTH (IN.) Side Return Bottom Return TYPE
17-t/2 (1) 16X25X It (1) 16 X 25 X It ! CIeanable
21 (1) 16X25X 1 (t) 20X25Xlt Cleanable
24-1/2 (1or2) 16X25X1 (1)24X25XlI" Cleanable
•Filtersmay be fieldmodified by cutting filtermaterial and supportrods(3) in
filters.Alternate sizes and additional filters may be ordered from your dealer.
f Factory-provided with furnace.
Use care when cutting support rods in filters to protect against
flying pieces and sharp rod ends. Wear safety glasses, gloves,
and appropriate protective clothing. Failure to follow this
caution could result in personal injury.
17
table in Product Data literature for specific use of single side
inlets. The use of both side inlets, a combination of 1 side and
the bottom, or the bottom only will ensure adequate return air
openings for airflow requirements above 1800 CFM.
IOTE: Side return-air openings can ONLY be used in UPFLOW
configurations. Install filterts) as shown in Fig. 23. Bottom
return-air opening may be used with all 4 orientations, Filter may
need to be cut to fit some furnace widths. Install filter a._ shown in
Fig. 24.
17_-IN. WIDE
CASINGS ONLY:
INSTALL FIELD-SUPPLIED
FILTER FILLER STRIP
UNDER FILTER.
RETAINER
\A93045
Fig. 23---Filter Installed for Side Inlet
NOTE: Remove and discard bottom closure panel when bottonl
inlet is used.
Step 6_Bottom Closure Panel
This furnace is shipped with bottom closure panel installed in
bottom return-air opening. This panel MUST be in place when side
return air is used.
To remove bottom closure panel, perform the following:
I. Tilt or raise furnace and remove 2 screws holding front filler
panel. ISee Fig. 25.)
2. Rotate front filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall front filler panel and screws.
Step 7_Gas Piping
Gas piping must be installed in accordance with national and local
codes. Refer to cmxent edition of NFGC in the United States.
Canadian installations must be made in accordance with NSCNG-
PIC and all authorities having jurisdiction.
Gas supply line should be a separate line running directly from
meter to furnace, if possible. Refer to Table 3 for recommended
gas pipe sizing.
Risers must be used to connect to furnace and to meter. Support all
gas piping with appropriate straps, hangers, etc. Use a mininmm of
1 hanger eve R, 6 ft. Joint compound (pipe dopet should be applied
sparingly and only to male threads of joints, Pipe dope must be
resistant to propane gas.
\
FILTER
FILTER
RETAINER
SUPPORT
Fig. 24---Bottom Filter Arrangement
A00213
/FRONT FILLER
PANEL
BOTTOM
CLOSURE
PANEL
Ag3047
Fig. 25--Removing Bottom Closure Panel
Connect gas pipe to furnace using a backup wrench to avoid
damaging gas controls.
18
Table 3---MAXIMUM CAPACITY OF PIPE*
NOMINAL
IRON
PiPE
SIZE
(IN.)
1/2
3/4
1
1-1/4
1-1/2
INTERNAL LENGTH OF PIPE (FT)
DIAMETER --_ -----
(IN.) 10 !20 30 40
0.622 175 120 97 82
0.824 360 250- 200 170
1.049 680 465 375 320
1.380 1400 950 770 660
1.610 2100 1460 1180 990
5O
73
151
285
580
900
*Cubic ft of gas per hr. for gas pressures of 0,5 psig (14_n. wc) or less and
a pressure drop of 0.5_n wc (based on a 0.60 specific gravity gas).
Ref: NFGC.
property damage or death.
r.,_'I2!_-JULR_
____) Never purge a gas line into a combustion chamber. Never test
for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of
leaks to check all connections, as specified in "Adjustments"
section. Failure to follow this warning could result in fire,
explosion, personal injury, or death.
Use proper length of pipe to avoid stress on gas control
manifold. Failure to follow this warning could result in a gas
leak resulting in l-we, explosion, personal injury, or death.
Install a sediment trap in riser leading to furnace. Trap can be
installed by connecting a tee to riser leading to furnace so
straight-through section of tee is vertical. Then connect a capped
nipple into lower end of tee. Capped nipple should extend below
level of gas controls. Place a ground joint union between gas
control manifold and manual gas shutoff valve. (See Fig. 26.)
GAS--I-'T
SUPPLY _
MANUAL _/ II
SHUTOFF _. _
VALVE
(R QU'RE':'If
SEDIMENT--" ]
TRAP UNION "J
--_ If local codes allow the use of a flexible gas appliance connector.
always use a new listed connector. Do not use a connector which
has previously serviced another gas appliance.
FIRE OR EXPLOSION HAZARD
Fadure to follow the safeb, warnings exactly could result in
serious injury, death or property damage.
Never test for gas leaks with an open flame. Use a commer-
cially available soap solution made specifically for the
delection of leaks to check all connections. Afire or explo-
sion may result causing property damage, personal injur3, or
loss of life.
An accessible manual shutoff valve MUST be installed external 1o
furnace casing and within 6 ft of furnace. A l/8-in. NPT plugged
tapping, accessible for test gage connection. MUST be installed
immediately upstream of gas supply connection to furnace and
downstream of manual shutoff valve.
Piping should be pressure tested in accordance with NFGC, local
mad national plumbing and gas codes before the furnace has been
connected. In Canada. refer to current edition of NSCNGPIC. If
the pressure exceeds 0.5 psig (14-in. wc). gas supply pipe must be
disconnected from the furnace and capped before pressure test. if
test pressure is equal to or less than 0.5 psig ( 14-in. wch turn off
electric shutoff switch located on gas valve before test. It is
recommended that the ground joint union be loosened before
pressure testing.
After all connections have been made, purge lines and check for
leakage.
NOTE: The gas valve inlet press tap connection is suitable to use
as test gage connection providing test pressure DOES NOT exceed
maximum 0.5 psig (14-in. wc) stated on gas valve, (,See Fig. 53.)
---) The gas supply pressure shall be within the maximum and
minimum inlet supply pressures marked on the rating plate with
the furnace burners ON at HI-HEAT and OFF.
Step 8_Electrical Connections
See Fig. 27, 28, and 50A-H for field wiring diagram showing
typical field ll5-v and 24-v wiring. Check all factory and field
electrical connections for tightness.
Blower access door switch opens 115~v power to furnace
control. No component operation can occur. Do not bypass or
close switch with panel removed. Failure to follow this
warning could result in personal injury or death.
----).Field-supplied wiring shall conform with the limitations of 63
degrees F rise.
A93324
Fig. 2_-Typical Gas Pipe Arrangement
19
box screw,
115-V WIRING
Before proceeding with electrical connections, make certain that
voltage, frequency, and phase correspond to that specified on the
BLK BLK
115-V FUSED
DISCONNECT
SWITCH
(WHEN REQUIRED)
.... FLELD24-V WIRING
.... FIELD 115-,208/230-, 460-V WIRING
-- FACTORY 24-V WIRING
-- FACTORY 115-V WIRING
1-STAGE THERMOSTAT TERMINALS
_, , ,,
TWO-WIRE I 1 1
HEATING- _ _ __"
ONLY ___--> I_ ', ',
---- I I I
I I I I
-- ----T .... i i
_.. 1 @ , , ,
UNCTION "_" i ,
BOX ® : '-_,-----
CONTROL
BOX @
Y4-V--
TERMINAL
BLOCK
FURNACE
I t
¢GNOr_
FIELD-SUPPLIED
FUSED DISCONNECT
--_---_ 208/230-OR
.... _JPHASE
.-_---1208/230-V
_,,J [.SINGLE
:--_-:-JPHASE
CONDENSING
UNIT
NOTES: 1. Connect Y-terminal as shown for proper operation.
2. Some therrnostats requirea "C" terminalconnectionas shown.
3. If any of the original wire, as supplied, must be replaced,
use same type or equivalent wire.
A99071
Fig. 27--Heating and Cooling Application Wiring Diagram 1-Stage Thermostat and Condensing Unit
_L_K _K_I
115-V FUSED
DISCONNECT
SWITCH
(WHEN REQUIRED)
.... FIELD 24-V WIRING
.... FIELD 115-,208/230-, 460-VWIRING
-- FACTORY 24-V WIRING
-- FACTORY 115-VWIRING
JUNCTION
BOX CONTROL
BOX
@
@
@
@
®
®
2_V
TERMINAL
BLOCK
III I
I l II
I I I I
FURNACE
FIEL_SUPPLIED
FUSED DISCONNECT
208/230- OR
$60-V
PHASE
208/230-V
NOTES: 1. Connect Y-terminal asshown for properoperation.
2. Somethermostatsrequirea "C" terminalconnectionasshown.
3. Ifanyof the originalwire,as supplied,must be replaced,
use sametype or equivalentwire,
A99072
Fig. 28--Heating and Cooling Application Wiring Diagram 2-Stage Thermostat and Condensing Unit
furnace rating plate. Also, check to be sure that service provided For U.S. instaUations, make all electrical connections in accor-
by power supply is sufficient to handle load imposed by this dance with National Electrical Code (NEC) ANSI/NFPA 70-2002
equipment. Refer to rating plate or Table 4 for equipment electrical and any local codes or ordinances that might apply. For Canadian
specifications. 20

Other manuals for GAS FURNACE 58MTA

3

Other Carrier Furnace manuals

Carrier 379C/HO User manual

Carrier

Carrier 379C/HO User manual

Carrier Comfort 59SC5A Series Operation manual

Carrier

Carrier Comfort 59SC5A Series Operation manual

Carrier N80VSL User manual

Carrier

Carrier N80VSL User manual

Carrier 58VMR Guide

Carrier

Carrier 58VMR Guide

Carrier 59SC5B Operation manual

Carrier

Carrier 59SC5B Operation manual

Carrier 58TUA Instructions and recipes

Carrier

Carrier 58TUA Instructions and recipes

Carrier CBLAAA060120 User manual

Carrier

Carrier CBLAAA060120 User manual

Carrier 394GAD User manual

Carrier

Carrier 394GAD User manual

Carrier OIL FURNACE 58CMA Guide

Carrier

Carrier OIL FURNACE 58CMA Guide

Carrier 58MEC Installation and user guide

Carrier

Carrier 58MEC Installation and user guide

Carrier Minor 2 Series Guide

Carrier

Carrier Minor 2 Series Guide

Carrier 58UHV Series Instructions and recipes

Carrier

Carrier 58UHV Series Instructions and recipes

Carrier 58BB User manual

Carrier

Carrier 58BB User manual

Carrier 58MCA Instructions and recipes

Carrier

Carrier 58MCA Instructions and recipes

Carrier Deluxe 58SXB User manual

Carrier

Carrier Deluxe 58SXB User manual

Carrier Condensing gas furnace User manual

Carrier

Carrier Condensing gas furnace User manual

Carrier 58SU0A Series User manual

Carrier

Carrier 58SU0A Series User manual

Carrier 58SG Dimensions and installation guide

Carrier

Carrier 58SG Dimensions and installation guide

Carrier 300 User manual

Carrier

Carrier 300 User manual

Carrier 59MN7A Guide

Carrier

Carrier 59MN7A Guide

Carrier 58WAV Operating manual

Carrier

Carrier 58WAV Operating manual

Carrier 58TN0B User manual

Carrier

Carrier 58TN0B User manual

Carrier 58MEC Instructions and recipes

Carrier

Carrier 58MEC Instructions and recipes

Carrier 59TP6A Guide

Carrier

Carrier 59TP6A Guide

Popular Furnace manuals by other brands

US Stove Company 8500 owner's manual

US Stove Company

US Stove Company 8500 owner's manual

vita vacumat 4000 premium t operating manual

vita

vita vacumat 4000 premium t operating manual

Payne PG95ESA Installation, start-up, operating and service and maintenance instructions

Payne

Payne PG95ESA Installation, start-up, operating and service and maintenance instructions

Bryant PG96VTA Installation, start-up, operating and service and maintenance instructions

Bryant

Bryant PG96VTA Installation, start-up, operating and service and maintenance instructions

Amana GMS8 Service instructions

Amana

Amana GMS8 Service instructions

Lennox ML180UHE Other

Lennox

Lennox ML180UHE Other

York TM9V080B12MP11 Technical guide

York

York TM9V080B12MP11 Technical guide

Payne PG96VAT Product data

Payne

Payne PG96VAT Product data

Lennox GHR26 SERIES User's information manual

Lennox

Lennox GHR26 SERIES User's information manual

Lennox G61MPVT-36B-070 installation instructions

Lennox

Lennox G61MPVT-36B-070 installation instructions

Tempstar G9MXT installation instructions

Tempstar

Tempstar G9MXT installation instructions

England's Stove Works 24-G Installation and operation manual

England's Stove Works

England's Stove Works 24-G Installation and operation manual

VERDER CARBOLITE GERO HTF 18/27 Installation, operation and maintenance instructions

VERDER

VERDER CARBOLITE GERO HTF 18/27 Installation, operation and maintenance instructions

Trane AUD2A040A9242A Installer's guide

Trane

Trane AUD2A040A9242A Installer's guide

York GY8S User's information, maintenance and service manual

York

York GY8S User's information, maintenance and service manual

York TG9S Technical guide

York

York TG9S Technical guide

American Standard *HV1MO87 User’s guide User's information guide

American Standard

American Standard *HV1MO87 User’s guide User's information guide

Lennox ML193UH User's information manual

Lennox

Lennox ML193UH User's information manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.