Impact Test Equipment AG250 User manual

www.impact-test.com
User Guide
User Guide
www.impact-test.com
www.impact-test.co.uk
www.impact-testsets.co.uk
Frost Heave Cabinet
AG250
Impact Test Equipment Ltd
www.impact-test.co.uk -www.impact-test.com
www.impact-testsets.co.uk

www.impact-test.co.uk www.impact-test.com www.impact-testsets.co.uk
Impact Test Equipment Ltd.
Building 21 Stevenston Ind. Est.
Stevenston
Ayrshire
KA20 3LR
T: 01294 602626
F: 01294 461168
E: sales@impact-test.co.uk
Test Equipment
www.impact-test.co.uk
Test Sieves & Accessories
www.impact-test.com
Test Sets to International Standards
www.impact-testsets.co.uk

www.impact-test.co.uk www.impact-test.com www.impact-testsets.co.uk
This equipment has been designed to meet the requirements of BS 812-124:2009
You will need to have a copy of this standard to refer to.
1. UNPACKING
1.1 Remove all packing material and place on a flat floor. It is important that the unit is level. Use the
self-levelling feet with an accurate spirit level instrument. Connect the drain to the fitting at the rear of
the Frost Heave. The Frost Heave is fitted with an automatic level filling system, however, with the nature
of the test, frost forms which condenses later and hence the unit will always be required to be connected
to the drain.
1.2 The unit has been pre-set to fill to 2mm below the samples, this can be adjusted by +/- 5 mm up
or down. To change the controlled fill height, adjust the framework holding the water tanks up and down
using the manual level control screws holding it in place. Raising the water framework will cause the
water level within the chamber to raise by the same amount. Alternatively, to lower the height, lower the
framework by that amount and then drain a little water out using the water drain valve.

www.impact-test.co.uk www.impact-test.com www.impact-testsets.co.uk
2. MAINS SUPPLY
2.1 240-volt units. Each unit comes supplied with a mains connection lead already fitted with a
correctly rated fuse. The fuse rating and other details for each unit is shown on the voltage plate riveted
to the back of the unit. It is important that, if the fuse needs to be replaced, it must only be replaced with
one of the correct rating. An integral RCD and MCB are also fitted within the control panel for added
electrical protection.
3. SET UP / OPERATION
3.1 Fill the top reserve tank with de ionised water and turn the unit on with the main black on/off
switch on the front panel.
3.2 Press the Level Control Button on the control panel. The screen should say ON and you will see
the water begin to fill into the bottom of the chamber. During filling, you will need to top of the reserve
water tank or the display will continuously state filling as will not get to the desired level. The system will
need around 45 litres of water to start. Refill the reserve tank with more de ionised water which will keep
the level constant during freezing and evaporation of the samples.
3.3 When the water level is close to the desired height, press the water pump button. If the button is
pressed too early, the display will change to Filling and only start to run when the level is high enough.
3.4 Check the height is correct as per the specification, if the level needs changing, follow step 1.2 in
chapter 1.
3.5 Position the lower 5 water probes in place using the guide bars. Follow the guide in BS 812-124
for the correct locations.
3.6 Place the wooden carry frame into the chamber
3.7 Place the test samples in the carry frame

www.impact-test.co.uk www.impact-test.com www.impact-testsets.co.uk
3.8 Position the 5 air probes into the top section of the chamber as per guidance from BS 812-124
3.9 Close lid, attached the upper frame and place the level guide rods through the 9 holes in the lid.
Connect your external displacement sensors to these guide rods (not supplied)
3.10 Leave the environment to settle as per guidance from BS 812-124
3.11 The air cooling and water heating can be controller independently and turned on or off as
required using buttons on the control system. As well as the main screen, there are LED indicators to
indicate if they are on and off. The value on the control screen shows the actual value. When you press
the Air Cooling Button, the onscreen timers starts to count up indicating the time the samples have been
under test conditions
3.12 To change set points, and control parameters including calibrations, scroll through the menu
pages using the up and down icon. They are set as the following
1Main Run Page
2Configure Air Temp
3Configure Water Temp
4Set Defrost Time
5Calibrate Air and Water Temperatures
3.13 To change air temperature set point
Press Down button to this page
Hold the Config button down for 5 seconds

www.impact-test.co.uk www.impact-test.com www.impact-testsets.co.uk
Press Enter Key to go to each value
Using the Up, Down, Left, Right keys, change to desired value
Press Configure Key to save value
Press Up Key to return to main run screen
3.14 To change water temperature set point
Press Down button twice to you get to the
Configuration Water Temp Screen
Repeat above procedures

www.impact-test.co.uk www.impact-test.com www.impact-testsets.co.uk
3.15 To change defrost time
Defrost time is the time in between each test that the unit requires to perform a defrost.
We recommend 3 hours in between each 96 hour test. This can be changes as follows
Press Down button 3 times
Hold the Config button down for 5 seconds
Change values as above and Save with the Configure Button
3.16 It may be required to calibrate the Frost Heave against reference sensors.
Press the down button 4 times
To apply a positive offset, highlight the sensor by holding the configure button down.
Increase the values of the sensor under calibration. (increase in 0.01 to start )
Save data
Check on previous screens that this new value represents the calibrated range, if not, repeat the
above.
To decrease the values, make the value lower

www.impact-test.co.uk www.impact-test.com www.impact-testsets.co.uk
3.17 Process data (5 air temperatures and 5 water temperatures) are constantly monitored during the
test on the recorder. The data views on the screen be changed by pressing the screen and the lower
blocks Mode, Menu & Group come on. Press up and down on the Mode to change views from test to
graph to all view. Press up and down on group to change from Air data to Water data. This data can be
exported via the USB socket, or connected onto your network via the rear mounted ethernet socket. A
full manual, and data reporting software is provided separately for the recorder. Ensure that before you
turn the control panel off, that you disable the recorder (or data may get corrupted.) To do this, press any
button on the screen, press MENU, press Safe shutdown, press YES.
Follow the online video tutorial in downloading the data and creating charts. Go to
https://www.youtube.com/watch?v=a50s-8b-jmQ

www.impact-test.co.uk www.impact-test.com www.impact-testsets.co.uk
3.18 At the end of the test, turn the following functions off by pressing the associated keys. Air
Cooling, Water Heating, Level Control and Water Pump. If you require to drain the system, ensure the
Level Control is turned off and open the manual water valve a shown in image below.
4. MAINTENANCE - ROUTINE CHECKS ON EACH OCCASION OF USE:
4.1 Check the condition of supply lead and plug top. These should be sound and undamaged.
4.2 Connect to mains supply and check:-
•Supply switch operation.
•Check the air cooling and water cooling switch turns cooling and heating off
4.3 With the plug disconnected, remove the panel under the control panel and ensure there is no
build up of dust around dirt around the fan and compressor unit.
4.4 Check the calibration of each sensor against a reference probe at the working temperature
range. Please note the probes will only be accurate at the working range hence 3 °C for water probes and
-18 °C for air probes.
5. PREVENTATIVE MAINTENANCE
Ensure that the unit is maintained in a clean, dry condition and when not in use, stored in a normal warm
atmosphere.
Minimum recommendation every six months:-
5.1 Check the plug top connections are tight and the fuse rating is correct.
5.3 Carry out an electrical safety check (Portable Appliances) using an appropriate appliance
tester operated by a competent person.
5.4 Check that the control temperature is maintained within limits. The manufacturer can offer the
above service on request.