IMPORTANT.
It is important that no external
control devices are directly connected to this
appliance - unless covered by these ‘Installation
and Servicing Instructions’ or otherwise recom-
mended by the manufacturer. If in doubt, please
enquire.
A 12V DC circuit is provided for system control
devices located in wet areas.
Any direct connection of a control device not
recommended by the manufacturer could infringe
the Gas Safety (Installation & Use) Regulations, the
above regulations and the normal appliance war-
ranty.
Manufacturer’s notes must NOT be taken, in any
way, as overriding statutory obligations.
Location of Boiler
The boiler MUST be fixed to a floor or vertical non-
combustible wall, capable of adequately supporting
the weight of the boiler and any ancillary equip-
ment.
THE BOILER IS NOT SUITABLE FOR
EXTERNAL INSTALLATION.
IMPORTANT NOTICE.
If the boiler is to be fitted in a timber framed building
it should be fitted in accordance with the British Gas
publication ‘Guide for Gas Installations in Timber
Frame Housing’, reference DM2. If in doubt, advice
must be sought from the Local Gas Region of
British Gas.
The boiler may be installed in any room or internal
space. Particular attention is drawn to the require-
ments of the current I.E.E Wiring regulations and, in
Scotland, the electrical provisions of the Building
Regulations applicable to Scotland with respect to
the installation of the boiler in a room or internal
space containing a bath or shower.
Where a room sealed appliance is installed in a
room containing a bath or shower then the appli-
ance and any electrical switch or appliance control,
utilising mains electricity should be so situated that
it cannot be touched by a person using the bath or
shower.
Where installation will be in an unusual location
then special procedures may be necessary and
BS.6798 gives detailed guidance on this aspect.
A compartment used to enclose the boiler MUST be
designed and constructed specially for this purpose.
An existing cupboard, or compartment, may be
used provided it is modified for the purpose. Details
of essential features of cupboard compartment
design, including airing cupboard installations are
given in BS.6798.
In siting the boiler, the following limitations MUST be
observed:
1. The position selected for installation MUST allow
adequate space for servicing in front of the boiler
and for air circulation around the boiler.
2. This position MUST also permit the provision of a
satisfactory balanced flue termination.
3. This position MUST also permit the provision of a
satisfactory connection to the condensate drain.
Gas Supply
An existing meter (NG) and pipework should be
checked, preferably by the Gas region, to ensure that
they are adequate to deal with the rate of gas supply
required.
Supply pipes should be sized to suit installation and
obtain a working pressure of 20 mbar (NG) or 37
mbar (Propane). Installation pipes should be fitted in
accordance with BS.6891.
A Natural Gas appliance must be connected to a
governed meter.
Conversion
The appliance can be converted from NG to LPG or
vice versa by change of the Burner, Main and Pilot
Injectors and re-setting the Gas Valve. Contact your
supplier for the necessary parts.
Flueing
Only flue components provided by the Manufacturer
should be used with these appliances. Detailed
recommendations for flueing are given in BS.5440: 1.
The following notes are intended for general guid-
ance.
1. Be aware of the plume from the flue and the
wetting effect it has to adjacent property.
2. The flues can be taken left, right or to the rear of
the appliance.
3. The appliance is supplied with two standard flue
sets. There are two lengths of Concentric Flue.
Standard, that will reach 500mm, and Extended
that will reach up to 2000mm. (Part No. M3838).
4. The boiler MUST be installed so that the termi
nals are exposed to external air.
5. It is important that the terminals allow the free
passage of air across them at all times.
6. The acceptable spacing from the terminal to
obstructions and ventilation openings are
specified in Table 1.
7. Because the flue gases and terminal are at very
low temperature it is not necessary to fit a
Terminal guard to protect against burns. If a
guard is required for any other reason the
following is recommended.
MBD200
3
14/02/04