12
Commissioning
4Commissioning
4.5 Filling the System
Grant Solar Thermal systems should be
flushed and filled using a purpose
designed closed circuit solar thermal
filling station, incorporating a high
pressure pump, such as the Grant Solar
Filling Station. See Figure 4-6.
4.6 Filling Procedure
IMPORTANT
The collectors must be cool before
filling the system. They must be
covered, to stop solar radiation
reaching them, until the filling and
commissioning procedure is
completed.
Before filling the system: Check all
system connections and the expansion
vessel charge pressure. Refer to Table
4-1 (page 10).
Phase 1
• Connect the pressure hose from the
filling station to the Filling Flow valve
connection and open the valve.
Refer to Figure 4-1 (page 10).
• Connect the return hose from the
filling station to the Filling Return
valve connection and open the
valve. Refer to Figure 4-1 (page 10).
• Using a small spanner, rotate the
Filling/Shut-off valve 90° clockwise.
Refer to Figure 4-2 (page 10).
This will divert the flow from the
filling station through the pump, up
to the collectors, through the coil of
the cylinder and back to the filling
station via the filling return valve.
• Fill the filling station tank with
sufficient solar fluid for the system.
• Check that Flow and Return valves
are set to 'half open' position (to
open the gravity brakes) as shown
in Figure 4-4 (page11).
• Switch on the filling station to fill and
then flush the solar circuit for
approx.15 minutes.
Phase 2
• Whilst the filling pump is running,
close the Filling Return valve and
allow the system pressure to reach
around 4 - 5 bar.
• When the pressure reaches 5 bar,
close the Filling Flow valve and
immediately switch off the filling
pump.
• Check that the system pipework
and pump station are leak-free.
After leaving the system at about 5
bar for a minimum of 15 minutes,
check if the pressure gauge shows
any significant drop in pressure. If it
does, this points to a leak in the
system that must be traced and
rectified.
• Check the operation of pressure
relief valve by slowly rotating the
valve knob, lifting the valve, until
fluid is discharged. This should be
collected in a suitable container, e.g.
a pressure relief valve fluid recovery
container (as shown in Figure 3-3 on
page 8).
Phase 3
• Re-open the Filling/Shut-off valve by
turning 90° anti-clockwise.
• Switch on the circulating pump (by
setting the solar controller to
“manual”) to the highest pumping
speed and allow the solar fluid to
circulate for at least 15 minutes.
• Set the solar controller to “stand by”
(pump = OFF).
• Bleed the air separator using the
manual air vent until the solar fluid
begins to escape. Refer to section
4.7 (page 13).
• Set the operating pressure (as in
Table 4-1) by carefully opening the
Filling Return valve and releasing the
fluid back into the filling station tank.
Phase 4
• Reset Flow and Return valves to
fully open position. Refer to
Figure 4-3 (page 11).
• Switch on the circulating pump
(solar controller set to “manual”).
• Set the flow rate on the flow rate
indicator (refer to section 4.8) by
selecting the appropriate pump
speed and by using the Filling/Shut-
off valve.
• Remove the filling station hoses
from the filling connections and
screw the caps on both valves.
Release the Filling Return valve first
and then the Filling Flow valve.
• Switch the solar controller to
automatic operation and remove
covers from the collectors.
Figure 4-6: Grant Solar Filling Station
If the pump station is located in the
roof space, there must be a suitable
flat surface on which to stand the
filling station, e.g. floor, loft boarding
or similar, capable of carrying the
weight of the filling station with a full
tank of solar fluid.
!WARNING