
6
Clearances to combustible materials
The Furnace -The furnace is approved for zero clearance to combustible materials regardless
of the heating capacity. It is recommended that 24” (60cm) be provided at the front of the
furnace for clear access for servicing.
Supply Air Ducts - Supply ducts for furnaces with a heating capacity up to and including
20kW may be installed with 0’’ (0 cm) clearance to combustibles. Heating ducts for furnaces
with heating capacities greater than 20kW must have a 1’’ (25 mm) clearance to combustibles
for the
fi
rst 36” (91.4 cm) of duct. Thereafter the clearance can be 0’’ (0 cm).
Duct connections to the furnace - The duct connection to the furnace is a critical aspect to
ensure the satisfactory performance of this furnace. To reduce the transmission of noise and
vibrations it is recommended to use non-flammable
fl
exible isolation collars. Correct duct sizing
and installation methods will ensure proper airflow providing comfortable balanced delivery of the
air. All duct work should be designed, fabricated and installed in accordance with all national
and/or local codes.
Air Filters - Included with this furnace is a 20” x 20” x 1” disposable air
fi
lter and supporting
fi
lter
rack. This
fi
lter rack shall be secured to the furnace casing on either side or the bottom. Do not
install this
fi
lter rack on the front or back of the furnace, doing so will result in inadequate air
fl
ows. When cutting the return air opening in the furnace casing, use the square knockouts in the
side and bottom panels as reference. This will provide a free area opening of 18” x 18”. The
use of pleated
fi
lters is not recommended unless sized to suit the airflow requirements for the
installation. Pleated air
fi
lters tend to increase total system static pressures. This may result in
reduced airflow. As a result, the heating elements may operate at increased temperatures
resulting in an overheat situation. Airflow reductions may also occur during cooling cycles
resulting in unacceptably low delivered air temperatures.
4. HIGH VOLTAGE CONNECTIONS
Line power 240Vac single phase 60Hz must be brought in to the furnace control compartment via
the knockout provided on the right hand or left hand side of the furnace. The use of any other
entry point may result in the high voltage leads encountering low voltage circuit components
resulting in potentially hazardous conditions. Power lines must be connected to the furnace
main terminal block.
Refer to Section 6 to determine proper wire sizing. A ground connection is provided in this
compartment. Always ensure that the ground circuit is installed to meet the requirements of all
local and national codes.
Fan motor connections.
All furnaces are provided with multi speed direct drive PSC or ECM motors. Furnaces up to and
including 23kW outputs are provided with 1/3hp PSC or 1/2hp ECM, 5 speed motors. 27kW
furnaces are provided with 3/4hp 5 speed motors. Only 3 speeds are connected to the controller
(the 4th and 5th speed motor lead is not connected.)