FATEK FBs-CMGSM User manual

140903 FBs-CMGSM User's Manual EN v3-04 Page #1 of 7
FBs-CMGSM
User’s Manual
1. Introduction
FBs-CMGSM (CMGSM for short) is communication module for FATEK PLC systems
FBs-xxMC. CMGSM uses the GSM network to transfer the data. CMGSM is based
on the quad band GSM module (850/900/1800/1900 MHz). CMGSM is backed
up by Li-Ion accumulator.
CMGSM offer three different ways of communication with connected PLC.
The first one is monitoring and remote control of PLC via SMS. CMGSM reads
periodically PLC registers containing a flag to send SMS, if the flag is set, CMGSM
reads destination phone number and string of characters (text), sends SMS and
clears the flag. If there is a SMS received by CMGSM, it is written into PLC registers
including another flag “SMS received” to be processed by PLC program. At the end
the PLC program clears this flag. So these operational SMS must be processed by
PLC program both on SMS reception and SMS sending. Some status and event SMS
are predefined in CMGSM (e.g. “Connection to PLC failure”) and only the destination
phone number have to be set in PLC registers.
The second way of communication with PLC via CMGSM is dial up data transfer
via GSM network (CSD). The connection can be only incoming for CMGSM, that
may be initiated from a control center for the purpose of remote system analysis
and PLC software tuning and modification by WinProladder SW.
The third way of CMGSM communication over the GSM network is GPRS data
connection using TCP/IP protocol. CMGSM opens the connection in TCP client
mode. Any SIM card, that can provide internet connection over the GSM network,
can be used. CMGSM connects to IP address and port specified in from PLC. It is
important to notice, that the connection can be opened in direction from CMGSM to
PC (server) only. PC cannot open a connection to CMGSM because CMGSM has no
server implemented and usually does not have public IP address. GPRS has special
data transfer properties (data grouping, data transfer delay 1 ... 10 seconds), which
are not suitable for WinProladder SW. WinProladder must use dial up data
transfer (so called CSD) only.
Main features
Three ways of GSM network use –SMS, GPRS, Data Call CSD (all of
them practically at the same time)
WinProladder remote GSM dial up data transfer connection (CSD)
USB port for module monitoring
One digital input IN and one digital output OUT
Firmware update via GSM available
Li-Ion backup accumulator –min. 2 days of operation w/o charging
Lowest level super watchdog function (Hardware Power OFF)
FBs-CMGSM can be used directly with PLC FBs-xxMC (Port 3)
SMS functionality is fully under PLC program control
Configuration of CMGSM means just to set several PLC registers
No PLC program support is necessary for CSD and GPRS operation
LEDs for indication of the CMGSM status and data flow signalization
Unlimited number of logical and analog inputs and outputs can work
with one CMGSM (PLC network)
1) GSM antenna connector
2) IO connector
3) SIM card holder
4) USB connector
5) DIN rail holder
6) FUNC button
7) Indication LEDs Rx, Tx
8) Flat cable for connection to PLC
9) Indication LEDs GSM, ERR
2. Content of the
Delivery
1 pc of FBS-CMGSM
1 pc of antenna GSM-ANT05S
1 pc of 6 pin connector, pitch 3.81 mm
1 pc of CD with documentation
3. Typical Application, Installation
FATEK PLC
CMGSM
Power +5VDC
GSM
Antenna
RS 232 Communication
Flat cable
Note: FATEK PLC is not part of the delivery of this product. It is needed to order
independently.
Warning
Turn off all power supply during installation of CMGSM to PLC to
prevent damage to equipment!
3.1 Configuration
If a SIM card does not need PIN code, no configuration for basic use is necessary.
For the SIM card with PIN code the configuration in PLC is necessary. Read chapter
5.1 Configuration for more.
3.2 Hardware settings
Switch off the power supply of PLC
Connect GSM antenna
Insert SIM card
Connect the flat cable between CMGSM and PLC
3.3 Startup
Device status is indicated with blue GSM LED on the CMGSM front panel. Valid
statuses are as follows:
Term
Description
permanently off
No power or STAND BY mode.
600 ms on /
600 ms off
Device is not logged into the GSM network.
This state occurs after start of device for approx. 30 seconds.
If it remains, check: SIM card (is inserted?, is valid?)
Antenna (is connected?)
Configuration (is SIM PIN correct?)
75 ms on /
3 s off
Device is logged into the GSM network and is idle. (It means
that no GPRS nor CSD connection is active.)
75 ms on /
75 ms off /
75 ms on /
3 s off
GPRS active, no data
500 ms on /
50 ms off
GPRS active, data transfer in progress
permanently on
CSD (data connection) in progress
Expressed line is common operating state.
3.4 Front Panel
Name
Element
Description
ANT
Connector
GSM Antenna connector
GSM
LED blue
GSM status
(see the previous table)
ERR
LED red
Error
IO
Connector
IN (input), OUT (output)
FUNC
Button
Multifunction Button:
DOUT2 change, RESTART,
STAND BY mode.
SIM
CARD
SIM card
Holder
Press the SIM card to
remove it from holder
USB
Connector
USB connection to PC for
debugging purposes
RCV
LED yellow
Receiving SMS
SND
LED green
Sending SMS
3.4.1 Pushbutton “FUNC”
Pushbutton “FUNC”has several functions. Short press
changes the state of the output OUT (DOUT2). Long press (longer than 3 seconds)
will either RESTART CMGSM (if CMGSM is powered by the PLC) or enter the
STAND BY MODE (if the CMGSM is powered from the internal accumulator - PLC is
either disconnected or turned off).
5
9
2
46
7
8
3
1
FBs-CMGSM
USB
COMMUNICATION
GSM MODULE
11
FUNC
RCV
SND
GSM
+
ERR
-
IN
OUT
SIM
PLC1.ir

140903 FBs-CMGSM User's Manual EN v3-04 Page #2 of 7
3.4.1 IO Connector
IO connector has 6 terminals. Terminals “+” “-” are intended for service purposes
only - for test of an internal accumulator. Terminals IN (“IN1”) are for digital input.
Terminals OUT (“DOUT2”) are for digital output.
8 to 30
VDC *)
OUTPUT (e.g.relay)
CMGSM
IN
OUT
4V
50 Ohm
GSM-PWR12
or
GSM-PWR1
GSM-RELE-OUT1
3k9
1k MAX *)
35VAC/70mA
50 VDC/100mA
TEST
ACC.
INPUT
(e.g. button or mg. contact)
*) Please, see the technical
specifications for details
+
-
4. Function of the device
4.1 SMS
One of the primary functions of the CMGSM is to send and receive SMS messages.
There are 2 kinds of SMS, which have different functions and purposes:
SMS for and from PLC FATEK, see chapters 4.1.1. and 4.1.2
Service SMS commands processed by CMGSM, see chapter 4.3
Outgoing SMS from PLC FATEK are sent by PLC program, that writes the text and
destination phone number into PLC registers and orders CMGSM to send the
message by write special value to another register (
SendFlag
). CMGSM sends SMS
and writes result of the sending to PLC register (
SendFlag
). Incoming messages for
PLC FATEK are received by CMGSM and the text and origin phone number are
written into PLC registers. Subsequently in another register (
RecvFlag
) is written
value, that signalizes new received SMS. PLC program analyzes the registers and
deactivates flag
RecvFlag
. All the SMS structure and security features must be done
by PLC program, including confirmation, that SMS was received, if required.
SMS messages, which contains characters “#!” (hash and exclamation) followed by
access code, are sent and received by CMGSM itself and their function, structure
and security features cannot be changed by user or PLC program. Incoming SMS of
this kind are described in chapter 4.3
Service SMS Commands
and are used to get
information about CMGSM status, to reset CMGSM or to get current CMGSM
configuration. Outgoing SMS of this kind are described in chapter 4.5
Events
. Events,
it is information about emergency status of CMGSM module like lost communication
with PLC. These events are sent to a predefined phone number (
Master
in
configuration).
4.1.1 Sending a SMS
CMGSM periodically tests the first register of the
Send Record
, standard base is
D3800. The
Send Record
is an area in PLC registers which must be filled by program
in PLC in order to send a SMS message. For structure of the record see the following
table.
Registers
Caption
Description
D3800
SendFlag
0x0000 –Idle
0x0001 –Command to send (written by
program in PLC)
0x0003 –SMS is sending (written by
CMGSM)
0x0000 –SMS sent successfully (written
by CMGSM)
0x0004 –Failed while sending SMS
(written by CMGSM)
D3810-D3819
SendDestAddress
Phone number where to send the
message. Length 20 characters.
D3820-D3899
SendUserData
Text of the message. Length 160
characters.
This range of registers cannot be used for any other purposes!
How does the CMGSM send a message:
START
? D3800 WAIT 5s
WRITE
0x0003
INTO D3800
0x0001
ELSE
READ
D3810-D3819
Phone number
READ
D3820-D3899
Text
SENDING
? RESULT
WRITE
0x0000
INTO D3800
WRITE
0x0004
INTO D3800
OK ERROR
Every register of
Phone number
or
Text
contains two characters. String of
characters ends with special character 0x00. Examples:
String with one character –“A”: D3820 = 0x0041
String “TEXT”: D3820 = 0x4554, D3821 = 0x5458, D3822 = 0x0000
String “HELLO”: D3820 = 0x4548, D3821 = 0x4C4C, D3822 = 0x004F
If the length of a phone number is exactly 20 characters (or 160 characters of text)
then the character 0x00 at the end is omitted!
Base of
Send Record
(D3800) may be changed to another D or R register via
configuration key REGSEND. Only register
SendFlag
(D3800) is changed during
sending a message.
Example of sending a message “WE ARE THE CHAMPIONS!” to phone “123465”:
(Check register D3800 –SendFlag for value 0x0000 before sending the message!)
Register
Value
Description
D3810
0x3231
SendDestAddress, characters “1” and “2”
D3811
0x3433
SendDestAddress, characters “3” and “4”
D3812
0x3635
SendDestAddress, characters “5” and “6”
D3813
0x0000
End of string
D3820
0x4557
SendUserData, characters “W” and “E”
D3821
0x4120
SendUserData, characters “ ” (space) and “A”
D3822
0x4552
SendUserData, characters “R” and “E”
D3823
0x5420
SendUserData, characters “ ” (space) and “T”
D3824
0x4548
SendUserData, characters “H” and “E”
D3825
0x4320
SendUserData, characters “ ” (space) and “C”
D3826
0x4148
SendUserData, characters “H” and “A”
D3827
0x504D
SendUserData, characters “M” and “P”
D3828
0x4F49
SendUserData, characters “I” and “O”
D3829
0x534E
SendUserData, characters “N” and “S”
D382A
0x0021
SendUserData, characters “!” and end of string
D3800
0x0001
SendFlag: send command
4.1.2 Receiving a SMS
Incoming SMS messages are saved into registers of PLC in
Recv Record
, standard
base D3700. Structure of the record is in following table.
Registers
Caption
Description
D3700
RecvFlag
0x0000 –Idle (written by PLC program)
0x0001 –Message received (written by
CMGSM)
D3710-D3719
RecvOrigAddress
Phone number of the message sender
(originator). Length 20 characters.
D3720-D3799
RecvUserData
Text of the message. Length 160
characters.
This range of registers cannot be used for any other purposes!
PLC1.ir

140903 FBs-CMGSM User's Manual EN v3-04 Page #3 of 7
How CMGSM stores a received message:
START
Message received
? D3700 WAIT 1s
WRITE
Phone number
INTO
D3710-D3719
0x0000
ELSE
WRITE
Text of SMS
INTO
D3720-D3799
WRITE
0x0001
INTO D3700
END
Every register of
Phone number
or
Text
contains two characters. String of
characters ends with special character 0x00. Examples:
String with one character –“A”: D3720 = 0x0041
String “TEXT”: D3720 = 0x4554, D3721 = 0x5458, D3722 = 0x0000
String “HELLO”: D3720 = 0x4548, D3721 = 0x4C4C, D3722 = 0x004F
If length of phone number is exactly 20 characters (or 160 characters of text) the
character 0x00 at the end is omitted!
CMGSM contains a queue of up to 100 SMS messages. After the queue is full all
other SMS messages are discarded. If a power failure occurs all received messages
in the queue are lost. Base of
Recv Record
(D3700) may be changed to another D
or R register via configuration key REGRECV. No other registers are changed than
the necessary ones.
Example of receiving of message “TEST MESSAGE.” from phone “+420123456789”:
Register
Value
Description
D3700
0x0001
RecvFlag: new message
D3710
0x342B
RecvOrigAddress, characters “+” and “4”
D3711
0x3032
RecvOrigAddress, characters “2” and “0”
D3712
0x3231
RecvOrigAddress, characters “1” and “2”
D3713
0x3433
RecvOrigAddress, characters “3” and “4”
D3714
0x3635
RecvOrigAddress, characters “5” and “6”
D3715
0x3837
RecvOrigAddress, characters “7” and “8”
D3716
0x0039
RecvOrigAddress, characters “9” and end of string
D3720
0x4554
RecvUserData, characters “T” and “E”
D3721
0x5453
RecvUserData, characters “S” and “T”
D3722
0x4D20
RecvUserData, characters “ ”(space) and “M”
D3723
0x5345
RecvUserData, characters “E” and “S”
D3724
0x4153
RecvUserData, characters “S” and “A”
D3725
0x4547
RecvUserData, characters “G” and “E”
D3726
0x002E
RecvUserData, characters “.” and end of string
4.2 GSM Data Connection (Data Call, CSD)
Data connection can be established anytime, even if GPRS communication is in
progress.
Warning
There is no security mechanism against unauthorized data connection to
PLC. So it is highly recommended to set security in PLC (password).
4.3 Service SMS Commands
Received SMS message with string ‘#!’ and password at the beginning are
considered to be
service SMS commands
. These messages are not forwarded to PLC,
but they are processed in CMGSM. Device will check for a valid access code (ACODE
parameter in configuration) and if the access code is valid, the message is searched
for keywords. Only one keyword in every SMS is executed.
Example of this SMS:
#!1234 INFO
#!998877 CONFIG
Table of all keywords:
Keyword
Description
INFO
STATE
Device will respond with SMS describing its current status, e.g.
CMGSM: NETWORK=Vodafone CZ 77%
IN1=off
OUT2=off
CSD=no connection
GPRS=no connection
PLC=connected
CMGSM v8.2
RESET
Device will respond with confirmation SMS and restart itself. PLC is
not affected.
This command is used after change of configuration in PLC register
to accept the changes by CMGSM.
CONFIG
Device will respond with current configuration. (Current
configuration is a default configuration with some values changed by
configuration string in PLC, see Chapter 5 –Configuration.)
FACTORY
CMGSM will respond with confirmation SMS. CMGSM will write
default configuration to attached PLC and restart itself.
ON
Activate digital output OUT2
OFF
Deactivate digital output OUT2
4.4 TCP over GPRS
One of the primary functions of this device is to establish and maintain TCP
connection from PLC to a server. In order to achieve this goal FBs-CMGSM has to
make following steps after power up:
Establish connection to PLC via serial port. Parameters of the serial port are: 9600
baud, 7 data bits, EVEN parity, 1 stop bit, no hw handshake (it is default FATEK
settings for all serial ports), address 01h.
After power on the FBs-CMGSM will proceed steps:
Read configuration from PLC register D3900 –D3999.
Login to the GSM network, using PIN from configuration.
Attach to GPRS, using APN, USER and PASSWD from configuration.
Establish and maintain TCP connection to SERVER on port PORT.
CMGSM will try indefinitely to read configuration from PLC at the beginning. If there
is no serial communication between CMGSM and PLC device will not login into the
GSM network! If there is no configuration in PLC or the configuration is damaged or
other problem occurs CMGSM writes default configuration into the PLC.
GPRS can be controlled and monitored via set of registers in PLC and via
configuration:
Registers
Caption
Description
D3510
GprsCommand
0=no connection (written by PLC)
1=open connection (written by PLC)
D3511
GprsState
0x00=no connection, idle
0x01=connecting
0x80=connected
0x81=disconnecting
D3512
GprsCntErr
Error counter for connection
D3516-D3517
GprsCntUp
Data counter, direction UP
(= PLCTCP), D3516 LSB
D3518-D3519
GprsCntDown
Data counter, direction DOWN
(= TCPPLC), D3518 LSB
D3520-D3523
GprsLocalIP
Local IP address if connected. “0.0.0.0” if
not connected. (D3520=MSB)
Example:
If local IP address is 147.32.80.1, then
D3520 … 0x0093 (147d)
D3521 … 0x0020 (32d)
D3522 … 0x0050 (80d)
D3523 … 0x0001 (1d)
D3524
GprsLocalPort
Local TCP port if connected, 0 if not
connected
D3525-D3528
GprsRemoteIP
Remote IP address if connected. “0.0.0.0”
if not connected. (D2425=MSB)
D3529
GprsRemotePort
Remote TCP port if connected, 0 if not
connected
This range of registers cannot be used for any other purposes!
GPRS diagnostic is part of Diagnostic (see chapter Diagnostic). Base of
Diag Record
(D3500) may be changed to another D or R register via configuration key REGDIAG.
4.5 Events
Device can detect special events and send a warning about them as a SMS:
Connection to PLC failure/restore
It is needed to set parameter MASTER in configuration for both of these events,
see chapter 5.2 Basic Parameters.
PLC1.ir

140903 FBs-CMGSM User's Manual EN v3-04 Page #4 of 7
4.6 Diagnostic
Diagnostics values are written to
Diagnostic Record
, standard base D3500. Structure
of the record is in following table:
Registers
Caption
Description
D3500.0
DiagCnct
0=no connection to PLC, 1=connection to
PLC OK
D3500.1
DiagRQueue
0=no SMS in receive queue, 1=at least one
SMS in receive queue
D3500.8-15
DiagGsmReg
result of command AT+CREG:
0=not registered, not searching
1=registered, home network
2=not registered, searching
3=registration denied
5=registered, roaming
D3501.0-7
DiagSigQuality
Signal quality in percent (0-100) or 255 if
unknown.
D3501.8-15
DiagSigErr
Signal BER (0-7) or 255 if unknown.
D3502
DiagAlive
CMGSM writes value 0x0001 whenever
diagnostic record is refreshed (cca 6
seconds). This is intended for PLC program
to check if CMGSM is alive. In this case PLC
program will write a 0x0000 into this
register and wait for 0x0001 here.
D3503
DiagVersion
Version of CMGSM3, in high byte is high
version number, in low byte is low byte is
low version number
D3504
0x0000
For future use
D3505
DiagReset
If PLC writes value 0xF3A5 to this register
the CMGSM will make reset of itself.
D3506
DiagAtFlag
0x0000 –Idle
0x0001 –Execute command in
DiagAtCmd (written by program in PLC)
0x0003 –Command is about to execute
(written by CMGSM)
0x0000 –Command executed successfully
(written by CMGSM)
0x0004 –Exception while executing the
command (written by CMGSM)
D3508-D3509
DiagUpTime
32 bit counter which is incremented
whenever CMGSM updates DiagRegisters
area in PLC. The counter is cleared after
restart of CMGSM. The counter value
indicates in a certain way how long the
CMGSM is running without restart (so
called Uptime).
D3510-D3529
Gprs ...
Reserved for GPRS diagnostics
See chapter “TCP over GPRS” for details
D3530-D3539
DiagOperator
String with name of operator when
registered. Empty string if not registered.
Length 20 characters.
D3540-D3549
DiagCredit
Reserved
D3550-D3699
DiagAtCmd
Sending AT commands to modem directly.
Write a command to this place and set
D3506 (DiagAtFlag) to 0x0001. Command
is executed and result is placed in this
place (overwriting original command). In
D3506 (DiagAtFlag) is signalized end of
execution. The system is the same as with
sending SMS.
This range of registers cannot be used for any other purposes!
Notation
D3500.x
means x-th bit of D3500 register. For example D3500.0 is the
least significant bit in register D3500. Another example D3500.8-15 are eight most
significant bits in register D3500 (high byte).
Base of
Diag Record
(D3500) may be changed to another D or R register via
configuration key REGDIAG.
5. Configuration
5.1 How to
Configuration for CMGSM is located inside PLC Fatek. Range of internal PLC registers
D3900 –D3999 is used. Configuration itself is a string of characters. This string is
created via WinProladder (software from PLC FATEK manufacturer), see following
images. This range of registers cannot be used for any other purposes!
Step 1 –Right click on Table edit - ASCII Table
and select “New ASCII Table”
Step 2 –Enter Table Name „cfg“ and Table starting address „D3900“.
Then click “OK”.
Step 3 –Enter configuration string
“CMGSM3;PIN=7608;ACODE=998877;$”into field “ASCII Editor”and
click on button “Output Preview”. !!! Warning: Change PIN according your
real SIM card !!!
Step 3 (GPRS) –Enter configuration string
“CMGSM3;PIN=7608;APN=internet;SERVER=test.server.com;PORT=5700
;ACODE=998877;$” into field “ASCII Editor” and click on button “Output
Preview”. !!! Warning: Change PIN according to your real SIM card !!!
PLC1.ir

140903 FBs-CMGSM User's Manual EN v3-04 Page #5 of 7
Step 4 –Select “Non Output Format” and click “OK”.
Step 5 –Configuration string is now black. Click “OK”.
Step 5 (GPRS) –Configuration string is now black. Click “OK”.
Step 6 –Result
Configuration is read after power up and only once. If you change configuration (for
example by WinProladder and second serial port), it is not read automatically. You
have to restart CMGSM. CMGSM will try to log in the GSM network without PIN if no
configuration in PLC is found. (In this case SIM card without PIN authorization is
requested.)
Configuration string is very simple. For example:
CMGSM3;PIN=7608;ACODE=998877;MASTER=+420777777497;$
For easy understanding this string says:
CMGSM3 –It is a configuration for CMGSM.
PIN=7608 –PIN code of the SIM card in order to register into the GSM
network.
ACODE=998877 –Access code for
Service SMS Commands
is 998877
MASTER=+420777777497 –Warning SMS is sent to this phone number
in case of any event. For example “Connection to PLC failure.”when
communication between CMGSM and PLC is lost or “IN1 activated (L-
>H).”when digital input IN (IN1) is activated respectively “IN1 released
(H->L).”when digital input IN (IN1) is deactivated.
Example of configuration string for GPRS:
CMGSM3;PIN=7608;APN=internet;
SERVER=test.server.com;PORT=5700;ACODE=998877;$
This string means:
CMGSM3 –It is configuration for CMGSM.
PIN=7608 –User PIN code of ‘7608’ for SIM card in order to register
into the network.
APN=internet –Access Point (APN) is needed in order to use GPRS
service in GSM network. In this example APN is ‘internet’.
SERVER=test.server.com –It is a name of a server, to which CMGSM
will connect. (Using TCP connection.)
PORT=5700 –Use TCP connection to port 5700
ACODE=998877 –Access code for SMS control is 998877
General format of these messages is following:
CMGSM3;KEY1=VALUE1;KEY2=VALUE2;...[;]$
Part ‘CMGSM3’ at the beginning of the string is mandatory. It is a stamp of validity.
Acceptable keys are shown in table below. Unknown keys are ignored, no spaces
are allowed inside keys or values. Order of pairs is not important. Keys are not case
sensitive, values are case sensitive. Maximum length of configuration string is 200
characters. At the end of each part MUST be character ‘;’ (semicolon), after last pair
MAY be character ‘;’ (semicolon) and MUST be character ‘$’ (dollar).
5.2 Basic parameters
Key
Description
Default
PIN
PIN code for SIM card. It may be omitted if the SIM
card does not need a PIN code. But it is mandatory if
the SIM card needs the PIN code.
<empty>
ACODE
Access code for SMS control. You can send SMS
message in order to control CMGSM. These SMS must
begin with this ACODE. They will be ignored
otherwise. Optional.
1234
MASTER
Phone number, where to send SMS about important
events: Connection to PLC failure. No SMS are sent if
value is empty. Only one master is possible.
<empty>
5.3 Advanced parameters
Key
Description
Default
REGSEND
First register of the
Send Record
.. It is area, where
PLC writes messages to send. See 4.1.1 Sending a
SMS. Only D or R registers can be used.
D3800
REGRECV
First register of the
Recv Record
. It is an area, where
CMGSM writes received messages. See 4.1.2 Receive a
SMS. Only D or R registers can be used.
D3700
REGDIAG
First register of the
Diagnostic Record
. It is an area,
where CMGSM writes diagnostic values like operator,
signal quality, … See chapter 4.4
D3500
NETRESET
This is a security feature. Value zero (0) in this
parameters means security reset every week (7 days).
If you do not want any security reset write -1 to this
parameter.
0
5.4 GPRS parameters
Keys in configuration string:
Key
Description
Default
APN
Access Point for GPRS. Ask your GSM provider for this
value.
internet
USER
User for APN. Mandatory is provider requires.
<empty>
PASSWD
Password for APN. Mandatory is provider requires.
<empty>
SERVER
Name or IP address of server, to which CMGSM will
connect. TCP connection is used. Optional.
<empty>
PORT
TCP port for connection. Optional.
5700
DNS
IP address of DNS server. Optional.
<empty>
If SERVER is omitted no GPRS connection is made and device waits for a data CSD
call only.
PLC1.ir

140903 FBs-CMGSM User's Manual EN v3-04 Page #6 of 7
5.5 Examples of Configuration Strings
5.5.1 SIM without PIN
Configuration string:
CMGSM3;ACODE=998877;$
Translated for human this string says:
CMGSM3 –It is configuration for CMGSM.
ACODE=998877 –Access code for
Service SMS Commands
is 998877
5.5.2 Use registers D1000-D1100 for sending SMS
Configuration string:
CMGSM3;PIN=7608;REGSEND=D1000;$
Translated for human this string says:
CMGSM3 –It is configuration for CMGSM.
PIN=7608 –PIN code 7608 for SIM card in order to register into
network.
REGSEND=D1000 –Begin of the
Send Record
.
[default Access code for SMS control is 1234]
5.5.3 Only CSD (without GPRS)
Configuration string:
CMGSM3;PIN=7608;$
Translated for human this string says:
CMGSM3 –It is configuration for CMGSM.
[default Access code for SMS control is 1234]
5.5.4 SIM without PIN, GPRS connection
Configuration string:
CMGSM3;APN=internet;SERVER=test.server.com;PORT=5700;AC
ODE=998877;$
Translated for human this string says:
CMGSM3 –It is configuration for CMGSM.
APN=internet –Access Point (APN) is ‘internet’.
SERVER=test.server.com –Connect to ‘test.server.com’
PORT=5700 –Use TCP connection to port 5700
ACODE=998877 –Access code for SMS control is 998877
6. Usage scenarios for SMS
Usage examples can be found on CD with documentation or on the web pages
http://fatek.seapraha.cz/. In category FAC-CMGSM are examples of programs
for receiving and sending of SMS from PLC.
7. Usage Scenarios for GPRS
7.1 Explanation of Important Terms
Term
Description
GPRS
The way how to transfer data through the GSM network. It is
charged according to transferred bytes (and not per minutes) and is
much more suitable for remote monitoring than data connection
(CSD).
TCP/IP
It is protocol which is used while communicating through GPRS.
(Like Fatek protocol is used to communicate between computer and
Fatek PLC).
TCP
It is one of protocols in TCP/IP family used with CMGSM. It may be
imagine as a bidirectional stream of bytes through the Internet and
the GSM network from your computer to a Fatek PLC
Firewall
It is a security device. It located between you LAN and Internet.
Main purpose of the Firewall is to protect your LAN against an attack
from Internet.
Port
It is a number of a service in your computer. Complete address
needed to connect your computer is composed from IP address and
Port number and may be seen as 11.22.33.44:5700 (IP-
ADDRESS:PORT).
7.2 Simple Use
We recommend this scenario for your first step with CMGSM.
Internet
Firewall
Your computer in LAN
of your company
GSM Network
LAN
FBs-
CMGSM FATEK
PLC
PWR
COMM
You need to prepare following items in this scenario:
External (WAN) IP address of your firewall. Rest of the Internet sees you
with this IP. Warning: it is NOT your IP address in LAN (i.e. 10.0.0.25).
Your external IP address may be obtained from various WEB sites, i.e.
http://www.whatismyip.com/.
A redirection of port 5700 from external side of your firewall to your
computer.
Cooperation of your IT department will be necessary for all of these items.
We offer simple program that acts like a server. CMGSM connects to this server.
This program is only a demonstration for one connection and elements X0-X3 and
Y0-Y3. It may be obtained from our WEB site (www.seapraha.cz).
Details:
Program listens on TCP port 5700 for incoming connection. Port 5700 is
default port where CMGSM connects to. Program periodically queries status of
inputs X0-X3 from remote station. You can change any of output Y0-Y3 by click on a
check box Y0-Y1.
8. Technical Specifications
8.1 General
Parameter
Symbol
Conditions
MIN.
TYP.
MAX.
Unit
Dimensions
Width
w
25
mm
Height
h
90
mm
Depth (without
antenna)
d
FBS-CMGSM
B1-CMGSM
80
55
mm
mm
Fixing
DIN rail or flat panel screw fixing
Power
5V DC / 120mA (max.)
from power supply of PLC main unit
Backup power
Internal Li-Ion accumulator for 2 days working without
charging. Full capacity will be after 2 day of charging.
Digital input
DC
(any polarity)
Number
-
1
-
Voltage log H
|VIN|
8
12
30
VDC
Voltage log L
|VIN|
<4
4
VDC
Current
IIN
5
mA
Digital outputs
DC, AC
Number
-
1
-
Voltage DC
VOUTDC
8
50
VDC
Voltage AC
VOUTAC
35
VAC
Current DC
IOUTDC
100
mA
Current AC
IOUTAC
70
mA
Temperature
Operational
tA
-20
+45
°C
Humidity
Operational
hA
90
%
GSM
RF power
2
W
GSM
frequencies
Worldwide 850 / 900 / 1800 / 1900
MHz
Antenna
connector
SMA female
GSM-ANT05S
recommended
Communication interface
Flat cable connected directly to PLC FATEK:
FBs-xxMC: Port 3, (Port 4*)
* PLC Port is not usable, but is not is not accessible for another expansions.
PLC1.ir

140903 FBs-CMGSM User's Manual EN v3-04 Page #7 of 7
9. FAQ
CSD (GSM data) connection cannot be established –1) check
power supply, 2) check indication LED on device, 3) are CSD connections
available on your SIM card? Ask provider, 4) check GSM signal quality on
your mobile phone near the device. At least 50% signal is recommended.
No reply to Service SMS Commands –1) check power supply, 2)
check indication LED on device, 3) check configuration (is access code
correct?), 4) try to send SMS from your mobile with SIM card in the
device. (Note: LED RCV and SND are not used for Command SMS)
Some special characters are not correctly transported by SMS –
Try to use so called 7 bit SMS (160 characters) and only basic ASCII
characters (0-127)
No communication with PLC –1) check power supply for PLC, 2)
check COM port settings in WinProladder. It MUST be 9600 7E1, address
01h.
GPRS connection cannot be established –1) check power supply, 2)
check communication with PLC Fatek, 3) check configuration, 4) check if
it is possible from another computer connected to the Internet to
connect to your server (may be firewall is wrong configured).
GPRS connection is not working during CSD connection –This is
the feature of GSM module. GPRS connection is restored automatically
after CSD connection is finished.
Communication is OK but real outputs Y0-Y3 do not reflect
commands –1) PLC FATEK must be in
Run
mode. Use WinProladder to
run PLC.
Communication is OK but inputs X1-X3 do not show correct
value –1) PLC FATEK must be in
Run
mode. Use WinProladder to run
the PLC.
Some parameters in the FATEK configuration are not
functioning –Please check if there is no “$” character before these
parameters (e.g. “CMGSM3;$PIN=7608; ACODE=998877;$”) because
CMGSM reads the configuration until the first “$” character.
10. Warranty
General warranty period is 12 months after purchase, when eventual malfunction
device will be repaired free of charge in SEA company while shipping to SEA is paid
by customer and SEA pays for shipping back to customer. For SW there is 24
months warranty under following conditions:
Both CPU and PC software is sold “as is”. The software was created by the best
software engineers in SEA and was carefully tested both in SEA and also by SEA
customers using GSM applications products made in SEA. In spite of making all
possible to get error free software it can happen, that the software in CPU or PC
programming SW or their mutual interaction has some error
under some specific conditions. If such error is found and the
description of the problem including configuration file is sent
by E-mail to SEA ltd., the error is removed free of charge and
SEA will send new SW by E-mail to customer.
SEA ltd. has NO RESPONSIBILITY for any
damage, lost, costs and any other problems direct or inducted,
caused by such SW error, by eventual device malfunction from
any reason or by undelivered SMS from the device.
CE Declaration of conformity
in accordance with the Radio and Telecommunications Terminal Equipment Directive 1999/5/EC (R&TTE) and
Directive 2011/65/EU (ROHS).
We SEA, spol. s r.o., Dolnoměcholupská 21, CZ 102 00 Praha 10, Czech Republic, ID: 47117931 (manufacturer)
declare under our sole responsibility, that product equipment for remote control and monitoring
type FBs-CMGSM and B1-CMGSM is in conformity with the following standards: