
8
ENERAL INFORMATION
LOCATION REQUIREMENTS
Location
1. IMPORTANT: If using a cooling evaporator coil with this fur-
nace, be sure the air passes over the heat exchanger before
passing over the cooling coil. The cooled air passing over the
warm ambient air inside the heat exchanger tubes can cause
condensation inside the tubes resulting in corrosion and even-
tual failure. An auxiliary drain pan should extend under any
evaporator coil installed with the furnace.
If there are manual dampers, they must be equipped to prevent
heating or cooling operation unless the damper is in the full heat
or cool position.
2. NOTE: This furnace is shipped with heat exchanger support
brackets installed under the back of the heat exchanger. These
may be removed before installation, but it is not required.
3. IMPORTANT: This furnace is not approved or recommended
for installation on its back, with access doors facing upwards.
4. This furnace is suitable for installation in buildings constructed
on-site. This heating unit should be centralized with respect to
the heat distribution system as much as practicable.
5. NOTE: These furnaces are approved for installation in attics,
as well as alcoves, utility rooms, closets and crawlspaces.
6. IMPORTANT: Support this unit when installed. Unit may be rein-
stalled on combustible wood floorin if using a supply air plenum.
If not using supply air plenum, a combustible floor base is re-
quired. See ducting section of this manual.
7. IMPORTANT: If installing in a utility room, be sure the door is
wide enough to:
a. allow the largest part of the furnace to pass; or
b. allow any other appliance (such as a water heater) to pass.
SITE SELECTION
1. Select a site in the building near the center of the pro-
posed, or existing, duct system.
2. Give consideration to the vent system piping when se-
lecting the furnace location. Be sure the venting system
can get from the furnace to the termination with minimal
length and elbows.
3. Locate the furnace near the existing gas piping. Or, if
running a new gas line, locate the furnace to minimize
the length and elbows in the gas piping.
4. Locate the furnace to maintain proper clearance to
combustibles as shown in following Figure 3.
CLEARANCE – ACCESSIBILITY
The design of forced air furnaces with input ratings as
listed in the tables under Figure 3 are clearances to com-
bustible materials shown in inches.
See name/rating plate and clearance label for specific
model number and clearance information.
Service clearance of at least 24 inches (30 cm) is recom-
mended in front of all furnaces.
NOTE: Use recommended 24” (30 cm) clearance if accessi-
bility clearances are greater than fire protection clearances.
ACCESSIBILITY CLEARANCES, WHERE REATER, MUST
TAKE PRECEDENCE OVER FIRE PROTECTION CLEAR-
ANCES.
!WARNING
WHEN THIS FURNACE IS INSTALLED IN A RESIDENTIAL
ARA E, IT MUST BE INSTALLED SO THE BURNERS
AND I NITION SOURCE ARE LOCATED NO LESS THAN
18 INCHES [450MM] ABOVE THE FLOOR. THIS IS TO PRE-
VENT THE RISK OF I NITIN FLAMMABLE VAPORS
WHICH MAY BE PRESENT IN A ARA E. ALSO, THE FUR-
NACE MUST BE LOCATED OR PROTECTED TO AVOID
PHYSICAL DAMA E BY VEHICLES. FAILURE TO FOLLOW
THESE WARNIN S CAN CAUSE A FIRE OR EXPLOSION,
RESULTIN IN PROPERTY DAMA E, PERSONAL INJURY
OR DEATH.
!WARNING
THIS FURNACE IS NOT APPROVED OR RECOMMENDED
FOR INSTALLATION ON ITS BACK, WITH ACCESS DOORS
FACIN UPWARDS.
!WARNING
DO NOT LIFT THE UNIT BY THE HEAT EXCHAN ER
TUBES. DOIN SO CAN DAMA E THE HEAT EX-
CHAN ER ASSEMBLY.
!WARNING
COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON
OR A AINST THE FURNACE JACKET. THE AREA
AROUND THE FURNACE MUST BE KEPT CLEAR AND
FREE OF ALL COMBUSTIBLE MATERIALS INCLUDIN
ASOLINE AND OTHER FLAMMABLE VAPORS AND LIQ-
UIDS. PLACEMENT OF COMBUSTIBLE MATERIALS ON,
A AINST OR AROUND THE FURNACE JACKET CAN
CAUSE AN EXPLOSION OR FIRE RESULTIN IN PROP-
ERTY DAMA E, PERSONAL INJURY OR DEATH. THE
HOMEOWNER SHOULD BE CAUTIONED THAT THE FUR-
NACE AREA MUST NOT BE USED AS A BROOM CLOSET
OR FOR ANY OTHER STORA E PURPOSES.