Clevertronics L10 LIFELIGHT PRO Installation and operating instructions

1942142
V1.2
9 February 2023
Instruction Sheet Template - V1.5 –Updated 09/06/2022
Clevertest Plus
Refer to the supplementary operation guide supplied with the product.
When activated the luminare will automatically perform a duration test every six-months.
After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red
flashing for a period up to 2 minutes.
Zoneworks, HIVE and DATA Monitored Options
Fittings with part numbers -ZW, -HV/-HVG, -DATA are fitted with Zoneworks communications modules
(nodes). These fittings are monitored using either Powerline Carrier Technology that utilise the power
cable to provide data communication, RF transceiver modules operating in the ISM band or a dedicated
data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can also
be connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor,
coordinate testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by a
single push of the test switch or by scanning the supplied barcode. The LED Test Switch indicator provides
a multifunction indication of the status of the fitting during testing and normal operation:
Option
State
LED Operation
ZW, HV, HVG, DATA
Commissioned
LED on Solid (Green)
ZW, DATA
Un-commissioned
Batt plugged-in: yellow 1s, green 1s
Batt unplugged: red 1s, off 1s
HV, HVG
Un-commissioned
With network connectivity
Batt plugged-in: yellow 1s, green 1s
Batt unplugged: red 1s, off 1s
HV, HVG
Un-commissioned
Without network connectivity
Batt plugged-in: yellow 250mS,
green 250mS, yellow 250mS, green
250mS, green 1s
Batt unplugged: red 250mS, off
250mS, red 250mS,off 250mS, off 1s
ZW, DATA
Emergency Light Test In Progress
LED flashes at yellow 5s , 0ff 1s
HV, HVG
Emergency Light Test In Progress
LED flashes at yellow 1s , 0ff 1s
In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the connection to
the DATA network via a multi-drop bus (daisy chain connection). For further information of installation of
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA
version)
DALI EM Option
Luminaires with part numbers having -DALI are fitted with DALI modules (nodes) that facilitate connection
and integration to 3rd Party Lighting Control Systems. Before installing the -DALI luminaire, please confirm
that the Lighting Control System has the capability to monitor DALI Emergency Luminaires. The -DALI
fitting will be addressed and configured into the control system by the Lighting Control System
Commissioning Technicians and not Clevertronics.
State
LED Operation
Commissioned/ Un-commissioned
LED on Solid (Green)
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
“IDENTIFY COMMAND”
Lamp and Status LED Flash for 30 seconds
A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network. DALI
connections are marked as Da Da.
L10™Weatherproof LIFELIGHT PRO Ceiling Mount
Installation & Maintenance Instruction Leaflet
Victoria (Head Office & Manufacturing)
Website: www.clevertronics.com.au
Email: info@clevertronics.com.au
Phone: +61 3 9559 2700
Fax: +61 3 9559 2799
New South Wales
Phone: +61 2 8805 6400
Fax: +61 2 8805 6444
Queensland
Phone: +61 7 3442 9700
Fax: +61 7 3442 9777
South Australia/Northern Territory
Phone: +61 8 8301 8800
Fax: +61 8 8351 8286
Western Australia
Phone: +61 8 9207 0000
Fax: +61 8 9207 0088
New Zealand
Phone: +64 800 548 448
Designed in Australia to comply with the
requirements of AS2293.3: 2005, AS CISPR15: 2011
NOTE: Standard product codes with this symbol are
enabled with Clevertest Plus capability. Please refer to
the operation guide supplied with the product for details.
Models:
LWPLIFE-PRO-xx-CM-yy-xxx
Testing:
Options:
Manual Test
xx = Blank
Colour variants
yy=BLK, MSLV
Zoneworks
xx = ZW
xxx = WHT, RAL
Z/W DATA
xx = DATA
Zoneworks HIVE
xx = HV/HVG
DALI
xx = DALI
Spare Parts:
15300230
Replacement Battery
1100817
Replacement Emergency LED Head (-BLK)
1100819
Replacement Emergency LED Head
AUM01370120001
Replacement Emergency Driver
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation,
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in
accordance with the relevant Australian and International Standards.

1942142
V1.2
9 February 2023
Instruction Sheet Template - V1.5 –Updated 09/06/2022
Installation:
This LWPLIFE-PRO-CM is a ceiling mount Emergency Luminaire.
•Loosen the grub screw and remove the mounting plate from the fitting.
•Locate the installation position.
•Using the mounting plate as a template, mark out the holes required to mount.
•Position the plate to the surface while routing the power cable through the gland.
•Circular power cable recommended to maintain IP rating
•Use suitable fixings to fasten the mounting plate to the mounting surface.
•Route and terminate the supply cables to the L, N & E terminals in the gear tray.(in the case of the
–DALI or –DATA fittings terminate the DALI or DATA cable to the terminals marked Da Da or
DATA).
•Check gland is tight with a good seal.
•Reinstall the main assembly and secure with the grub screws.
•Apply power to the fitting and check operation.
•If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four
Segment Marking on the product will include an ‘’F’’ in third segment block.
Networking:
When installing the product on a monitored network, (ZONEWORKS, HIVE, DATA, DALI) simply insert
the relevant Smart Node PCA. Record the node’s unique serial number on the logbook’s baseline data
Dimensions:
Testing:
When the LWPLIFE-PRO-CM unit is connected to the un-switched active, it must be allowed to charge
the battery for at least 24 hours. The emergency lamp only illuminates during a power failure. Conduct
the following tests:
•During the first commissioning test the emergency lamp must illuminate for at least 2 hours after
disconnection from the main supply. The results of all tests are required to be recorded in a service
logbook, which is to be kept on-site at all times. If the unit fails to illuminate for the requisite time,
remedial action must be taken to repair the situation and once completed, the unit must pass the
next subsequent test.
•To test, remove the screws holding the glass cover to the fitting to access the test button.
•Press and hold Test Button check that the emergency lamp is On.
•Alternately, turn off Mains Supply to the fitting. Verify the lamp is on.
•Release the Test Button or Switch on Mains Supply, check that the emergency lamp is Off (Non-
maintained operation).
Trouble Shooting:
Below are a list of common problems and their possible causes.
Fault: The Green LED Test Switch indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault: Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is connected.
Battery is connected
Fault: Lamp illuminates in emergency mode, but only stays on for a short period.
Check: Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1,(refer to
spacing tables for installation positions):
Refer to the Technical Label for classification information.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such
abuse, are specifically EXCLUDED from Clevertronics warranty terms.
Warranty:
For Product Warranty information and Terms and Conditions of Sales please refer to our website
http://clevertronics.com.au/terms-conditions-sale-australia-nz/
This luminaire (with reinforced insulation between control/LED terminal and AC Supply) contains non-
user replaceable light source –to be replaced (if required) by the manufacturer or his service agent or a
similar qualified person.
Popular Rack & Stand manuals by other brands

Flexispot
Flexispot KT1 installation guide

Aydin Displays
Aydin Displays CAMBRIDGE CFP47W1 user manual

Display Mount Pro
Display Mount Pro LCD351D-STAND Installation instruction

Technimount System
Technimount System BRACKET PRO 76 Series user guide

AmazonBasics
AmazonBasics B082Z3BQRJ manual

ERARD
ERARD EXO OLED TW 2 manual