esera automation 11216 User manual

* if the sensor or actuator supports Auto-E-Connect. For details, please refer to the operating instructions of the sensor or actuator.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de 11216 V5.0 R1.0 Manual Page 1 of 9
Art. No. 11216
User Guide
8-fold Digital Input for 1-Wire Bus
8 inputs for 10-30V DC signals
e.g. for switches, reed contacts or other
digital sensors
LED displays for input status,
and supply voltage
Inputs can be activated by manual operation
DIN rail housing for control cabinet installation
Connection via screw terminals
Simple software integration
1-Wire interface DS2408 commands
Housing color green (RAL 6020)
Note
Before you start assembling the device and put it into operation, read this operating manual through
to the end at your leisure, especially the section on safety instructions.

*if the sensor or actuator supports Auto-E-Connect. For details, please refer to the operating instructions of the sensor or actuator.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de 11216 V5.0 R1.0 Manual Page 2 of 9
1 Product description
The 8-fold Digital Input Module can be used to query the status of 8 switches, reed contacts or all kinds of digital
sensors. The LED indicators on the front panel show the status of the switch inputs. When the input voltage is
present, the respective LED indicator lights up.
To protect the inputs additionally against disturbances, the module has filters with a delay of only 30ms.
Each input can be set manually by pushbutton for test purposes, maintenance or development.
The inputs are isolated from the 1-Wire Network by Optocouplers. This allows very long connection cables
between the module and the sensors without interfering with the 1-Wire Bus.
In addition, the isolation between switch inputs and 1-Wire Network provides increased safety.
For the operation of the Module only a 2V supply voltage is necessary. For this, we recommend the use of one
of our 1-Wire Hub module.
2 Technical Data
Number and Type
8 inputs for DC voltage signals 10 - 30VDC
Input voltage
max. 30 VDC, max.8mA, low level: <5V high level 10-30V
Filter
Software filter against switch bounce (30 ms delay)
LED displays
10 LEDs (Power LED, Status LED, 8 x Input)
Input LED lights up at status high of the 1-Wire DS2408 interface
Data interface
1-Wire Bus (12V, Data and ground), DS2808 command set
Auto-E-Connect
Support
Level I to II
Operating voltage
12VDC (+/-10%)
Current
consumption 12V
12V: max. 40mA, all inputs active
Internal fuses
no changeable fuses available
Insulation voltage
min. 500VAC against 1-Wire Bus
Connection
srew terminals (up to 2,5qmm cable cross section)
3 Ambient conditions
Temperature,
Operation
-10°C to +50°C
Air humidity
10 - 92% (non condensing)
Dimensions
32 x 90 x 70mm (WxHxD)
Protection class
II
Protection system
IP20
Auto-E-Connect
Support
Level I to II
Insulation
resistance
500VAC inputs to 1-Wire Bus
Note
Basics and Tips on the 1-Wire Bus system can be found in the ESERA Online Shop under
1-Wire Basics or please refer to our eBook in the shop under Training/Documentation.
Note
Only a 12V supply voltage is required to operate the module.
For power supply we recommend a 1-Wire Hub device. Input voltages above 30V can cause permanent
damage to the module.

* if the sensor or actuator supports Auto-E-Connect. For details, please refer to the operating instructions of the sensor or actuator.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de 11216 V5.0 R1.0 Manual Page 3 of 9
Art. No. 11216
4 Auto-E-Connect Support
The 8-fold Switching Module supports Auto-E-Connect Level I and II.
1 Auto-E-Connect System
With the launch of the ECO controllers, the ESERA Auto-E-Connect® 1-Wire Plug and Play system for the
1-Wire Bus is now introduced and supported.
This means that fully automatic configuration of the 1-Wire Devices* (sensors and actuators) on the
1-Wire Bus is now possible.
It is optimised for commercial and industrial applications and enables significant added value beyond sensor
and chip data.
The Auto-E-Connect function is built up in three levels. Currently there are Level I, Level II and Level III
available.
With Auto-E-Connect Level III, fully automatic configurations of the 1-Wire Devices on the
1-Wire Bus are possible. It is optimised for industrial and IoT applications and enables significant added
value beyond sensor and chip data.
With the Auto-E-Connect function, ESERA Devices are recognised fully automatically, suitable libraries are
started and ready-formatted data is output.
The Auto-E-Connect functionality will be available for the ECO Controller and ESERA-Station 200 Pro from
2021.
Auto-E-Connect Level I
OWD Detect: detection of new sensors* and actuators* and automatic start of adapted libraries.
Auto-E-Connect Level II
Visualisation product data: reading out and visualising of the Auto-E-Connect and manufacturer data of
sensors* and actuators*, e.g. article number, date of manufacture, firmware and hardware version.
Auto-E-Connect Level III
Extended Plug and Play System for 1-Wire Bus
oPre Configuration: The OWD number for the next installation can be written to the 1-Wire Device*.
oAutomatic Positioning: The Device* logs on to each ECO Controller with Auto-E-Connect III with the new
desired OWD number. This automatic login works up to the maximum possible OWD number of the
ECO Controller.
oSensorfinder Function: The ECO Controller can activate a status LED within the ESERA 1-Wire Pro
sensors*. The status LED flashes or lights up continuously for a certain time. This makes it much easier to
detect a device in a 1-Wire Network. Faster detection saves a lot of time and therefore money when
searching for a 1-Wire Device.
oClasses Assignment: ESERA 1-Wire Devices are assigned to OWD classes with the same properties. This
assignment enables fully automatic visualisation and data evaluation in control systems. A class list is
available from ESERA.
For further information on the ESERA Auto-E-Connect system, please refer to the ESERA Website and the
ESERA Config Tool 3.
Auto-E-Connect is registered by ESERA GmbH as a German and European Patent.

*if the sensor or actuator supports Auto-E-Connect. For details, please refer to the operating instructions of the sensor or actuator.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de 11216 V5.0 R1.0 Manual Page 4 of 9
5 Conformity
EN 50090-2-2
EN 61000-4-2, ESD
EN 61000-4-3, HF
EN 61000-4-4, Burst
EN 61000-4-5, Surge
EN 61000-6-1, Interference immunity
EN 61000-6-3, Interference radiation
RoHS
6 Connection diagram
The connection diagram is available in the
Shop
Connection top side:
inputs
7 = input 1
8 = input 2
9 = input 3
10 = input 4
11 = input 5
12 = input 6
6 = input 7
5 = input 8
4 = GND/ground input
Connection bottom side:
1-Wire Bus
1 = GND (1-Wire ground)
2 = 1-Wire
3 = +12V voltage
Note
The module may only be operated at the voltages and under the ambient conditions specified for it. The
operating position of the device is arbitrary.
The modules may only be commissioned by a qualified electrician.
For further information on the operating conditions, see the following instructions under "Operating
conditions".
Note on switching loads
When switching capacitive or inductive loads, very strong arcs can occur at the relay contacts, which can
cause interference with the logic of the switching module, the ECO Controller and other devices. In order to
extinguish these arcs or to dampen the resulting disturbances to such an extent, appropriate additional
circuits, such as spark quenching capacitors, and/or varistors per switching contact and free-wheeling
diodes per relay, must be provided.
For details on spark quenching, see Wikipedia: https://de.wikipedia.org/wiki/Funkenl%C3%B6schung
The max. switching current and max. switching capacity are reduced for capacitive or inductive loads.

* if the sensor or actuator supports Auto-E-Connect. For details, please refer to the operating instructions of the sensor or actuator.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de 11216 V5.0 R1.0 Manual Page 5 of 9
Art. No. 11216
8 Connection example
Here is a connection example with 1-Wire Controller or 1-Wire Gateway, Dual Digital Output and 8-fold Digital
Input.

*if the sensor or actuator supports Auto-E-Connect. For details, please refer to the operating instructions of the sensor or actuator.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de 11216 V5.0 R1.0 Manual Page 6 of 9
9 LED display and operating elements
The module has a green LED for each input channel, which lights up when a DC voltage greater than 10VDC is
applied. Input signals can be simulated via the two buttons. This can be helpful in case of service, during tests or
during commissioning. For the simulation, the LED displays and pushbuttons each have double functions.
Display
Designation
Function
LED Green
PWR
the LED has a double function
lights up permanently, display for 12V power supply
flashes in Manual Mode
LED Status
Status
the LED has a double function
flashes when changing the input status of all inputs
Manual Mode: input on/off for the selected channel
LED Green
(8x)
1 –8
Status display of the inputs
LED lights up when a signal voltage is applied to the corresponding
input.
LED flashes if the input was set via the Manual Mode.
Pushbutton
Designation
Function
Pushbutton 1
MAN/Select
the pushbutton has a double function
press for 2 seconds, activation of Manual Mode for setting the inputs
after that, selection of the input to be set by pressing briefly
Pushbutton 2
ON/OFF
the pushbutton has a double function
input on/off in Manual Mode by pressing briefly
press for 2 seconds, deactivates Manual Mode for all manually set
inputs
10 Software / Control
The 1-Wire interface of the module is read out via 1-Wire command for the 1-Wire module DS2408.
The module is a standard module for very many systems and software programs, such as ESERA-Station 200,
PowerDog, SmartOne, FHEM, OWFS, IP-Symcon, etc
10.1 Data output 1-Wire Controller / 1-Wire Gateway
The 1-Wire interface of the 8-fold Digital Input is read by standard commands for the module DS2408.
For the 8-fold Digital Input, the following data is output for the binary / digital inputs. The input value is output as
decimal value 0-254 and in a second data set with binary display (0 and 1). Each input has a valence, which is
added up in each case.
Input value:
Input 1 = 1, input 2 = 2, input 3 = 4, input 4 = 8, input 5 = 16, input 6 = 32, input 7 = 64,
input 8 = 128.
Via the Config-Tool you can assign the article number 11216 to the DS2408 module. After assigning the article
number, you will receive the following formatted output.
Data output:
1_OWD1_1|8 => Controller No._module No._Data set | decimal value input
1_OWD1_2|10000000 => Controller No._module No._Data set | binary representation input
Further information about the possibilities and commands can be found in the current documentation 1-Wire
Controller /1-Wire Gateway.

* if the sensor or actuator supports Auto-E-Connect. For details, please refer to the operating instructions of the sensor or actuator.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de 11216 V5.0 R1.0 Manual Page 7 of 9
Art. No. 11216
11 1-Wire Network, Cabling
The special feature of the 1-Wire system is the "BUS technology". All devices (sensors and actuators) are
operated in parallel on a three-wire line, which is used for both power supply and data communication. The
1-Wire Bus system joins the list of other successful bus systems such as CAN or Modbus RTU. All of the
installation principles recommended for these are also applicable and appropriate to 1-Wire.
The maximum size of a 1-Wire network is determined by various factors. These are mainly:
- Total cable length and cable type
- Number of 1-Wire devices
- Type of cable installation (topology)
- Number and design of cable connectors (unnecessary connection transitions should be avoided)
All factors in total are summarised and designated as 1-Wire Bus load. Each increase in a factor increases the
total 1-Wire Bus load for the 1-Wire Controller and thus reduces the maximum network size.
According to our many years of experience and a lot of feedback from customers, the following conservative
recommendation can be made:
- Maximum cable length 50 -120m
- Number of 1-Wire devices no more than 20 -22 pieces
- As linear a topology as possible without T-junctions
The topology in particular plays a major role. If possible, it should be installed in a linear topology. The linear
topology can be compared like pearls on a pearl necklace. The data line should be laid from one device to the
next without T-joints.
Furthermore, the type of cable used can also be mentioned here. We recommend for the cabling
CAT5 or CAT6 network cable. It is also possible to use J-Y(St)Y telephone cables and KNX cables. Longer cable
runs are possible with CAT5 versus CAT7 cables.
With twisted pair cables, a longer connection length can be achieved in an undisturbed environment, as the
capacitive bus load is lower. A total length of 50 m and more can be easily achieved without additional measures.
In disturbed, commercial and industrial environments, the cable should always be shielded in order to increase
the "robustness" or interference sensitivity of the system.
12 Operating conditions
The module may only be operated at the voltages and under the ambient conditions specified for it. The operating
position of the device is arbitrary. The device is intended for use in dry and dust-free rooms.
If condensation forms, an acclimatization time of at least 2 hours must be allowed.
Assemblies and components do not belong in the hands of children!
The modules may only be put into operation under the supervision of a qualified electrician.
In commercial facilities, the accident prevention regulations of the German Federation of Institutions for Statutory
Accident Insurance and Prevention for electrical systems and equipment must be observed.
Do not operate the module in an environment where flammable gases, vapors or dusts are present or may be
present.
Note
The above statements on 1-Wire are hints and tips and do not describe any product property or represent
any guaranteed product property of this article and the 1-Wire Controllers.
Information on the basics and tips on the 1-Wire Bus system can also be found in the ESERA Online Shop
under https://www.esera.de/1-wire-grundlagen/

*if the sensor or actuator supports Auto-E-Connect. For details, please refer to the operating instructions of the sensor or actuator.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de 11216 V5.0 R1.0 Manual Page 8 of 9
13 Assembly
The mounting location must be protected against moisture. The device may only be used in dry indoor areas and
in protected outdoor areas.
The device is intended for mounting inside a control cabinet as a stationary device.
14 Disposal note
Do not dispose of the unit in household waste! Electronic devices must be disposed of at
the local collection points for electronic devices in accordance with the Directive on
Waste Electrical and Electronic Equipment!
15 Safety instructions
When using products that come into contact with electrical voltage, the valid VDE regulations must be observed, especially
VDE 0100, VDE 0550/0551, VDE 0700, VDE 0711 and VDE 0860
All final or wiring work must be carried out with the power turned off.
Before opening the device, always unplug or make sure that the unit is disconnected from the mains.
Components, modules or devices may only be put into service if they are mounted in a contact proof housing. During
installation they must not have power applied.
Tools may only be used on devices, components or assemblies when it is certain that the devices are disconnected
from the power supply and electrical charges stored in the components inside the device have been discharged.
Live cables or wires to which the device or an assembly is connected, must always be tested for insulation faults or
breaks.
If an error is detected in the supply line, the device must be immediately taken out of operation until the faulty cable
has been replaced.
When using components or modules it is absolutely necessary to comply with the requirements set out in the
accompanying description specifications for electrical quantities.
If the available description is not clear to the non-commercial end-user what the applicable electrical characteristics for
a part or assembly are, how to connect an external circuit, which external components or additional devices can be
connected or which values these external components may have, a qualified electrician must be consulted.
It must be examined generally before the commissioning of a device, whether this device or module is basically
suitable for the application in which it is to be used.
In case of doubt, consultation with experts or the manufacturer of the components used is absolutely necessary.
For operational and connection errors outside of our control, we assume no liability of any kind for any resulting
damage.
Kits should be returned without their housing when not functional with an exact error description and the
accompanying instructions. Without an error description it is not possible to repair. For time-consuming assembly or
disassembly of cases charges will be invoiced.
During installation and handling of components which later have mains potential on their parts, the relevant VDE
regulations must be observed.
Devices that are to be operated at a voltage greater than 35 VDC / 12mA, may only be connected by a qualified
electrician and put into operation.
Commissioning may only be realized if the circuit is built into a contact proof housing.
If measurements with an open housing are unavoidable, for safety reasons an isolating transformer must be installed
upstream or a suitable power supply can be used.
After installing the required tests according to DGUV / regulation 3 (German statutory accident insurance
https://en.wikipedia.org/wiki/German_Statutory_Accident_Insurance) must be carried out.
16 Warranty
ESERA GmbH guarantees that the goods sold at the time of transfer of risk to be free from material and workmanship
defects and have the contractually assured characteristics. The statutory warranty period of two years begins from date of
invoice. The warranty does not extend to the normal operational wear and normal wear and tear. Customer claims for
damages, for example, for non-performance, fault in contracting, breach of secondary contractual obligations,
consequential damages, damages resulting from unauthorized usage and other legal grounds are excluded. Excepting to
this, ESERA GmbH accepts liability for the absence of a guaranteed quality resulting from intent or gross negligence.
Claims made under the Product Liability Act are not affected.
If defects occur for which ESERA GmbH is responsible, and in the case of replacement goods, the replacement is faulty,
the buyer has the right to have the original purchase price refunded or a reduction of the purchase price. ESERA GmbH
accepts liability neither for the constant and uninterrupted availability of the ESERA GmbH or for technical or electronic
errors in the online offer.
We develop our products further and we reserve the right to make changes and improvements to any of the products
described in this documentation without prior notice. If you need documentation or information about older product

* if the sensor or actuator supports Auto-E-Connect. For details, please refer to the operating instructions of the sensor or actuator.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de 11216 V5.0 R1.0 Manual Page 9 of 9
Art. No. 11216
17 Trademarks
All mentioned designations, logos, names and trademarks (including those which are not explicitly marked) are
trademarks, registered trademarks or other copyright or trademarks or titles or legally protected designations of their
respective owners and are hereby expressly recognized as such by us. The mention of these designations, logos, names
and trademarks is made for identification purposes only and does not represent a claim of any kind on the part of
ESERA GmbH on these designations, logos, names and trademarks. Moreover, from their appearance on ESERA GmbH
webpages it cannot be concluded that designations, logos, names and trademarks are free of commercial property rights.
ESERA and Auto-E-Connect are registered trademarks of ESERA GmbH.
Auto-E-Connect is registered by ESERA GmbH as a German and European Patent.
18 Contact
ESERA GmbH
Adelindastrasse 20
87600 Kaufbeuren
GERMANY
Tel.: +49 8341 999 80-0
Fax: +49 8341 999 80-10
www.esera.de
WEEE-Number: DE30249510
Other manuals for 11216
1
Table of contents
Other esera automation I/O System manuals

esera automation
esera automation 11216 User manual

esera automation
esera automation Auto-E-Connect 11230 User manual

esera automation
esera automation 11228 V2 User manual

esera automation
esera automation 11229 V2 User manual

esera automation
esera automation 11208 User manual

esera automation
esera automation 11218 User manual
Popular I/O System manuals by other brands

Siemens
Siemens SIMATIC ET 200AL manual

Pfeiffer Vacuum
Pfeiffer Vacuum ASM 340 operating instructions

Siemens
Siemens SIMATIC ET 200eco PN Equipment manual

National Instruments
National Instruments REM-11120 Getting started guide

Siemens
Siemens SIMATIC 505 user manual

Kolbinger electronic
Kolbinger electronic PCI-1760U user manual