  7. Furnace
  8. •
  9. ICP N9MP1 User manual

ICP N9MP1 User manual

Other manuals for N9MP1

3

This manual suits for next models

33

Other ICP Furnace manuals

ICP EF12F1900A User manual

ICP

ICP EF12F1900A User manual

ICP N8MPN User manual

ICP

ICP N8MPN User manual

ICP NTGM/GNK Series User manual

ICP

ICP NTGM/GNK Series User manual

ICP N9MSE Quick start guide

ICP

ICP N9MSE Quick start guide

ICP NTG3/FBF Series User manual

ICP

ICP NTG3/FBF Series User manual

ICP NTC6050FBA1 Installation instructions

ICP

ICP NTC6050FBA1 Installation instructions

ICP N9MP1100F14A2 User manual

ICP

ICP N9MP1100F14A2 User manual

ICP N9MSB Installation instructions

ICP

ICP N9MSB Installation instructions

ICP N8MPN User manual

ICP

ICP N8MPN User manual

ICP 8MPT Series Quick start guide

ICP

ICP 8MPT Series Quick start guide

ICP H9MPT050F12B1 User manual

ICP

ICP H9MPT050F12B1 User manual

ICP AMP105-1E2 Quick start guide

ICP

ICP AMP105-1E2 Quick start guide

ICP G9MAC Series User manual

ICP

ICP G9MAC Series User manual

ICP N9MP1080F16A2 User manual

ICP

ICP N9MP1080F16A2 User manual

ICP N9MSB0401410C Installation instructions

ICP

ICP N9MSB0401410C Installation instructions

ICP G9MVE0401410A2 Installation instructions

ICP

ICP G9MVE0401410A2 Installation instructions

ICP NTC7/GNL Series User manual

ICP

ICP NTC7/GNL Series User manual

ICP OLR Series Assembly instructions

ICP

ICP OLR Series Assembly instructions

ICP T8DNL100F14B1 User manual

ICP

ICP T8DNL100F14B1 User manual

ICP C9MPT Guide

ICP

ICP C9MPT Guide

ICP 9MPT Series User manual

ICP

ICP 9MPT Series User manual

ICP EF08B1500A3 User manual

ICP

ICP EF08B1500A3 User manual

ICP GAS FURNACE Guide

ICP

ICP GAS FURNACE Guide

ICP N9MP2125J20A1 User manual

ICP

ICP N9MP2125J20A1 User manual

Popular Furnace manuals by other brands

Unitary products group AHV8 UH installation manual

Unitary products group

Unitary products group AHV8 UH installation manual

VERDER CARBOLITE GERO RHF 14/8 Installation, operation and maintenance instructions

VERDER

VERDER CARBOLITE GERO RHF 14/8 Installation, operation and maintenance instructions

Tempstar B Series Service and technical support manual

Tempstar

Tempstar B Series Service and technical support manual

Carrier Performance 59SP5A Installation, start-up, operating and service and maintenance instructions

Carrier

Carrier Performance 59SP5A Installation, start-up, operating and service and maintenance instructions

Armstrong EG7H SERIES Installation and maintenance instructions

Armstrong

Armstrong EG7H SERIES Installation and maintenance instructions

Payne PG92ESA Installation, start-up, operating and service and maintenance instructions

Payne

Payne PG92ESA Installation, start-up, operating and service and maintenance instructions

NANOE Zetasinter Operation manual

NANOE

NANOE Zetasinter Operation manual

SUPREME FEM10-M2301CM-A Installation instructions and homeowner's manual

SUPREME

SUPREME FEM10-M2301CM-A Installation instructions and homeowner's manual

Johnson Controls TM9T User's information manual

Johnson Controls

Johnson Controls TM9T User's information manual

Fluke 9118A user manual

Fluke

Fluke 9118A user manual

Lennox EL195UHE Elite Series Unit information

Lennox

Lennox EL195UHE Elite Series Unit information

Intertherm M7RL Series user manual

Intertherm

Intertherm M7RL Series user manual

HDG Pelletmaster 15 Operation manual

HDG

HDG Pelletmaster 15 Operation manual

Nortek MG2S Series installation instructions

Nortek

Nortek MG2S Series installation instructions

VERDER CARBOLITE GERO ABF 8/28 Installation, operation and maintenance instructions

VERDER

VERDER CARBOLITE GERO ABF 8/28 Installation, operation and maintenance instructions

Goodman GMV9 Installation & operating instructions

Goodman

Goodman GMV9 Installation & operating instructions

SUPREME SUP10-M2301C Installation instructions and homeowner's manual

SUPREME

SUPREME SUP10-M2301C Installation instructions and homeowner's manual

Dettson AMT400B34-SM1PMA Installation instructions and homeowner's manual

Dettson

Dettson AMT400B34-SM1PMA Installation instructions and homeowner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING,
CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is
only used on product labels to signify an immediate
hazard. The signal words WARNING, CAUTION,
and NOTE will be used on product labels and
throughout this manual and other manual that may
apply to the product.
DANGER - Immediate hazards which will result in
severe personal injury or death.
Signal Words in Manuals
The signal word WARNING is used throughout
this manual in the following manner:
The signal word CAUTION is used throughout
this manual in the following manner:
WARNING - Hazards or unsafe practices which
could result in severe personal injury or death.
CAUTION - Hazards or unsafe practices which
may result in minor personal injury or product or
property damage.
NOTE - Used to highlight suggestions which will
result in enhanced installation, reliability, or
operation.
Signal Words on Product Labeling
Signal words are used in combination with
colors and/or pictures or product labels.
z_ Safety-alert symbol
When you see this symbol on the unit and in
instructions or manuals, be alert to the
potential for personal injury.
TABLE OF CONTENTS
Safety considerations ........................... 4
Safe Installation Requirements ................... 4
Installation ..................................... 6
Combustion & Ventilation Air ..................... 10
Vent and Combustion Air Piping .................. 14
Concentric Termination .......................... 32
Gas Supply and Piping .......................... 33
Electrical Wiring ................................ 38
Ductwork and Filter ............................. 39
Checks and Adjustments ........................ 42
Furnace Maintenance ........................... 45
Sequence of Operation & Diagnostics ............. 46
Technical Support .............................. 48
Use of the AHRI Certified TM Mark indicates a
manufacturer's participation in the program.
For verification of certification for individual
products, go to www.ahridirectory.org .
International Comfort Products, LLC
Lewisburg, TN 37091 U.S.A.
www.icpusa.com
PERSONAL INJURY, AND/OR PROPERTY
DAMAGE HAZARD
Failure to carefully read and follow this warning could
result in equipment malfunction, property damage,
personal injury and/or death.
Installation or repairs made by unqualified persons could
result in equipment malfunction, property damage,
personal injury and/or death.
The information contained in this manual is intended for
use by a qualified service technician familiar with safety
procedures and equipped with proper tools and test
instruments.
Installation must conform with local building codes and
with the Natural Fuel Gas Code (NFCG) NFPA 54/ANSI
Z223.1, and National standards of Canada
CAN/CSA-B149.1 and .2 Natural Gas and Propane
Installation Codes.
INSTALLER: Affix these instructions on or adjacent to the
furnace.
CONSUMER: Retain these instructions for future
reference.
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1-2009_, with permission of National Fire Protection Association, Quincy, MA 02269 and American Gas Association, Washington, DC
20001. This reprinted material is not the complete and official position of the NFPA or ANSi, on the referenced subject, which is represented only by the standard in its entirety.
PrintedinU.S.A. 440 01 1024 04 Dec. 2010
Required Notice for Massachusetts Installations
(a)
Important
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows:
5.08: Modifications to NFPA-54, Chapter 10
2) Revise 10.8.3 by adding the following additional requirements:
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential
purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet
above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1, INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the
installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor
level where the gas equipment is to be installed, in addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired
carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall
horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified license
professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirement; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall
comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet
above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall
read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
4. INSPECTION. The state of local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless,
upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a) 1 through 4:
(c)
(d)
(e)
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the
Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by
the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side
wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the
following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed
installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists
for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
For questions regarding these requirements, please contact the Commonwealth of Massachusetts Board of State Examiners of Plumbers and Gas
Fitters, 239 Causeway Street, Boston, MA 02114. 617-727-9952
440 01 1024 04 Specifications are subject to change without notice. 2
START-UP CHECK SHEET
For 90+ Furnace
(This sheet is optional. Keep this page for future reference.)
Date of Start-Up:
Dealer Name:
Address:
City, State(Province), Zip or Postal Code:
Phone:
Owner Name:
Address:
City, State(Province), Zip or Postal Code:
Model Number:
Serial Number:
Setup Checks
Check the box when task is complete
All Electrical Connections Tight?
Have hoses been relocated for furnace application
(upflow/horizontal)?
Condensate Drain Connected?
Condensate Drain Trapped?
Manual Gas Shut-Off Upstream of Furnace/Drip-Leg?LU
Gas Valve turned ON? Lj
Type of Gas: Natural: Lj Propane: Lj
Calculated Firing Rate:(See Checks and
Section).
Heating Check
Measured Line Pressure when Firing Unit:
Adjustments
Measured Manifold Gas Pressure:
Temperature of Supply Air:
Temperature of Return Air:
Temperature Rise (supply-return temperature): (o)__
In Rise (see furnace rating plate)? (o)__
Static Pressure (Ducts): Supply Air Return
Which blower speed tap is used? (Heating)
Optional Check: CO ? CO2 ?
Cooling Check
Temperature of Supply Air:
Temperature of Return Air:
Temperature Difference:
Static Pressure (Ducts) cooling: Supply Air
Blower Speed Tap used for cooling:
Dealer Comments:
o)__
(o)__
(o)__
__ Return
Filter Type and Size:
3 Specifications are subject to change without notice. 440 01 1024 04
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical shock,
or other conditions which may cause death, personal injury, or
property damage. Consult a qualified installer, service agency,
or your distributor or branch for information or assistance. The
qualified installer or agency must use factory-authorized kits or
accessories when modifyingthis product. Refer to the individual
instructions packaged with the kits or accessories when
installing.
Follow all safety codes. Wear safety glasses, protective
clothing, and work gloves. Use quenching cloth for
brazing operations. Have fire extinguisher available.
Read these instructions thoroughly and follow all
warnings or cautions included in literature and attached
to the unit. Consult local building codes, the current
editions of the National Fuel Gas Code (NFCG) NFPA
54/ANSI Z223.1, and the National Electrical Code (NEC)
NFPA 70.
In Canada refer to the current editions of the National
standards of Canada CAN/CSA-B149.1 and .2 Natural
Gas and Propane Installation Codes, and Canadian
Electrical Code CSA C22.1.
Recognize safety information. This is the safety-alert
symbol z_. When you see this symbol on the unit and in
instructions or manuals, be alert to the potential for
personal injury. Understand these signal words;
DANGER, WARNING, and CAUTION. These words are
used with the safety-alert symbol. DANGER identifies the
most serious hazards which will result in severe personal
injury or death. WARNING signifies hazards which could
result in personal injury or death. CAUTION is used to
identify unsafe practices which may result in minor
personal injury or product and property damage. NOTE is
used to highlight suggestions which will result in
enhanced installation, reliability, or operation.
Safe Installation Requirements
FIRE, EXPLOSION, AND ASPHYXIATION HAZARD
ELECTRICALSHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on unit, always turn off main power switch to unit and
install lockout tag. Unit may have more than one
power switch.
CARBON MONOXIDE POISONING AND FIRE
HAZARD
Failure to follow safety warnings could result in
personal injury, death, and/or property damage.
This furnace is not designed for use in mobile homes,
trailers or recreational vehicles.
CUT HAZARD
Failure to follow this caution may result in damage
personal injury.
Sheet metal parts may have sharp edges or burrs.
Use care and wear appropriate protective clothing,
safety glasses and gloves when handling parts and
servicing furnaces.
Improper adjustment, alteration, service,
maintenance or installation could cause personal
injury, death and/or property damage.
Installation or repairs made by unqualified persons
could result in hazards to you and others.
Installation MUST conform with local codes or, in
the absence of local codes, with codes of all
governmental authorities having jurisdiction.
The information contained in this manual is
intended for use by a qualified service agency that
is experienced in such work, is familiar with all
precautions and safety procedures required in
such work, and is equipped with the proper tools
and test instruments.
NOTE: This furnace is design-certified by the CSA International
(formerly AGA and CGA) for installation in the United States and
Canada. Refer to the appropriate codes, along with this manual,
for proper installation.
•Use only the Type of gas approved for this furnace (see
Rating Plate on unit). Overfiring will result in failure of heat
exchanger and cause dangerous operation. (Furnaces
can be converted to Propane gas with approved kit.)
• Install this furnace only in a location and position as
specified in "Installation" of these instructions.
• Provide adequate combustion and ventilation air to the
furnace as specified in "Combustion and Ventilation Air" of
these instructions.
Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system only, as
specified in "Vent and Combustion Air Piping" of these
instructions.
Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for
the detection of leaks to check all connections, as
specified in "Gas Supply and Piping, Final Check" of these
instructions.
Always install furnace to operate within the furnace's
intended temperature-rise range with a duct system which
has an external static pressure within the allowable range,
as specified in "Technical Support Manual" of these
instructions. See furnace rating plate.
Specifications are subject to change without notice
44001 102404
• When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled
by a duct(s) sealed to the furnace casing and terminating
outside the space containing the furnace.
• A gas-fired furnace for installation in a residential garage
must be installed as specified in "Installation" of these
instructions.
• This furnace is not to be used for temporary heating of
buildings or structures under construction.
•This furnace is NOT approved for installation in
mobile homes, trailers or recreation vehicles.
• Seal around supply and return air ducts.
• Install correct filter type and size.
• Unit MUST be installed so electrical components are
protected from direct contact with water.
SafetyRules
Your unit is built to provide many years of safe and dependable
service providing it is properly installed and maintained. However,
abuse and/or improper use can shorten the life of the unit and
create hazards for you, the owner.
A. The U.S. Consumer Product Safety Commission encourages
installation of carbon monoxide alarms. There can be various
sources of carbon monoxide in a building or dwelling. The
sources could be gas-fired clothes dryers, gas cooking
stoves, water heaters, furnaces, gas-fired fireplaces, wood
fireplaces.
Carbon monoxide can cause serious bodily injury and/or
death. Carbon monoxide or "CO" is a colorless and odorless
gas produced when fuel is not burned completely or when the
flame does not receive sufficient oxygen.
a.
Therefore, to help alert people of potentially dangerous carbon
monoxide levels, you should have a commercially available
carbon monoxide alarm that is listed by a nationally
recognized testing agency in accordance with Underwriters
Laboratories Inc. Standard for Single and Multiple Station
Carbon Monoxide Alarms, ANSl/UL 2034 or the CSA 6.19-01
Residential Carbon Alarming Devices installed and
maintained in the building or dwelling concurrently with the
gas-fired furnace installation (see Note below). The alarm
should be installed as recommended by the alarm
manufacturer's installation instructions.
There can be numerous sources of fire or smoke in a building
or dwelling. Fire or smoke can cause serious bodily injury,
death, and/or property damage. Therefore, in order to alert
people of potentially dangerous fire or smoke, you should have
fire extinguisher and smoke alarms listed by Underwriters
Laboratories installed and maintained in the building or
dwelling (see Note below).
Note: The manufacturer of your furnace does not test any alarms
and makes no representations regarding any brand or type
of alarms.
C.
1.
2.
To ensure safe and efficient operation of your unit, you should
do the following:
Thoroughly read this manual and labels on the unit. This
will help you understand how your unit operates and the
hazards involved with gas and electricity.
Do not use this unit if any part has been under water.
Immediately call a qualified service technician to inspect the
unit and to replace any part of the control system and any gas
control which has been under water.
3. Never obstruct the vent grilles, or any ducts that provide
air to the unit. Air must be provided for proper combustion
and ventilation of flue gases.
FrozenWater Pipe Hazard
WATER DAMAGE TO PROPERTY HAZARD
Failure to follow this caution may result in property
damage.
Do not leave your home unattended for long periods
during freezing weather without turning off water
supply and draining water pipes or otherwise
protecting against the risk of frozen pipes and
resultant damage.
Your furnace is designed solely to provide a safe and comfortable
living environment. The furnace is NOT designed to ensure that
water pipes will not freeze. It is equipped with several safety
devices that are designed to turn the furnace off and prevent it from
restarting in the event of various potentially unsafe conditions.
If your furnace remains off for an extended time, the pipes in your
home could freeze and burst, resulting in serious water damage.
If the structure will be unattended during cold weather you should
take these precautions.
1. Turn off the water supply to the structure and drain the water
lines if possible and add an antifreeze for potable water to
drain traps and toilet tanks. Open faucets in appropriate
areas.
2.
3.
-or-
Have someone check the structure frequently during cold
weather to make sure it is warm enough to prevent pipes
from freezing. Instruct them on a service agency to call to
provide service, if required.
-or-
Install a reliable remote sensing device that wilt notify
somebody of freezing conditions within the home.
WinterShutdown
If you go away during the winter months and do not leave the heat
on in your home, the plastic transition box and the condensate trap
on the furnace must be protected from freeze damage.(See
Figure 11 trough Figure 20)
1. Disconnect the 5/8"(15.9mm) OD rubber hose from the vent
drain fitting that is located downstream of the combustion
blower. Insert a funnel into the hose and pour four(4) ounces
of sanitary type (RV) antifreeze into the condensate trap.
Reconnect the 5/8"(15.9mm) OD rubber hose to the stub on
the vent drain fitting. Secure with the hose clamp.
2. Disconnect the 3/4" (15.9mm)OD rubber hose from the
condensate trap. Insert a funnel into the hose and and pour
four(4) ounces of sanitary type (RV) antifreeze into the
plastic Transition box. Squeeze the hose together near the
end and quickly reconnect the 3/4" (19.1mm) OD rubber
hose to the stub on the condensate trap. Secure with the
hose clamp.
When you return home, your furnace will be ready to start, as it is
not necessary to drain the antifreeze from the furnace.
44001102404
Specifications are subject to change without notice
Installation
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in
personal injury or death.
This furnace can NOT be common vented or
connected to any type B, BW or L vent or vent
connector, nor to any portion of a factory-built or
masonry chimney. If this furnace is replacing a
previously common-vented furnace, it may be
necessary to resize the existing vent and chimney to
prevent oversizing problems for the other
remaining appliance(s). See Venting and Combus-
tion Air Check in Gas Vent Installation section. This
furnace MUST be vented to the outside.
Location and Clearances
1. Refer to Figure 1 or Figure 2 for typical installation and
basic connecting parts required. Refer to Figure 5 for
typical horizontal direct vent installation and basic
connecting parts required. Supply and return air plenums
and duct are also required.
2. If furnace is a replacement, it is usually best to install the
furnace where the old one was. Choose the location or
evaluate the existing location based upon the minimum
clearance and furnace dimensions (Figure 3).
Typical Upflow Installation
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
Aluminumornon-rustingshieldrecommended.(SeeVent
TerminationShieldingfordimensions).
"8" (203.2mm) Min.
20 (6.1m) Max. , _ i Couplingonendsof
in same _1 I_ /_ exhaust pipe. Total
atmospheric [_ __ !_tuP_d0n // I_\pipe s c°upling°ut-
___ 5' U_ ._ _ side structure = 8"
zune _ _ Singleffipe / J;
_/._ _-I> model) '_ (203.2omm!
_ _,_ "-..........
VentPipes MUSTbe = .._
supported _ _" ....
=*8 2032mm)MIn
Horizontallyand o /. , ' '
Vertically _" i 20 6.1m)Max.
I, " i ins_[meatmosphericzone
* Increaseminimumfrom8"(203.2mm)to 18"(457.2mm)for coldclimates(sus-
tainedtemperatures0°F (-17°C)andbelowfor24ormoreconsecutivehours),
25-23-33
Typical Downflow Installation
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
SeeVentTermination
Shieldingin VentSection. Coupling on inside
\ andoutsideofwallto
\,, restrainventpipe
InletPipe _[Z;i I_ "8" (203.2mm)Min. \ /'\ /
(notusedonF [ _ 20' (6 lm_ Max in '_, /, 8" Min
• • \" /'\/i _ '
S,ngle.P,pe_ L<lJ) sameatmosphericzone \ _" / i
moael} .... \/_ ._.
,'_" _ •i,_
_ ' ,_ _ ',
VentPipesMUST -- : -_--_ _ .....A
be supported Hori- _ u_::_
zontallyandVertically _ i "8" (-_03.2mm) Min.
i 20'( .1m)Max.
-_ in s_me
atmo.'phericzone
°[ i/
Dlscharge_
_
•Increaseminimumfrom 8" (203.2mm)to 18" (457.2mm)for coldclimates(sus-
tainedtemperatures0° F (-17°C)andbelowfor 24ormoreconsecutivehours),
25-23-33a
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in
personal injury or death.
Do NOT operate furnace in a corrosive atmosphere
containing chlorine, fluorine or any other damaging
chemicals, which could shorten furnace life.
Refer to Combustion & Ventilation Air section,
Contaminated Combustion Air for combustion air
evaluation and remedy.
FROZEN AND BURST WATER PIPE HAZARD
Failure to follow this caution may result in property
damage.
Special precautions MUST be made if installing
furnace in an area which may drop below freezing.
This can cause improper operation or damage to
equipment. If furnace environment has the potential
of freezing, the drain trap and drainline must be
protected. The use of electric heat tape or RV
antifreeze is recommended for these installations.
(See "Condensate Trap Freeze Protection Section")
Do NOT operate furnace in a corrosive atmosphere
containing chlorine, fluorine or any other damaging
chemicals. Refer to Combustion & Ventilation Air section,
Contaminated Combustion Air.
Specifications are subject to change without notice
44001 102404
InstallationRequirements
1. Install furnace level.
2. This furnace is NOT to be used for temporary heat of buildings
or structures under construction.
3.
4.
5.
6.
7.
Install the vent pipes as short as practical. (See Gas Vent
Installation section).
Do NOT install furnace directly on carpeting, tile or other
combustible material other than wood flooring.
Maintain clearance for fire safety and servicing. A front
clearance of 24" (609.6mm) required and 30" (762mm)
recommended for access to the burner, controls and filter.
See clearance requirements in Figure 3.
Use a raised base if the floor is damp or wet at times.
Residential garage installations require:
• Burners and ignition sources installed at least 18"
(457.2mm) above the floor.
8.
9.
Furnace must be located or physically protected from
possible damage by a vehicle.
If the furnace is to be suspended from the floor joists in a
basement or a crawl space or the rafters in an attic, it is
necessary to use steel pipe straps or an angle iron frame to
attach the furnace. These straps should be attached to the
furnace with sheet metal screws and to the rafters or joists
with bolts. The preferred method is to use an angle iron frame
bolted to the rafters or joists.
Local codes may require a drain pan under the entire furnace
and condensate trap when the furnace is installed in attic
application.
This furnace may be used for construction heat provided that all
the following conditions are met:
The furnace is permanently installed with all electrical
wiring, piping, venting and ducting installed according to
these installation instructions. A return air duct is provided,
sealed to the furnace casing, and terminated outside the
space containing the furnace. This prevents a negative
pressure condition as created by the circulating air blower,
causing a flame rollout and/or drawing combustion products
into the structure.
• The furnace is controlled by a thermostat. Itmay not be "hot
wired" to provide heat continuously to the structure without
thermostatic control.
Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and
other construction materials. It also prevents the
entrainment of drywall dust into combustion air, which can
cause fouling and plugging of furnace components.
The temperature of the return air to the furnace is
maintained between 55° F (13° C) and 80° F (27° C), with no
evening setback or shutdown. The use of the furnace while
the structure is under construction is deemed to be
intermittent operation per our installation instructions.
The air temperature rise is within the rated rise range on the
furnace rating plate, and the firing rate has been set to the
rating plate value.
The filters used to clean the circulating air during the
construction process must be either changed or thoroughly
cleaned prior to occupancy.
The furnace, ductwork and filters are cleaned as necessary
to remove drywall dust and construction debris from all
HVAC system components after construction is completed.
After construction is complete, verify furnace operating
conditions including ignition, input rate, temperature rise
and venting according to these instructions.
44001102404
Specifications are subject to change without notice
Dimensions & Clearances
--1 F
TO P "\-
/
-_ E
........ AIR INTAKE
_..z-Iz" fVENT (N9MPD & *9MPD)
'_ t H
21/_
]
LEFT SIDE ,611/1__
TRAP(KO)(COUNTERFLOW)_ _
GAS...
VENT ........_J.)
AIRINTAKE(KO) ,/_,,
(ALTERNATE) 4:1:_116"_J)
i
TRAP (KO) (122.2) _
UPFLOW/HORIZONTAL.............
•THERMOSTAT //'k __ 7--_
(177.8)
215/8 I47/8
(549.3) (123.8)
24
(609.6)
ELECTRICAL
11/4
(32)
13/B
(34.9)
175/16 1913/16
(439.7) (503.2)
111/16I
(42i9)
A
FRONT
MINIMUM CLEARANCES TO
COMBUSTIBLE MATERIALS FOR ALL UNITS
REAR 0
FRONT (combustion air openings 3" (76.2)
in furnace and in structure)
Required For Service *24" (609.6)
ALL SIDES Of SUPPLY PLENUM 1" (25.4)
SIDES 0
VENT 0
TOP OF FURNACE 1" (25.4)
*30" (762mm)dearancerecommendedforfurnaceremoval.
Horizontalposition:Linecontactispermissibleonlybetween
linesformedbyintersectionsoftopandtwosidesoffurnace
jacket,andbuildingjoists,studsorframing.
NOTE: Evaporator "A" coil drain pan dimensions may
vary from furnace duct opening size. Always consult
evaporator specifications for duct size
requirements.
Furnace is designed for bottom return or side
return.
Return air through back of furnace is NOT allowed,
(31.7)
BOTTOM
.... 231/8
C (587.4)
Cabinet
Unit
Capacity
N9MP1040/050B^^
N9MP1060/075B^^
N9MP1080/100F^^
N9MPl100/125J^^
N9MP2050/075B^^
N9MP2080/100F^^
N9MP2100/125J^^
N9MPD040/050F^^
N9MPD060/075F^^
N9MPD080/100J^^
N9MPD125L^^
*9MPD050/075F^^
*9MPD080/100J^^
*9MPD125L^^
* Denotes Brand
^^ Cooling Air Flow
_ 37/8
(98.4)
ALL DIMENSIONS -IN(MM)
1in=25,4mm
Bottom Top
23/8(60)_
11/16(27)_
GAS.. \
1110
(10) 413/16_
_, (122)
I r;I '/18 .........
27
91 /16 (6 I1)/
{2'I}3
175/16
(440)111,
/
/281/2(724)
r
/' RIGHT SIDE
,' / TRAP(COUNTERFLOW)
ELECTRICAL(KO)
_- I AIR INTAKE (KO)
_. ).......... (ALTERNATE)
_J
_/t, ' VENT(KO)
_\]-) TRAP(KO)
C- UPFLOW/HORIZONTAL
(178) \ 21/4(57)
THERMOSTAT T
1
(489)
47/8 215/8
(124) - (549)
24
(610)
(KO)
3L
17/8
(48)
KO = KnockOut 25-23-36b
Drawing is representative, but some models may vary
8 44001 102404
Specifications are subject to change without notice
KnockOuts for upflow and downflow installations or top to bottom for horizontal
installations.
CUT HAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs.
Use care and wear appropriate clothing, safety
glasses and gloves when handling parts and
servicing furnaces.
Use a hammer and screwdriver to strike a sharp blow (See
Figure 4) directly to the knockout tie points or use a hammer in the
upper left corner of the desired knockout. Remove any burrs and
sharp edges.
Hammer and Screwdriver used
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiifor Knockout
!'
25-40-06
NOTE: If a knockout does not come out after two sharp blows, pull
and snip as needed to remove the knockout.
InstallationPositions
This furnace can be installed in an upflow, horizontal (either left or
right) or downflow airflow position. DO NOT install this furnace on
its back. For the upflow position, the return air ductwork can be
attached to either the left or right side panel and/or the bottom. For
horizontal and downflow positions, the return air ductwork must be
attached to the bottom. The return air ductwork must never be
attached to the back of the furnace.
FurnaceInstallationConsiderations
The installation of the furnace for a given application will dictate the
position of the furnace, the airflow, ductwork connections, vent and
combustion air piping. Consideration must be given to the
following:
CondensateTrapand DrainLines
The supplied condensate trap must be attached to the furnace
side panel on either the left or right side. For horizontal
installations, the drain trap is vertically attached to the side panel
below the furnace. A minimum clearance of 6" (152.4mm) below
the furnace is required for the condensate trap. Downward slope of
the condensate drain line from the condensate trap to the drain
location must be provided. Adequate freeze protection of the drain
trap and the drain line must be provided. See "Condensate Drain
Trap" section for further details.
Leveling
Proper leveling of the furnace must be provided to insure proper
drainage of the condensate from the furnace. The furnace must be
level to within 1/4" (6.4mm) from front to back and from side to side
44001102404
Ventand Combustion Air Connections
For venting information literature, call 931.270.4100 with the
complete model and serial number of the furnace.
Special Venting Requirements for Installations in Canada
Installation in Canada must conform to the requirements of CSA
B149 code. Vent systems must be composed of pipe, fittings,
cements, and primers listed to ULC S636. The special vent fittings
and accessory concentric vent termination kits and accessory
external drain trap have been certified to ULC S636 for use with
those Royal Pipe and IPEX PVC vent components which have
been certified to this standard. In Canada, the primer and cement
must be of the same manufacturer as the vent system - GVS-65
Primer (Purple) for Royal Pipe or IPEX System 636, PVC/CPVC
Primer, Purple Violet for Flue Gas Venting and GVS-65 PVC
Solvent Cement for Royal Pipe or IPEX System 636(1),M,PVC
Cement for Flue Gas Venting, rated Class IIA, 65 deg C. must be
used with this venting system - do not mix primers and cements
from one manufacturer with a vent system from a different
manufacturer. Follow the manufacturer's instructions in the use of
primer and cement and never use primer or cement beyond its
expiration date.
The safe operation, as defined by ULC S636, of the vent system is
based on following these installation instructions, the vent system
manufacturer's installation instructions, and proper use of primer
and cement. All fire stop and roof flashing used with this system
must be UL listed material. Acceptability under Canadian
standard CSA B149 is dependent upon full compliance with all
installation instructions. Under this standard, it is recommended
that the vent system be checked once a year by qualified service
personnel.
The authority having jurisdiction (gas inspection authority,
municipal building department, fire department, etc) should be
consulted before installation to determine the need to obtain a
permit.
(1) System 636 is a trademark of IPEX Inc.
Consignes sp6ciales pour I'installation de ventillation au
Canada
L'installation faite au Canada doit se conformer aux exigences du
code CSA B149. Ce syst_me de ventillation doit se composer de
tuyaux, raccords, ciments et appr_ts conformes au ULC S636. La
tuyauterie de ventillation des gaz, ses accessoires, le terminal
concentrique mural ainsi que I'ensemble du drain de condensat
exterieur ont et6 certifies ULCS 636 pour I'application des
composantes Royal Pipe, IPEX PVC qui sont certifiees & ce
standard. Au Canada, I'appr_t et le ciment doivent _tre du m_me
fabricant que le systeme d'evacuation. Uappr_t GVS-65 (Purple)
et le ciment-solvant GVS-65 doivent _tre utilise avec les Royal
Pipe. Systeme IPEX 636, appr_t PVC/CPVC, Purple pour
evacuation des gaz de combustion et systeme IPEX 636(1)'_,
ciment PVC pour evacuation des gaz de combustion, cote classe
IIA, 65 deg C. doivent _tre utilises avec le systeme d'evacuation
IPEX 636 - Ne pas combiner I'appr_t et le ciment d'un
manufacturier avec un systeme d'evacuation d'un manufacturier
different.
Bien suivre les indications du manufacturier Iors de t'utilisation de
I'appr_t et du ciment et ne pas utiliser ceux-ci si la date d'expiration
est atteinte.
Uoperation securitaire, tel que definit par ULC S636, du systeme
de ventilation est base sur les instructions d'installation suivantes,
ainsi que I'usage approprie de I'appr_t et ciment. Tout arret feu et
solin de toit utilises avec ce systeme doivent _tre des materiaux
listes UL. Uacceptation du standard Canadien CSA B419 est
directement relie& l'instaltation conforme aux instructions ci- haut
Specifications are subject to change without notice
mentionnees. Le standard Canadien recommande I'inspection
par un personel qualifie et ce, une fois par annee.
Les autoritees ayant juridiction (inspecteurs de gas, inspecteurs
en b&timents, departement des incendies, etc) devraient _tre
consultees avant I'instatlation afin de determiner si un permis est
requis.
On the N9MPD or *9MPD furnace, the vent and combustion air
pipes attach to the furnace through the top panel for the upflow and
horizontal installations. For the downflow installation, the vent and
combustion air pipes attach to the furnace through the alternate
locations on the furnace side panels.
Note: On the N9MP2 furnace, the vent pipe attaches to the furnace
through the side panels. The combustion air pipe attaches to the
top panel or to the alternate location on the side panel.
On the Single Pipe furnace, the vent pipe attaches to the furnace
through the furnace side panels.
Note: Repositioning of the combustion blower is required for the
vent pipe connection to the furnace through the "right side" panel.
See "Vent and Combustion Air Piping" section for further details.
HorizontalFurnaceInstallation
This furnace can be installed horizontally in an attic, basement,
crawl space, alcove, or suspended from a ceiling in a basement or
utility room. See Figure 5. Do not install furnace on its back or in
the reverse airflow positions as safety control operation will be
adversely affected.
If the furnace is to be installed in a crawl space, consult local
codes. A suitable concrete pad or blocks are recommended for
crawl space installation on the ground.
NOTE: 6" (152.4mm) bottom clearance required for condensate
trap.
24"(609.6mm) between the front of the furnace and adjacent
construction or other appliances MUST be maintained for service
clearance. 30" (762mm) inches is required to remove furnace.
Typical Horizontal Installation
Att i C
Inlet Pipe/(not....used_?_onSinglePipemodel)
Vent
Pipe-_
_ z/ Condensate
.!_ Trap
-%. \J_
25-23-34
NOTE: 6"(152.4mm)bottomclearancerequiredfor condensatetrap.
Auxiliarydrain panis requiredif over a finished living space.
Keep all insulating materials clear from Iouvered door. Insulating
materials may be combustible.
The horizontal furnaces may be installed directly on combustible
wood flooring or supports as long as all required furnace
clearances are met. See Figure 5.
This furnace MUST NOT be installed directly on carpeting or tile or
other combustible material other than wood flooring or supports.
For horizontal installation over a finished living space. A field
fabricated auxiliary drain pan with drain pipe is required to prevent
damage by overflow due to blocked condensate drain.
Combustion & Ventilation Air
ForSinglePipeInstallation
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in
personal injury or death.
Provide adequate combustion and ventilation air.
Use methods described here to provide
combustion and ventilation air.
Furnaces require ventilation openings to provide sufficient air for
proper combustion and ventilation of flue gases. All duct or
openings for supplying combustion and ventilation air must
comply with the gas codes, or in the absence of local codes, the
applicable national codes.
Combustion and ventilation air must be supplied in accordance
with one of the following:
Note: The Combustion & Ventilation Air Section in this document,
uses tables and information from the ANSI Z223.1/NFPA
54. For use in Canada, use CSA B149.1 for this information.
1. Section 9.3, Air for Combustion and Ventilation, of the National
Fuel Gas Code, (NFGC), ANSI Z223.1/NFPA 54-2009 in the
U.S.,
2. Sections 8.2, 8.3, 8.5, 8.6, 8.7, and 8.8 of National Standard of
Canada, Natural Gas and Propane Installation Code
(NSCNGPIC), CSA B149.1-05 in Canada,
3. Applicable provisions of the local building code.
This furnace can NOT be common vented or connected to any
type B, BW or L vent or vent connector, nor to any portion of a
factory-built or masonry chimney. Multistory venting is NOT
permitted. If this furnace is replacing a previously common-vented
furnace, it may be necessary to resize the existing vent and
chimney to prevent oversizing problems for the other remaining
appliance(s). See "Venting and Combustion Air Check" in this
section. This furnace MUST be vented to the outside.
When the installation is complete, check that all appliances have
adequate combustion air and are venting properly. See Venting
And Combustion Air Check in "Gas Vent Installation" Section in
this manual.
OutdoorCombustionAir Method
A space having less than 50 cubic feet per 1,000 BTUH (4.8 cubic
meters per kW) input rating for all gas appliances installed in the
space requires outdoor air for combustion and ventilation.
AirOpeningsand ConnectingDucts
1. Total input rating for all gas appliances in the space MUST be
considered when determining free area of openings.
2. Connect ducts or openings directly to the outdoors.
3. When screens are used to cover openings, the openings
MUST be no smaller than 1/4" (6.4mm) mesh.
4. The minimum dimension of air ducts MUST NOT be less than
3" (76.2mm).
10
Specifications are subject to change without notice
44001 102404