esera automation 11218 User manual

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de 11218 V2.0 R1.0 Manual Page 1 of 7
Art. No. 11218
User Guide
Binary output / Dual switching module
for 1-Wire Bus system
Two changeover relays with 10A continuous power
Control inputs for button and 1-Wire Bus
LED display for activated relays
Switching of direct or alternating current consumers,
e. g. lighting, heating or sockets
Top-hat rail housing for control cabinet installation
Easy software-based control
Low space requirement in control cabinet
Easy to assemble
1 Introduction
Before you start to install the Dual Switch Module and put the device into operation, please read this operating
manual through to the end, especially the section on safety instructions.
2 Product description
With the Dual Digital switching module, direct and alternating current consumers with a capacity of up to 10A
continuous current can be switched. It is also possible to control motors, such as roller shutter drives.
The switch module can be controlled directly by an external switch (e.g. light switch) or by a switch on the top of
the module, also independently of the 1-Wire interface. For this switching function by push-button, it is sufficient if
the 12V supply voltage is applied. This ensures extremely high reliability, e.g. for switching lights, socket circuits or
other important consumers, even if a central control unit/software fails.
The installed high-performance relays can be operated in a special power saving mode to reduce the power
consumption. This can reduce the current consumption of the two output relays by approx. 40 %.
To supply the switching module we recommend the use of one of our 1-Wire Hub modules.
3 Energy-saving mode
The Dual Switching Module has a modern energy saving mode for the output relays. The energy saving mode
can be switched on or off via key 1 (module top side). The energy saving mode is deactivated at delivery. The
selected setting remains permanently stored, even after a power interruption. Depending on the function, quiet
noises may be audible with active output relays in energy saving mode. If these are disturbing, e.g. when
operating in the living room, you should switch to normal mode.

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de 11218 V2.0 R1.0 Manual Page 2 of 7
Function button 1 Module top side
Briefly press button: Switching the output relay
Press button for 2 seconds: Changing energy mode on/off
Power saving mode on: LED1 flashes twice briefly
Normal operation mode: LED1 lights up for 2 seconds
Function button 2 Module top side
Briefly press button: Switching output relay
4 Technical data
Switching channels: 2, changeover relay (NO and NC contact)
Switching voltage: maximum 250V direct power voltage or alternative power voltage
Switching power/Power: maximum 10A continuous current, maximum 2200VA continuous current at Ohm
resistive load. minimum load 10mA
In case of capacitive or inductive loads, appropriate additional wirings, e.g. spark
suppressor capacitors must be considered. Maximum power and output will be reduced.
Fuses: External preliminary fuse with 10A recommended
Data interface: 1-Wire Bus (12V, data and ground),
1-Wire component: DS2413 (Dual I/O)
Supply voltage: 12VDC (+/-10 %)
Power consumption 12V:Idle mode, no output relay active: approx..6mA
Both output relays are active: approx. 75mA in normal mode, approx. 38mA in
energy-saving mode
Button interface: 2, input for button (make contact), no external power allowed
Connection: Screw terminals (up to 2,5qmm wire cross section)
5 Ambient conditions:
Temperature, operation: 0 °C up to +50 °C
Air humidity: 10 –92 % (non-condensing)
Measurements: 35 x 90 x 70mm (WxHxD)
Protection class: II
Protection type: IP20
Insulation strength: 500VAC output to 1-Wire Bus, 250VAC output to output
6 Connection plan
Connection plan is available in the webshop
as own document
Note: A back-up fuse of 10A must be
provided before terminals 8 and 11
6.1 Option: Changeover relay, switch
Connection Top side:
7 = Relay 1, normally open contact / NO
8 = Relay 1, input
9 = Relay 1, normally closed contact / NC
10 = Relay 2, normally closed contact / NC
11 = Relay 2, input
12 = Relay 2, normally open contact / NO
1-Wire Bus
Module bottom side:
1 = GND (ground)
2 = 1-Wire data line
3 = +12V power
4 = GND (ground)
5 = Button interface 1 external
6 = Button interface 2 external

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de 11218 V2.0 R1.0 Manual Page 3 of 7
Art. No. 11218
7 Connection Example
The following example shows 1-Wire Controller or 1-Wire Gateway, Dual Digital Output and 8-Fold Digital Input:

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de 11218 V2.0 R1.0 Manual Page 4 of 7
8 Conformity
EN 50090-2-2,
EN 61000-4-2, ESD
EN 61000-4-3, HF
EN 61000-4-4, Burst
EN 61000-4-5, Surge
EN 61000-6-1, Interference immunity
EN 61000-6-3, interference radiation
RoHS
9 LED display and button
The module has two LED displays.
Display
Designation
LED Function
LED Green
Output 1
- LEDs flash at system start-up
- LED is lit when an output relay is active
- Display of the energy mode
LED Green
Output 2
- LEDs flash at system start-up
- LED is lit when an output relay is active
Button
Designation
Button function
1 internal
Output 1 On/Off
Button 1 has two different functions
- Changeover of relay 1
- Energy-saving mode on/off
For details refer to chapter „Energy-saving mode“
2 internal
Output 2 On/Off
Changeover of relay 2
1 external
Output 1 On/Off
Changeover of relay 1
2 external
Output 2 On/Off
Changeover of relay 2
10 Button and 1-Wire Interfaces
In addition to the buttons on the top side of the module, the module has an external button-interface to connect
two external buttons (make contact). This means, light switches can be connected to the external button interface
to control on/off light commands. For connection regular light switches of all manufacturers can be used.
Within the module, a µ-controller takes over the query of the buttons, the 1-Wire interface and the control of the
relays. Flank control is used to query buttons and 1-Wire component.
The switching status of the relays can be set via the external and internal buttons. Relays can also be set by the
1-Wire Interface.
The state of the relay that has been triggered by the button cannot be read by the 1-Wire interface.
Button 1 on the module has a double function. For details refer to chapter „Energy-saving mode“.
External and internal control inputs:
Button interface, external button 1
Button interface, external button 2
Module top side, button 1 internal / Mode: Energy saver mode/Normal mode
Module top side, button 2 internal
1-Wire Component, DS2413 channel 0
1-Wire Component, DS2413 channel 1
No voltage source may be connected to the external push-button interface. The connecting cables between
module and push button must be laid isolated from other cables. 5V DC voltage is applied to the connections of
the pushbutton interface when not in use.
11 Software / Control
The module is controlled by 1-wire commands for the DS2413 module.

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de 11218 V2.0 R1.0 Manual Page 5 of 7
Art. No. 11218
12 Control via 1-Wire Controller / 1-Wire Gateway
The 1-Wire interface of the Dual Digital Switch Module is controlled by standard commands for the DS2413
module. Outputs switched by the pushbutton interface or in manual mode cannot be read back by the 1-wire
interface. The dual digital switching module can be easily controlled by a 1-wire controller / 1-wire gateway. For
this purpose the following two commands are available.
12.1 Switching of an output relay
To switch a relay output, use the following command to set only the output selected to 0 or 1.
Command: SET,OWD, OUT,OWD-Number, Output, Value
Example: set,owd,out,2,1,1 => OWD Number 2, output 2 will be switched to “on”.
After switching the output latest status will be output as confirmation.
12.2 Switching of all output relays (Port)
Some applications require switching all outputs with one command.
The following command sets both outputs of the 1-Wire device to a desired state. The 1-wire controller / 1-wire
gateway handles the command adaptation to the connected Dual digital switching module.
Output value is displayed as a decimal value 0-3. Each relay output has a significance, which is added up.
Output value 0 = all off, 1 = output 1 active, 2 = output 2 active
If output 1 and 2 should be switched to "active", add up the output values
Example: Output value: 1 + 2 = 3
Permitted output values for 1-Wire digital outputs: 0 - 3
Command: SET,OWD, OUTH,OWD-Number, Output Value
Example: set,owd,outh,2,3 => OWD Number 2, outputs 1 and 2 will be switched to „Active“
After switching the output latest status will be output as confirmation.
12.3 Data output 1-Wire Controller / 1-Wire Gateway
For the Dual Switch Module the following data are output to display relay status.
Data output:
1_EVT|12:27:40
1_OWD2_1|0 => controller no._module no._data set|status output 1
1_OWD2_2|1 => controller no._module no._data set|status output 2
Further information for options and commands can be found in the latest available documentation for
1–Wire Controller / 1–Wire Gateway.
13 Operating conditions
The operation of the assembly group can take place only on condition of observing the required voltage and the
ambient conditions. The operating position of the device is irrelevant. The device is meant to be used in dry
areas free of dust.
Should condensed water build up within the sensor, an acclimatization period of at least 2 hours must be met.
The components can be operated only under the supervision of an electrically skilled person. Assembly groups
and components do not belong into the hands of children
In industrial facilities, the accident prevention regulations of the federation of industrial professional associations
for electrical installations and equipment must be observed. Do not operate the components in an environment
with inflammable gases, vapors or dusts or in an environment where such gases, vapors or dusts may occur.
14 Assembly
The mounting place must be protected against moisture. The module may only be used in dry indoor rooms or in
protected outside areas. The device is designed for fixed installation within a switching cabinet.

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de 11218 V2.0 R1.0 Manual Page 6 of 7
15 Disposal information
Do not dispose of the device in household waste! Electronic devices must be disposed of in
accordance with the directive on waste electrical and electronic equipment via the local collection
points for waste electronic equipment!
16 Safety Instructions
When using products that come into contact with electrical voltage, the valid VDE regulations must be
observed, especially VDE 0100, VDE 0550/0551, VDE 0700, VDE 0711 and VDE 0860
During final works and wiring works power has to be de-connected.
Before opening the device, always unplug and make sure that the unit is disconnected from the mains.
Components, modules or devices may only be put into service if they are mounted in a contact proof housing. During
installation they must not have power applied.
Tools may only be used on devices, components or assemblies when it is certain that the devices are disconnected from
the power supply and electrical charges stored in the components inside the device have been discharged.
Live cables or wires to which the device or an assembly is connected, must always be tested for insulation faults or breaks.
If an error is detected in the supply line, the device must be immediately taken out of operation until the faulty cable has
been replaced.
When using components or modules it is absolutely necessary to comply with the requirements set out in the
accompanying description specifications for electrical quantities.
If the available description is not clear to the non-commercial end-user what the applicable electrical characteristics for a
part or assembly are, how to connect an external circuit, which external components or additional devices can be
connected or which values these external components may have, a qualified electrician must be consulted.
It must be examined generally before the commissioning of a device, whether this device or module is basically suitable for
the application in which it is to be used.
In case of doubt, consultation with experts or the manufacturer of the components used is absolutely necessary.
For operational and connection errors outside of our control, we assume no liability of any kind for any resulting damage.
Kits should be returned without their housing when not functional with an exact error description and the accompanying
instructions. Without an error description it is not possible to repair the device. For time-consuming assembly or
disassembly of cases charges will be invoiced.
During installation and handling of components which later have mains potential on their parts, the relevant VDE
regulations must be observed.
Devices that are to be operated at a voltage greater than 35 VDC / 12mA, may only be connected by a qualified electrician
and put into operation.
Commissioning may only be realized if the circuit is built into a contact proof housing.
If measurements with an open housing are unavoidable, for safety reasons an isolating transformer must be installed
upstream or a suitable power supply can be used.
After installing the required tests according to DGUV / regulation 3 (German statutory accident insurance,
https://en.wikipedia.org/wiki/German_Statutory_Accident_Insurance)must be carried out.
17 Warranty
ESERA GmbH guarantees that the goods sold at the time of transfer of risk to be free from material and workmanship
defects and have the contractually assured characteristics. The statutory warranty period of two years begins from date of
invoice. The warranty does not extend to the normal operational wear and normal wear and tear. Customer claims for
damages, for example, for non-performance, fault in contracting, breach of secondary contractual obligations,
consequential damages, damages resulting from unauthorized usage and other legal grounds are excluded. Excepting to
this, ESERA GmbH accepts liability for the absence of a guaranteed quality resulting from intent or gross negligence.
Claims made under the Product Liability Act are not affected.
If defects occur for which the ESERA GmbH is responsible, and in the case of replacement goods, the replacement is
faulty, the buyer has the right to have the original purchase price refunded or a reduction of the purchase price.
ESERA GmbH accepts liability neither for the constant and uninterrupted availability of the ESERA GmbH or for technical
or electronic errors in the online offer.
We are constantly developing our products further and reserve the right to make changes and improvements to any of the
products described in this documentation without prior notice. Should you require documents or information on older

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de 11218 V2.0 R1.0 Manual Page 7 of 7
Art. No. 11218
18 Trademarks
All mentioned designations, logos, names and trademarks (including those which are not explicitly marked) are
trademarks, registered trademarks or other copyright or trademarks or titles or legally protected designations of their
respective owners and are hereby expressly recognized as such by us. The mention of these designations, logos, names
and trademarks is made for identification purposes only and does not represent a claim of any kind on the part of ESERA
GmbH on these designations, logos, names and trademarks. Moreover, from their appearance on ESERA GmbH
webpages it cannot be concluded that designations, logos, names and trademarks are free of commercial property rights.
ESERA and Auto-E-Connect are registered trademarks of ESERA GmbH.
19 Contact
ESERA GmbH
Adelindastrasse 20
87600 Kaufbeuren
GERMANY
Tel.: +49 8341 999 80-0
Fax: +49 8341 999 80-10
www.esera.de
WEEE-Number: DE30249510
Table of contents
Other esera automation I/O System manuals

esera automation
esera automation 11208 User manual

esera automation
esera automation 11228 V2 User manual

esera automation
esera automation 11216 User manual

esera automation
esera automation 11229 V2 User manual

esera automation
esera automation 11216 User manual

esera automation
esera automation Auto-E-Connect 11230 User manual
Popular I/O System manuals by other brands

WAGO
WAGO 750-344 manual

Measurement Computing
Measurement Computing PCI-DAS64/M1/16 user guide

Allen-Bradley
Allen-Bradley 1734-OE4C installation instructions

Aaeon
Aaeon GENE-BSW5 user manual

Measurement Computing
Measurement Computing PCI-DAS4020/12 user guide

Maple Systems
Maple Systems HMC7-MIO-08 Quick start guides