
3
1. Connect the right ground terminal to the earth
ground bus at the service panel. Use #14 AWG
copper conductor wire.
2. Connect the left ground terminal to the metal rigid
conduit used to feed service panel wiring with #14
AWG copper conductor wire.
3. Connect power wires to the appropriate terminals
on the power supply terminal strip: Ground, Line,
Neutral, Earth Ground.
Sensor Wiring
All sensor wiring is to be intrinsically
safe and run into the right side of
the wiring bay and be fully contained
within the intrinsically safe wiring
compartment. When replacing
the faceplate, make sure no wires
are pinched under the faceplate
compartment divider.
1. Remove the wire jumper from each contact input
that you plan to use.
2. Wire each normally closed sensor to the
appropriate terminals.
Note: Only the following FFS sensors can be used with
the S940 console:
• TSP-ULS Universal Liquid Sensor
• TSP-HLS High Level Sensor
• TSP-UHS Universal Hydrostatic Sensor
• TSP-HFS Horizontal Float Switch Sensor
Using other sensors will violate the warranty.
Note: Sensors must be 3rd party or simple apparatus.
Relay Wiring
1. Wire the device to the relay terminal strip in
accordance with the instructions furnished by the
manufacturer of the device.
2. Observe the relays for terminal layout and
voltage / current limits (10A @ 240 VAC).
Operation
When the contact input senses an open condition the
corresponding red alarm LED will light and the annunciator
will sound, and if a relay has been programmed it will
change states.
The annunciator can be silenced by pressing the
silence / test button. It will continue to sound until this
button is pressed, even if the actual alarm condition clears.
The alarm LED (and relay if programmed) will turn off
when the alarm condition clears.
If there is no alarm condition, and the alarm reset button
is pressed, the audible alarm will sound and the relays will
activate. Press again to silence and turn off the relays.
Programming
The settings for the DIP switches in gure 3 determine
which output relay is triggered in response to particular
sensor inputs and the type of audible alarm transmitted.
Relay 1 Activation and Sensor Assignment
DIP
Switch
Switch
Position Affected Sensor
1On Sensor 1 triggers Relay 1
2On Sensor 2 triggers Relay 1
3 On Sensor 3 triggers Relay 1
4On Sensor 4 triggers Relay 1
Relay 2 Activation and Sensor Assignment
DIP
Switch
Switch
Position Affected Sensor
5On Sensor 1 triggers Relay 2
6On Sensor 2 triggers Relay 2
7On Sensor 3 triggers Relay 2
8On Sensor 4 triggers Relay 2
The default position for DIP switches is the Off / Open
position where no relays will be triggered by any sensor.
When assigning a sensor to activate the RELAY 1 (Relay
2), only one of DIP switches 1-4 (5-8) may be set to the
On / Closed position. All other DIP switches in this group
must be set to the Off / Open position.
RELAY 1 Alarm Type: Steady or Single Pulse
DIP
Switch
Switch
Position Alarm Type
9On Single Pulse Alarm - RELAY 1
9Off Steady Alarm - RELAY 1
RELAY 2 Alarm Type: Steady or Single Pulse
DIP
Switch
Switch
Position Alarm Type
10 On Single Pulse Alarm - RELAY 2
10 Off Steady Alarm - RELAY 2
Figure 3: DIP Switch Location
Warning
DIP Switches
4
1 2 3 5 687 9 10
Relay 1 Relay 2