Circulating Air Source Heat Pump Water Heater
13
that’s the heating water tank and the thermal storage water tank are set at the architectural plane. Water
discharge water pump should be set between thermal storage water tank and heating water tank for
sending the heated water to the thermal insulating water tank (see fig 3). The other setting method is the
non-contour setting, that’s the heating water tank is higher than the thermal storage water tank. The
heated water can be send to the thermal insulating water tank by the gravity of water and it’s no need to
set water pump (fig 4). The second setting method is suggested for the project.
6) When users don’t use the hot water for a long time, the water temperature inside the thermal
storage water tank will decrease due to the heat loss. It needs to set thermal insulating unit on the
project. When the water temperature inside the thermal storage water tank is lower than a certain
temperature below the set temperature (user can set the temperature by themselves), and thermal
insulating unit will be started up and heat the water inside the thermal storage water tank. When the
water temperature reaches to set temperature, the thermal insulating unit will stop operation. The
detailed quality is decided by the actual circumstances.
7) Back water control of water system at user side: When the water at the user side hasn’t been
consumed for a long time, the water temperature inside the water pipe will decrease. When the water
temperature is decreased to set temperature (20~50℃adjustable),backwater pump or backwater
solenoid valve will be started up to heat water or suck the hot water inside the thermal storage water tank
into pipe network to increase the water temperature. When the water temperature is increased to a
certain temperature above set temperature, backwater pump or backwater solenoid valve will be
stopped for ensuring the water temperature requirement.
If user has requirement for water supply pressure. Users are suggested to adopt water pump +
electric contact type pressure switch. When the water pressure is lower than set value, the water pump
will be started up; when the pressure reached to set value, the water pump will stop operation. When
user is using water, the user water supply water pump will be controlled by the by electric contact
manometer or water flow switch (equipped by project). Meanwhile, they will send the power-off
command to backwater solenoid valve.
8) High/low water level requirement for water level switch
The high water level of water level switch for the heating water tank should be lower than the
overflow pipe (generally, on top of the water tank) of the heating water tank. The low water level should
be a little higher than the pipe inlet of unit at the circulating heating side.
9) Water system instruction at user side
If the system pipeline is short and the pipe network is simple, user can supply water by the gravity of
water, no need to adopt water pump circulation. You can also adopt the water pump circulation system
as shown in fig 3 and fig4. If the water hasn’t been used for a long time, the water temperature inside the
water pipe will decrease. When it’s decreased to a certain temperature below the set temperature, water
supply water pump will be started up to compress the hot water inside the thermal storage water tank
into pipe network for increasing the water temperature.
10) Control of auxiliary electric heating: The auxiliary electric heating adopts pipeline electric heating,
which is controlled by ambient temperature and the unit.
Special hint:
If the unit hasn’t been used for a long time or the unit is started up for the first time, please check the