
8
PN 240010964 Rev. L [10/01/2021]
Chart 1- United Technologies 1158-120 (UMLA)
Dip Switch Position Blower Delay Times
1 2 3 4 On Seconds O Minutes
O O 30
On O 60
O On 90
On On 120
O O 2
On O 3
O On 4
On On 6
furnaces are manufactured as direct vent units. Refer to Direct
Vent Installation, Operation and Maintenance Manual, part number
240011300, included with direct vent furnace, for details.
Direct venting requires use of specic oil burners, Beckett NX or
Riello 40BF3 or 40BF5.
Refer to Appendix A, Tables A-2 and A-4.
13a. Fan Timer Board And Limit Control (UMLA)
[See Figure 5, page 16]
Electronic Fan Timer integrates control of burner and
circulator fan operations. Control is central wiring point for
most of furnace electrical components.
• United Technologies 1158-120 has an adjustable fan on time
set by selecting dipswitch combination displayed in Chart
1. Fan on delay can be set at 30, 60, 90 or 120 seconds.
Provides a delay between burner ignition and blower start-up
to eliminate excessive ow of cold air when blower comes
on. Manufacturer recommended fan on delay is 30 seconds
for UML100A models and 60 seconds for UML65/80/90A
models.
• United Technologies 1158-120 has an adjustable fan o time
of 2, 3, 4 or 6 minutes as displayed in Chart 1. Fan o delay
time starts when burner motor is de-energized at end of call
for heat. Blower shutdown is delayed to remove any residual
heat from heat exchanger. Manufacturer recommended fan
o delay is 3 minutes.
• Electronic fan timer board works in conjunction with snap
disc limit controls, performing a safety function, shutting o
burner if furnace over-heats.
• Limit control is thermally operated and automatically
resets. Limit control is factory installed, pre-set and is not
adjustable.
13b. Fan Timer Board And Limit Control
(UMLVA) [See Figure 6, page 16]
United Technologies 1168-1 ECM tap board has adjustable fan on/
o delay and airow settings that must be adjusted in accordance
with furnace input rating (nozzle size). Refer to Table A-9 for ECM
blower set-up.
14. Electrical Connections
• Furnace is listed by Canadian Standards Association under
NRTL (North American) Standard.
• All eld wiring shall conform to CAN/CSA C22.1 Canadian
Electrical Code, Part 1, and by local codes, where they
prevail.
• United States, wiring shall conform to National Fire
Protection Association NFPA-70, National Electrical Code, and
with local codes and regulations.
• Wire furnace to separate dedicated circuit in main electrical
panel.
• Suitably located circuit breaker can be used as service
switch, separate service switch is advisable.
• Service switch is necessary if circuit breaker is close to the
furnace, or furnace is located between circuit breaker and
entry to furnace room.
• Clearly mark service switch. Install in accessible area
between furnace and furnace room entry. Locate so as
to reduce possibility it can be mistaken as light switch or
similar device.
• Power requirement for all UML models is: 120 VAC, 1 Ø, 60
Hz., 12A.
• Accessory equipment such as electronic air cleaners and
humidiers may be included on furnace circuit.
• Accessories requiring 120 VAC power sources such as
electronic air cleaners and humidier transformers may be
powered from electronic fan timer board where provisions
have been made for connections, but should have their own
controls.
11. Barometric Damper Control
Barometric damper control, also known as draft regulator, is used
on conventional chimney venting only. Control automatically
maintains constant negative pressure. Ensures proper pressures
are not exceeded. If chimney does not develop sucient draft,
draft control does not function properly.
• Install draft regulator in same room or enclosure as furnace.
Draft regulator should not interfere with combustion air
supplied to the burner.
• Locate control near furnace ue outlet.
• Install per instructions supplied with regulator.
• Set breech draft to -0.02 in. w.c.
12. Optional Direct Venting
Certain UMLA and UMLVA
Manufacturer recommends breech draft of -0.02 in. w.c.
Flue pipe must not pass through any oor or ceiling, may pass
through a wall where suitable re protection provisions have been
installed.
• Canada, refer to CAN/CSA B-139 for rules governing the
installation of oil burning equipment.
• United States, refer to NFPA 31 for regulations governing the
installation of oil burning equipment.
See appendix A for burner set-up.
• If limit control opens with United Technologies 1158-120
electronic fan control, circulating fan will energize. When
limit closes, fan o timer begins. At the end of fan o time
cycle burner is energized, initiating normal burner cycle.