
1. Remove the furnace from box/packaging taking
care not to damage the paper template. This is
to be used to mark the holes for mounting the
2. After marking where the appropriate holes will
be by using the template mentioned above,
make a 2 in. diameter hole. If a hole is already
present from a previous heater, use the Retro-
fi t/Vinyl Adapter Kit to compensate for the size
difference. This kit can also be used to extend
the placement of the vent on houses with vinyl
siding. If you are using the Retrofi t/Vinyl Adapter
Kit, install the plate using the intstructions in-
cluded with the kit before proceeding.
3. Cut the combustion exhaust and fresh air inlet
tubes according to the wall thickness (see Fig-
ure 2 below). Air inlet tube length = wall thick-
ness + 3/32 in. Flue outlet tube length = wall
thickness + 1-5/16 in. If you are using the Retro-
fi t/Vinyl Adapter Kit, you will need to include the
distance the plate extends from the wall in your
measurement of the wall thickness.
4. Drill the fi xing holes A (5 holes for 5001/5002, 8
holes for 8001/8002) in the wall. If the wall can
receive self–tapping screws, drill 1/8 in. diam-
eter. If not, drill 1/4 in. diameter and use the
plastic anchors provided.
5. Install the supporting bracket to the wall; insert
the air pipe in the wall through the hole pro-
vided in the support bracket. Place the round
adhesive gasket around the hole, so that the air
pipe remains on its positions (see Figure 3 and
6. Fix the supporting bracket with the screws. Use
self–tapping screws if the wall can receive them.
If not, use the plastic anchors provided.
7. Remove the casing loosening the fi xing screws
(see Figure 5 on page 13) and disconnect the
If using the Retrofi t/Vinyl Adapter Kit, include
the distance the plate extends from the wall
1. Remove the furnace from box/packaging taking
care not to damage the paper template. This is
to be used to mark the holes for mounting the
2. After marking where the appropriate holes will
be by using the template mentioned above,
make a 2 in. diameter hole. If a hole is already
present from a previous heater, use the Retro-
fi t/Vinyl Adapter Kit to compensate for the size
difference. This kit can also be used to extend
the placement of the vent on houses with vinyl
siding. If you are using the Retrofi t/Vinyl Adapter
Kit, install the plate using the intstructions in-
cluded with the kit before proceeding.
3. Cut the combustion exhaust and fresh air inlet
tubes according to the wall thickness (see Fig-
ure 2 below). Air inlet tube length = wall thick-
ness + 3/32 in. Flue outlet tube length = wall
thickness + 1-5/16 in. If you are using the Retro-
fi t/Vinyl Adapter Kit, you will need to include the
distance the plate extends from the wall in your
measurement of the wall thickness.
4. Drill the fi xing holes A (5 holes for 5001/5002, 8
holes for 8001/8002) in the wall. If the wall can
receive self–tapping screws, drill 1/8 in. diam-
eter. If not, drill 1/4 in. diameter and use the
plastic anchors provided.
5. Install the supporting bracket to the wall; insert
the air pipe in the wall through the hole pro-
vided in the support bracket. Place the round
adhesive gasket around the hole, so that the air
pipe remains on its positions (see Figure 3 and
6. Fix the supporting bracket with the screws. Use
self–tapping screws if the wall can receive them.
If not, use the plastic anchors provided.
7. Remove the casing loosening the fi xing screws
(see Figure 5 on page 13) and disconnect the
If using the Retrofi t/Vinyl Adapter Kit, include
the distance the plate extends from the wall
1. Remove the furnace from box/packaging taking
care not to damage the paper template. This is
to be used to mark the holes for mounting the
2. After marking where the appropriate holes will
be by using the template mentioned above,
make a 2 in. diameter hole. If a hole is already
present from a previous heater, use the Retro-
fi t/Vinyl Adapter Kit to compensate for the size
difference. This kit can also be used to extend
the placement of the vent on houses with vinyl
siding. If you are using the Retrofi t/Vinyl Adapter
Kit, install the plate using the intstructions in-
cluded with the kit before proceeding.
3. Cut the combustion exhaust and fresh air inlet
tubes according to the wall thickness (see Fig-
ure 2 below). Air inlet tube length = wall thick-
ness + 3/32 in. Flue outlet tube length = wall
thickness + 1-5/16 in. If you are using the Retro-
fi t/Vinyl Adapter Kit, you will need to include the
distance the plate extends from the wall in your
measurement of the wall thickness.
4. Drill the fi xing holes A (5 holes for 5001/5002, 8
holes for 8001/8002) in the wall. If the wall can
receive self–tapping screws, drill 1/8 in. diam-
eter. If not, drill 1/4 in. diameter and use the
plastic anchors provided.
5. Install the supporting bracket to the wall; insert
the air pipe in the wall through the hole pro-
vided in the support bracket. Place the round
adhesive gasket around the hole, so that the air
pipe remains on its positions (see Figure 3 and
6. Fix the supporting bracket with the screws. Use
self–tapping screws if the wall can receive them.
If not, use the plastic anchors provided.
7. Remove the casing loosening the fi xing screws
(see Figure 5 on page 13) and disconnect the
If using the Retrofi t/Vinyl Adapter Kit, include
the distance the plate extends from the wall
3. Cut the combustion exhaust and fresh air inlet
tubes according to the wall thickness (see Fig-
ure 2 below).
Air inlet tube length = wall thickness + 3/32
in. (33.3 mm)
Flue outlet tube length = wall thickness +
1-5/16 in. (2.3 mm)
If you are using the Retrot/Vinyl Adapter
Kit, you will need to include the distance the
plate extends from the wall in your mea-
surement of the wall thickness.
Air inlet tube length = wall thickness + 3/32 in. (33.3 mm)
Flue outlet tube length = wall thickness + 1-5/16 in. (2.3 mm)