Eaton TC 24 User manual

RR
www.comoso.com

The Symbol calls attention to an operating procedure, practice, or the
like, which, if not correctly performed or adhered to, could result in
personal injury or damage to or destruction of part or all of the
product and system. Do not proceed beyond a warning symbol until
the indicated conditions are fully understood and met.
Installers
System Designer
Expert User
Read Chapter 1, 2
Read All Chapters
Read Page 11
NOTE:NOTE:
It is stronglyrecommended that aprocess should
incorporate a LIMITCONTROL likeL91 which willshut down
the equipment ata preset processcondition in orderto
preclude possible damageto products orsystem.
Some programming parametersshown in thismanual may not
be available oncurrently offered models.
It is stronglyrecommended that aprocess should
incorporate a LIMITCONTROL likeL91 which willshut down
the equipment ata preset processcondition in orderto
preclude possible damageto products orsystem.
Some programming parametersshown in thismanual may not
be available oncurrently offered models.
Information in this user's manual is subject to change without
Copyright aApril 2003, Eaton Corporation, all rights reserved. No
part of this publication may be reproduced, transmitted,
transcribed or stored in a retrieval system, or translated into any
language in any form by any means without the written permission
of Eaton Corporation.
2
This manual isapplicable for theproducts with software
version 23 andlater version.
This manual isapplicable for theproducts with software
version 23 andlater version.
www.comoso.com

3
ContentsContents
Chapter 1 OverviewChapter 1 Overview
1-1 General -------------------------5
1-2 Ordering Code ---------------8
1-3 Keys and Displays ------------9
1-4 Menu Overview -------------11
1-5 Parameter Descriptions ----12
Page No
Chapter 2 InstallationChapter 2 Installation
2-1 Unpaking ----------------------19
2-2 Mounting ----------------------19
2-3 Wiring precautions ----------21
2-4 Power Wiring -----------------23
2-5 Sensor Installation -
Guidlines----------------------23
2-6 Sensor Input Wiring ---------24
2-7 Control Output Wiring ------24
2-8 Alarm Wiring -----------------27
Chapter 3 ProgrammingChapter 3 Programming
3-1 Lockout ------------------------28
3-2 Signal Input -------------------28
3-3 Control Outputs --------------29
3-4 Alarm ---------------------------34
3-5 Configure Display -----------35
3-6 Ramp ---------------------------36
3-7 Dwell Timer -------------------37
3-8 PV Shift ------------------------38
3-9 Digital Filter -------------------39
3-10 Failure Transfer -------------40
3-11 Auto-tuning ------------------41
3-12 Manual tuning --------------42
3-13 Manual Control -------------43
Chapter 4 Calibration --------45Chapter 4 Calibration
Chapter 5 Specifications -----46Chapter 5 Specifications
Page No
AppendixAppendix
A-1 Error Codes ------------------52
A-2 Warranty ----------------------53
www.comoso.com

Figures &TablesFigures &Tables Page No
Figure 1.1 Fuzzy Control Advantage ----------------------------------------------------------------6
Figure 1.2 Front Panel Description -----------------------------------------------------------------10
Figure 1.3 Display of Initial Stage -------------------------------------------------------------------10
Figure 2.1 Mounting Dimensions -------------------------------------------------------------------20
Figure 2.2 Lead Termination ------------------------------------------------------------------------22
Figure 2.3 Rear Terminal Connection --------------------------------------------------------------22
Figure 2.4 Power Supply Connections --------------------------------------------------------------23
Figure 2.5 Sensor Input Wiring ----------------------------------------------------------------------24
Figure 2.6 Output 1 Relay to Drive Load ----------------------------------------------------------24
Figure 2.7 Output 1 Relayto Drive Contactor ---------------------------------------------------25
Figure 2.8 Output 1 Pulsed Voltage to Drive SSR ---------------------------------------------25
Figure 2.9 Output 1 Linear Current ---------------------------------------------------------------26
Figure 2.10 Output 2 Relay to Drive Load --------------------------------------------------------26
Figure 2.11 Output 2 Relayto Drive Contactor --------------------------------------------------26
Figure 2.12 Alarm Output to Drive Load ----------------------------------------------------------27
Figure 2.13 Alarm Output to Drive Contactor ----------------------------------------------------27
Figure 3.1 Conversion Curve for Linear Type Process Value ---------------------------------29
Figure 3.2 Heat Only ON-OFF Control ------------------------------------------------------------30
Figure 3.3 Output 2 Deviation High Alarm --------------------------------------------------------33
Figure 3.4 Output 2 Process Low Alarm ----------------------------------------------------------33
Figure 3.5 RAMP Function ---------------------------------------------------------------------------36
Figure 3.6 Dwell Timer Function --------------------------------------------------------------------37
Figure 3.7 PV Shift Application ----------------------------------------------------------------------38
Figure 3.8 Filter Characteristics ---------------------------------------------------------------------39
Figure 3.9 Effects of PID Adjustment -------------------------------------------------------------44
Table 1.1 Display Form of Characters -------------------------------------------------------------11
Table 3.1 Heat-Cool Control Setup Value ---------------------------------------------------------29
Table 3.2 PIDAdjustment Guide --------------------------------------------------------------------43
Table A.1 Error Codes and Corrective Actions ---------------------------------------------------52
4
www.comoso.com

Chapter 1OverviewChapter 1Overview
1-1 General1-1 General
The Fuzzy Logic plus PID microprocessor-based controller series,
incorporate a bright, easy to read 4-digit LEDdisplay,indicating
process value or set point value. The FuzzyLogic technology
enables a process to reach a predetermined set point in the
shortest time, with the minimum of overshoot duringpower-up or
external load disturbance.
The TC/PC 24 is a 1/32 DIN sizepanel mount controller. These units
are powered by 11-26 or 90-250 VDC/VAC supply, incorporating a
2 amp control relay output as standard. Thesecond output can be
used as cooling control, an alarm or dwell timer. There are
six types of alarm plus a dwell timer can beconfigured for the
second output.The units are fully programmable for PT100 and
thermocouple types J,K, T, E, B, R, S, N, Lwith no need to modify the
unit. The input signal is digitized by using a18-bit Ato D converter.
Its fast sampling rate allows the unit to control fastprocesses.
By using proprietary Fuzzy modified PID technology, the control
loop will minimize the overshoot and undershoot in a shortest
time. The following diagram is a comparisonof results with and
without Fuzzy technology.
5
www.comoso.com

6
PID control with properly tuned
PID + Fuzzy control
Warm Up Load Disturbance
Set
point
Temperature
Time
High AccuracyHigh Accuracy
The series are manufactured with custom designedASIC(Application
Specific Integrated Circuit ) technology which contains a 18-bitA to
D converter for high resolution measurement ( true 0.1BF resolution
for thermocouple and PT100 ) and a 15-bit Dto Aconverter for linear
current or voltage control output. TheASIC technology provides
improved operating performance, low cost, enhanced reliability and
higher density.
Fast Sampling RateFast Sampling Rate
The sampling rate of the input Ato D converter reaches 5 times/second.
The fast sampling rate allows this series to control fast processes.
Fuzzy ControlFuzzy Control
The function of Fuzzy control is to adjust PID parameters from time to
time in order to make manipulation output value more flexible and
adaptive to various processes. The results is to enable a process to
reach a predetermined set point in the shortest time, with the minimum
of overshoot and undershoot during power-up or external load
disturbance.
Figure 1.1
Fuzzy Control
Advantage
Figure 1.1
Fuzzy Control
Advantage
www.comoso.com

Auto-tuneAuto-tune
The auto-tune function allows the user to simplifyinitial setup for a
new system. Aclever algorithm is provided to obtain an optimal set
of control parameters for the process, and itcan be applied either as
the process is warming up ( cold start )or as the process has been
in steady state ( warm start ).
Lockout ProtectionLockout Protection
According to actual security requirement, one of four lockoutlevels
can be selected to prevent the unit from beingchanged abnormally.
Bumpless TransferBumpless Transfer
Bumpless transfer allows the controller to continue to control by
using its previous value as the sensor breaks. Hence, theprocess
can be well controlled temporarily as if the sensoris normal.
Soft-start RampSoft-start Ramp
The ramping function is performed during power up as well as any
time the set point is changed. It can be ramping up or ramping
down. The process value will reach the set point with a predetermined
constant rate.
Digital FilterDigital Filter
A first order low pass filter with a programmable time constant is used
to improve the stability of process value. This is particularly useful in
certain application where the process value is too unstable to be read.
7
www.comoso.com

8
Power InputPower Input
4: 90 - 250 VAC,
50/60 HZ
5: 11 - 26 VAC or VDC
4: 90 - 250 VAC,
50/60 HZ
5: 11 - 26 VAC or VDC 0: None0: None
CommunicationsCommunications
1: Relay rated 2A/240VAC
2: Pulsed voltage to drive SSR,
5V/30mA
3: Isolated 4 - 20mA / 0 - 20mA
1: Relay rated 2A/240VAC
2: Pulsed voltage to drive SSR,
5V/30mA
3: Isolated 4 - 20mA / 0 - 20mA
Output 1Output 1
1: Standard Input
Thermocouple: J, K, T, E, B,
R, S, N, L
RTD: PT100 DIN, PT100 JIS
6: 4 - 20 mA
1: Standard Input
Thermocouple: J, K, T, E, B,
R, S, N, L
RTD: PT100 DIN, PT100 JIS
6: 4 - 20 mA
Signal InputSignal Input
TC 24-
PC 24-
TC 24-
PC 24-
1: Form A relay 2A/240VAC1: Form A relay 2A/240VAC
Output 2Output 2
1-2 Ordering Code1-2 Ordering Code
0: Red color0: Red color
Display ColorDisplay Color
www.comoso.com

1- 3 Keys and Displays1- 3 Keys and Displays
KEYPAD OPERATIONKEYPAD OPERATION
SCROLL KEY :
This key is used to select a parameter to be viewed or adjusted.
UP KEY :
This key is used to increase the value of selected parameter.
DOWN KEY :
This key is used to decrease the value of selected parameter.
RESET KEY :
This key is used to:
1. Revert the display to the process value or set point value
(if DISP is set with SP1).
2. Reset the latching alarm, once the alarm condition is
removed.
3. Stop the manual control mode, auto-tuning mode and calibration
mode.
4. Clear the message of auto-tuning error.
5. Restart the dwell timer when the dwell timer has been time out.
6. Enter the manual control menu when failure occurs.
ENTER KEY : Press for a minimum of 5 seconds.
Press for 5 seconds to:
1. Enter setup menu. The display shows .
2. Enter manual control mode when manual control mode
or is selected.
3. Enter auto-tuning mode when auto-tuning mode
is selected.
SCROLL KEY :
UP KEY :
DOWN KEY :
RESET KEY :
ENTER KEY :
presspress
9
www.comoso.com

Table1.1 Display Form ofCharactersTable1.1 Display Form ofCharacters
AEINSX
BFJOTY
CGKPUZ
cHLQV
?
DhMRW=
Figure 1.3 Front Panel DescriptionFigure 1.3 Front Panel Description
The diagram shows program no. 33
with version 24.
Display program code of the product
for 2.5 seconds.
Figure 1.4
Display of InitialStage
Figure 1.4
Display of InitialStage
Output 2
Indicator
Output 2
Indicator
Output 1
Indicator
Output 1
Indicator
O1
O2
C
10
O1
O2
C
www.comoso.com

1- 5 Menu Overview1- 5 Menu Overview
ADLO
ADHI
RTDL
CJLO
RTDH
CJHI
7.4 sec.
User menu *1User menu *1 Setup menu*1Setup menu*1 Calibration ModeCalibration Mode
Press for
5 seconds to
perform calibration.
*2
Applying these modes will
break the control loop
and change some of the
previous setting data.
Make sure that the
system will allow application
of these modes.
The flow chart shows a
complete listing of all
parameters. For actual
application the number of
available parameters
depends on setup
conditions, and should be
less than that shown in
the flow chart.
Release , press
again for 2 to 3 seconds, then
release to enter the
calibration menu.
*1:
*2:
2 sec.
LOCK
INPT
UNIT
DP
INLO
SP1L
INHI
SP1H
SHIF
FILT
DISP
OUT1
O1TY
O1FT
O1HY
CYC1
PB
TI
TD
OFST
RAMP
RR
OUT2
O2TY
O2FT
O2HY
CYC2
CPB
DB
ALMD
COMM
ADDR
BAUD
DATA
PARI
STOP
RELO
REHI
SEL1
SEL2
SEL3
SEL4
SEL5
SEL6
SEL7
SEL8
6.2 sec.
Value
Value
Value
Value
(DISP=PV)(DISP=PV) (DISP=SP1)(DISP=SP1)
SP1
SP2
H
C
A-T
Manual
Mode
Manual
Mode
5 sec.
Auto-tuning
Mode
Auto-tuning
Mode
or
PV SP1
Value
or PV
Value
Manual
Mode
Manual
Mode
5 sec.
5 sec.
INPT
UNIT
DP
PB
TI
TD
CYC1
ADDR
Value
Value
11
www.comoso.com

1-6 Parameter Descriptions1-6 Parameter Descriptions
Parameter
Notation Default
Value
Select parameters to be
locked
0 : No parameter
is locked
1 : Setup data are
locked
2 : Setup data and
User data except Set
point are locked
3 : All data are locked
LOCK 0
Parameter Description Range
0
1
2
3
4
5
6
:
:
:
:
:
:
:
T type thermocouple
E type thermocouple
B type thermocouple
R type thermocouple
S type thermocouple
J type thermocouple
K type thermocouple
7
13
8
14
9
10
11
12
N type thermocouple
L type thermocouple
PT 100 ohms DIN
curve
PT 100 ohms JIS
curve
4 - 20 mA linear
current input
0 - 20 mA linear
current input
0 - 1V linear voltage
input
:
:
:
:
:
:
:
:0 - 60 mV linear
millivolt input
INPT Input sensor selection 1
(0)
SP2
Set point for output 2
when output 2 performs
alarm function or dwell
timer
Low: -19999 High :45536
10.0 C
(18.0 F)
°
°
SP1 Set point for output 1 Low: SP1L High :SP1H
25.0 C
(77.0 F)
°
°
15
16
17
0 - 5V linear voltage
input
1 - 5V linear voltage
input
0 - 10V linear voltage
input
:
:
:
12 www.comoso.com

Parameter
Notation Default
Value
Parameter Description Range
UNIT Input unit selection
0
1
2
:
:
:
Degree C unit
Degree F unit
Process unit
0
(1)
DP Decimal point selection
0
1
2
3
1
:
:
:
:
No decimal
point
1 decimal digit
2 decimal digits
3 decimal digits
INLO
INHI
Input low sale value
Input high scale value
-19999
INLO+50
45486
45536
Low:
Low:
High:
High:
-17.8 C
( 0 F )
°
°
SHIF PV shift (offset) value -200.0 C
(-360.0 F)
°
°0.0
Low: 200.0 C
( 360.0 F)
°
°
High:
High:
93.3 C
(200.0 F)
°
°
0
1
2
3
4
5
6
7
8
9
FILT Filter damping time
constant of PV
0 second time
constant
0.2 second time
constant
0.5 second time
constant
1 second time
constant
2 seconds time
constant
5 seconds time
constant
10 seconds time
constant
20 seconds time
constant
30 seconds time
constant
60 seconds time
constant
:
:
:
:
:
:
:
:
:
:
2
SP1L Low limit of set point
value -19999 High: -17.8 C
(0 F)
°
°
SP1H High limit of set point
value SP1L High: 537.8 C
(1000 F)
°
°
45536
Low:
45536
Low:
13
www.comoso.com

Parameter
Notation Default
Value
Parameter Description Range
0
O1TY Output 1 signal type
: Relay output
: Solid state relay
drive output
: Solid state relay
output
: 4-20 mA current
module
0
1
2
3
4
5
6
7
0 - 20 mA current
module
0 - 1V voltage
module
0 - 5V voltage
module
1 - 5V voltage
module
80 - 10V voltage
module
:
:
:
:
:
O1FT Output 1 failure transfer
mode
Select BPLS ( bumpless
transfer ) or 0.0 ~ 100.0 % to
continue output 1 control
function as the unit fails, or
select OFF (0) or ON (1)
for ON-OFF control.
0
O1HY Output 1 ON-OFF control
hysteresis Low: 0.1 High: 50.0 C(90.0 F)°°
0.1 C
(0.2 F)
°
°
CYC1 Output 1 cycle time Low: 0.1 High: 90.0 sec. 18.0
PB Proportional band value 10.0 C
(18.0 F)
°
°
Low: 0 500.0 C
(900.0 F)
°
°
High:
High:
TI
TD
Integral time value
Derivative time value
0
0
100
25.0
Low:
Low:
1000 sec
360.0 sec
High:
High:
OFST Offset value for P control Low: 0 High: 100.0 % 25.0
Output 1 function 0
OUT1
0
1
Reverse (heating )
control action
Direct (cooling)
control action
:
:
DISP Normal display selection
: Display process
value normally
0
: Display set point 1
value normally
1
0
14 www.comoso.com

RR Ramp rate 0.0
Low: 0 500.0 C
(900.0 F)
°
°
High:
Parameter
Notation Default
Value
Parameter Description Range
OUT2 Output 2 function
0 : Output 2 No Function
2 : Deviation High Alarm
3 : Deviation Low Alarm
6 : Process High Alarm
7 : Process Low Alarm
8 : Cooling PID Function
2
O2TY Output 2 signal type 0
0
1
2
3
Relay output
Solid state relay
drive output
Solid state relay
output
4 - 20 mA current
module
:
:
:
:
4
5
6
7
0 - 20 mA current
module
0 - 1V voltage
module
0 - 5V voltage
module
1 - 5V voltage
module
80 - 10V voltage
module
:
:
:
:
:
O2FT
Select BPLS ( bumpless transfer )
or 0.0 ~ 100.0 % to continue
output 2 control function as the
unit fails, or select ON (0) or
OFF (1) for alarm and dwell timer
function.
Output 2 failure
transfer mode 0
RAMP Ramp function
selection
0 : No Ramp Function
2 : Use unit/hour as
Ramp Rate
1 : Use unit/minute as
Ramp Rate 0
1 : Dwell timer action
4 : Deviation band out of
band Alarm
5 : Deviation band in
band Alarm
15
www.comoso.com

Parameter
Notation Default
Value
Parameter Description Range
ALMD Alarm operation mode
0: Normal alarm action
1: Latching alarm action
2: Hold alarm action
3: Latching & Hold action
0
COMM Communication
function
0 : No communication
1 : Modbus RTU mode
protocol
1
Heating-cooling dead
band (negative value=
overlap) 0
Low: -36.0 High: 36.0 %
DB
CPB Cooling proportional
band value 100
Low: 50 High: 300 %
CYC2 Output 2 cycle time Low: 0.1 High: 90.0 sec. 18.0
O2HY
Output 2 hysteresis
value when output 2
performs alarm
function
Low: 0.1 High: 50.0 C
(90.0 F)
°
°
0.1 C
(0.2 F)
°
°
BAUD
:
:
:
:
:
:
:
Baud rate of digital
communication 2
0
1
2
3
4
5
6
2.4 Kbits/s baud rate
4.8 Kbits/s baud rate
9.6 Kbits/s baud rate
14.4 Kbits/s baud rate
19.2 Kbits/s baud rate
28.8 Kbits/s baud rate
38.4 Kbits/s baud rate
ADDR Address assignment of
digital communication Low: 1 High: 255
2:4-20mA retransmission
output
3:0-20mA retransmission
output
:0-5V retransmission
output
4
:1-5V retransmission
output
5
:0-10V retransmission
output
6
16 www.comoso.com

Parameter
Notation Default
Value
Parameter Description Range
DATA Data bit count of digital
communication
0 : 7 data bits
1 : 8 data bits 1
PARI Parity bit of digital
communication
0 : Even parity
1 : Odd parity
2 : No parity bit
0
STOP Stop bit count of digital
communication
0 : One stop bit
1 : Two stop bits 0
SEL1 Select 1st parameter for
user menu
0:No parameter selected
2
1:LOCK is put ahead
2:INPT is put ahead
3:UNIT is put ahead
5:SHIF is put ahead
6:PB is put ahead
7:TI is put ahead
4:DP is put ahead
8:TD is put ahead
11 :OFST is put ahead
14 :CYC2 is put ahead
17 :ADDR is put ahead
12 :RR is put ahead
13 :O2HY is put ahead
15 :CPB is put ahead
16 :DB is put ahead
10 :CYC1 is put ahead
9:O1HY is put ahead
RELO Retransmission low
scale value Low: -19999 High: 45536 0.0 C
(32.0 F)
°
°
REHI Retransmission high
scale value Low: -19999 High: 45536
100.0 C
(212.0 F)
°
°
17
www.comoso.com

Parameter
Notation Default
Value
Parameter Description Range
SEL2 Select 2nd parameter
for user menu 3
Same as SEL1
SEL3 Select 3rd parameter
for user menu 4
Same as SEL1
SEL4 Select 4th parameter
for user menu 6
Same as SEL1
SEL5 Select 5th parameter
for user menu 7
Same as SEL1
SEL6 Select 6th parameter
for user menu 8
Same as SEL1
SEL7 Select 7th parameter
for user menu 10
Same as SEL1
SEL8 Select 8th parameter
for user menu 17
Same as SEL1
18 www.comoso.com

Chapter 2 InstallationChapter 2 Installation
Dangerous voltages capable of causing death are
sometimes present in this instrument. Before installation or
beginning any cleaning or troubleshooting procedures the power
to all equipment must be switched off and isolated.Units
suspected of being faulty must be disconnected and removed to
a properly equipped workshop for testing and repair. Component
replacement and internal adjustments must be made by a
qualified maintenance person only.
Dangerous voltages capable of causing death are
sometimes present in this instrument. Before installation or
beginning any cleaning or troubleshooting procedures the power
to all equipment must be switched off and isolated.Units
suspected of being faulty must be disconnected and removed to
a properly equipped workshop for testing and repair. Component
replacement and internal adjustments must be made by a
qualified maintenance person only.
Do not use this instrument in areas under hazardous
conditions such as excessive shock, vibration, dirt, moisture,
corrosive gases or oil. The ambient temperature of theareas
should not exceed the maximum rating specified in Chapter 6.
Do not use this instrument in areas under hazardous
conditions such as excessive shock, vibration, dirt, moisture,
corrosive gases or oil. The ambient temperature of theareas
should not exceed the maximum rating specified in Chapter 6.
2-2 Mounting2-2 Mounting
2-1 Unpacking2-1 Unpacking
Upon receipt of the shipment remove the unitfrom the carton and
inspect the unit for shipping damage. If any damage due totransit,
report and claim with the carrier. Write down the model number,
serial number, and date code for future reference when
corresponding with our service center. The serial number (S/N) and
date code (D/C) are labeled on the box and thehousing of control.
Upon receipt of the shipment remove the unitfrom the carton and
inspect the unit for shipping damage. If any damage due totransit,
report and claim with the carrier. Write down the model number,
serial number, and date code for future reference when
corresponding with our service center. The serial number (S/N) and
date code (D/C) are labeled on the box and thehousing of control.
Make panel cutoutto dimension shownin Figure 2.1.Make panel cutoutto dimension shownin Figure 2.1.
Remove stains from this instrument using a soft,dry cloth.
Don't use harsh chemicals, volatile solvent such as thinner or
strong detergents to clean the instrument in order toavoid
deformation or discoloration.
Remove stains from this instrument using a soft,dry cloth.
Don't use harsh chemicals, volatile solvent such as thinner or
strong detergents to clean the instrument in order toavoid
deformation or discoloration.
This instrument is protected throughout by Double
Insulation . To minimize the possibility of fire or shock, do
not expose this instrument to rain or excessive moisture.
This instrument is protected throughout by
. To minimize the possibility of fire or shock, do
not expose this instrument to rain or excessive moisture.
Double
Insulation
19
Remove bothmounting clamps andinsert the controllerinto
panel cutout. Reinstall the mountingclamps. Gently tighten
the screws inthe clamp untilthe controller frontpanel is fitted
snugly in thecutout.
Remove bothmounting clamps andinsert the controllerinto
panel cutout. Reinstall the mountingclamps. Gently tighten
the screws inthe clamp untilthe controller frontpanel is fitted
snugly in thecutout.
www.comoso.com

Figure 2.1 Mounting DimensionsFigure 2.1 Mounting Dimensions
98.0mm
Panel
10.0mm
12.5mm
SCREW
MOUNTING
CLAMP
22.2 +0.3
45 +0.5
_0
_0
20 www.comoso.com
This manual suits for next models
1
Table of contents