manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Lennox
  6. •
  7. Furnace
  8. •
  9. Lennox G24MCE2-45 User manual

Lennox G24MCE2-45 User manual

Page 1
PRODUCT LITERATURE

2000 Lennox Industries Inc.
Dallas, Texas
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
INSTALLATION
INSTRUCTIONS
G24MCE Series
GAS-FIRED FURNACE
Direct Spark Ignition
503,95 M
05/2000
Supersedes 11/99
Ta le of Contents
G24MCE Unit Dimensions 2. . . . . . . . . . . . . . . . . . . .
G24MCE GasĆFired Furnace 3. . . . . . . . . . . . . . . . . .
Shipping and Packing List 3. . . . . . . . . . . . . . . . . . . . .
Requirements 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion, Dilution & Ventilation Air 4. . . . . . . . . .
Setting Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . .
Duct System 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Venting 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vertical Flue Using Metal Flue Pipe 9. . . . . . . . . . .
Vertical Flue Using Lined Masonry Chimney 11. .
Horizontal Flue Using Metal Flue Pipe 12. . . . . . .
Gas Piping 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Start-up 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Adjustments 19. . . . . . . . . . . . . . . . . . . . . . . . . . .
Service 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data Table 22. . . . . . . . . . . . . . . . . . . . . . . .
Ignition Control Board Diagnostic Codes 23. . . . . . .
Troubleshooting 24. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List 27. . . . . . . . . . . . . . . . . . . . . . . . . . . .
G24MCE Parts Arrangement 27. . . . . . . . . . . . . . . . .
G24MCE Start-up & Performance Check List 28. . .
WHAT TO DO IF YOU SMELL GAS:
If the information in this manual is not
followed exactly, a fire or explosion
may result causing property damage,
personal injury or loss of life.
WARNING
Do not store or use petrol or other
flamma le vapours and liquids in the
vicinity of this or any other appliance.
Installation and service must e perĆ
formed y a qualified installer, serĆ
vice agency or the gas supplier.
Do not try to light any appliance.
Do not touch any electrical switch; do not
use any telephone in your uilding.
Immediately call your gas supplier from a
neigh or's telephone. Follow the gas supĆ
plier's instructions.
If you cannot reach your gas supplier, call
the local fire rigade.
Extinguish any open flames.
Litho USA
Page 2
G24MCE Unit Dimensions - millimeters
G24MCE Series
SUPPLY
AIR
OPENING
A
B
*C
**C
RETURN AIR
KNOCKOUT
(Either Side)
Return Air
Opening
Return Air
Opening
GAS PIPING
INLET
(Both Sides)
ELECTRICAL
INLETS
(Both Sides)
FLUE
OUTLET
D
AIR FLOW
FRONT VIEW SIDE VIEW
TOP VIEW
F Left Side
G Right Side
752
*495
495
495
381
51
E
25
GAS PIPING
INLET
ELECTRICAL INLETS
(Top & Bottom)
19
105
*483
Unit shown in upflow position. Rotate 180° for
downflow applications and 90° clockwise or
counterclockwise for horizontal applications.
25
25
25
25
2525 25
*NOTE - The supply air opening is equipped with a 19 mm scored
flange that may e ent 90_ for plenum connection.
The dimensions shown were taken after the flange was ent.
The dou le scored flange at the front of the supply air
opening may e ent for a total opening dimension
(front to rear) of either 495 mm or 483 mm.
**NOTEĊ The return air opening is
equipped with a 19 mm scored flange
that may e ent 90_ for plenum conĆ
nection. The dimensions shown were
taken after the flange was ent.
Model No. A B C D E F G
G24MCE2Ć45
G24MCE3 0/75
mm
432
921
381
171
2
293
1 5
G24MCE3Ć 0/75
G24MCE4Ć75
mm 432 921 381 171 2 293 1 5
G24MCE4/5Ć100
mm
521
991
470
213
108
331
203
G24MCE4/5
Ć
100
G24MCE4/5Ć120 mm 521 991 470 213 108 331 203
G24MCE4/5 140
mm
591
991
540
248
108
329
180
G24MCE4/5Ć140 mm 591 991 540 248 108 329 180
Page 3
G24MCE GasĆFired Furnace
The G24MCE multi-position gas furnace is shipped ready
for installation in the upflow position. The unit can easily
be converted for installation in either downflow or horizonĆ
tal applications. The furnace is shipped with a bottom seal
panel in place for side return air in upflow applications.
Shipping and Packing List
Package 1 of 1 contains:
1 - Assembled unit
1 - Flue adapter (requires fieldĆinstallation)
1 - Upflow/horizontal filter rack
1 - Filter
The following additional items may be ordered separately,
if required:
1 - Additive base (downflow applications)
1 - Thermostat
1 - Hanging bracket kit
1 - External filter rack kit (downflow applications)
1 - LP Changeover kit
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
Requirements
Lennox G24MCE units carry CE marking and are certified
for installation in the following countries using the gas
categories shown:
II2H3P : GB, IE, ES, PT and CH
I2H : DK and IT
II2L3P : NL
II2Er3P : FR
I2ELL and I3P :DE
*I2E+(S) :BE
* Units for installation in Belgium are set and sealed for use with
G20 reference gas and must not e adjusted y installer.
Units must be adjusted or converted in accordance with
specific instructions provided by Lennox Industries prior
to installation or use in the other countries listed.
These appliances must only be installed, adjusted, conĆ
verted or serviced by properly qualified personnel. Failure
to comply with this requirements may result in a dangerĆ
ous situation.
The installation must comply with all relevant local and
national gas, electrical, building and fire regulations.
Proper ventilation is essential for safe operation and must
be provided as detailed in these instructions.
The flue system must be properly designed to comply with
any relevant regulations and the requirements set out in
these instructions.
Installation clearances must be provided around the apĆ
pliance and access provided for servicing requirements.
See figures 5, 7 and 9.
Before installation, check that the local distribution condiĆ
tions, nature of gas and pressure and adjustment of the
appliance are compatible.
NOTE-For installation on combustible floors, appliance shall
not be installed directly on carpeting, tile, or combustible maĆ
terial such as wood flooring Protection via a non-combusĆ
tible material must be provided
The G24MCE unit must not e installed in a residential
or commercial garage.
Unit must be adjusted to obtain a temperature rise within the
range specified on appliance rating plate.
G24MCE unit must be installed so that electrical compoĆ
nents are protected from water.
When furnace is used in conjunction with cooling units, it
shall be installed on the upstream side of cooling units to
avoid condensation in the heating compartment.
When installed, furnace must be electrically earthed in
accordance with national regulations.
Electrical supply must be properly fused and should be
provided with means of isolating the unit from the supply.
When the furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside of the space
containing the furnace, return air shall be handled by a
duct(s) sealed to the furnace casing and terminating outĆ
side of the space containing the furnace.
NOTE Ċ G24MCE series units must not be used as a
construction furnace" at any time during any phase of
construction Very low return air temperatures, harmful
vapors and misplacement of the filters will damage the
unit and its efficiency
The Lennox G24MCE furnace may be installed in alĆ
coves, cupboards, attics, basements, and utility rooms in
any of its approved installation positions.
The G24MCE unit must not e installed in a residential
or commercial garage.
The air furnace must not e installed in a room conĆ
taining a ath or shower. In addition, it is recomĆ
mended that the furnace should not e fitted in a edĆ
room.
A compartment used to enclose the air furnace must be
designed and constructed specifically for this purpose.
An existing cupboard or compartment may be used proĆ
vided that it is modified for the purpose.
WARNING
The Fan door must e securely in place when the
fan and urners are operating. Gas fumes, which
could contain car on monoxide, can e drawn into
living space resulting in personal injury or death.
General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
Page 4
In addition to the requirements outlined previously, the folĆ
lowing general recommendations should be considered
when installing the Lennox G24MCE furnace.
The furnace should be placed as close to the center of the
air distribution system as possible. The furnace should
also be located close to the chimney or vent termination
point.
Do not install the furnace where draughts might blow diĆ
rectly into it. This could cause improper combustion and
unsafe operation.
Do not block furnace combustion air openings with clothĆ
ing, boxes, doors, etc. Combustion air is needed for propĆ
er combustion and safe unit operation.
When the furnace is installed in an attic or other insulated
space, keep insulation away from the furnace.
WARNING
Product contains glass fi re.
Surface tears due to rough handling during shipĆ
ping or installation should e repaired straight
away to avoid respiratory, skin and eye irritation.
Com ustion, Dilution & Ventilation Air
In the past, there was no problem in bringing in sufficient outĆ
door air for combustion. Infiltration provided all the air that
was needed. In today's homes, tight construction practices
make it necessary to bring in air from outside for combustion.
Take into account that exhaust fans, appliance vents, chimĆ
neys, and fireplaces force additional air that could be used
for combustion out of the house. Unless outside air is brought
into the house for combustion, negative pressure (outside
pressure is greater than inside pressure) will build to the point
that a downdraft can occur in the furnace vent pipe or chimĆ
ney. As a result, combustion gases enter the living space
creating a potentially dangerous situation.
In the absence of local codes concerning air for combustion
and ventilation, this section outlines guidelines and recomĆ
mends procedures for installing G24MCE Furnaces in a
manner that ensures efficient and safe operation. Special
consideration must be given to combustion air needs as
well as requirements for exhaust vents and gas piping.
CAUTION
Do not install furnace in a corrosive or contaminated
atmosphere. Meet all com ustion and ventilation air
requirements, as well as all local codes.
CAUTION
Insufficient com ustion air can cause headaches,
nausea, dizziness or asphyxiation.
Com ustion Air Requirements
All gasĆfired appliances require air for the combustion
process. If sufficient combustion air is not available, the
furnace or other appliance will operate inefficiently and
unsafely. Enough air must be provided to meet the needs
of all fuelĆburning appliances and appliances such as exĆ
haust fans which force air out of the house. When fireĆ
places, exhaust fans, or clothes dryers are used at the
same time as the furnace, much more air is required to enĆ
sure proper combustion and to prevent a downdraft. InĆ
sufficient air causes incomplete combustion which can reĆ
sult in carbon monoxide.
In addition to providing combustion air, fresh outdoor air
dilutes contaminants in the indoor air. These contamiĆ
nants may include bleaches, adhesives, detergents, solĆ
vents and other contaminants which can corrode furnace
components.
The requirements for providing air for combustion and
ventilation depend largely on whether the furnace is
installed in an unconfined or a confined space.
Unconfined Space
An unconfined space is an area such as a basement or
large equipment room with a volume greater than 4.85m3
per 1 kW (50 ft3 per 1000 Btuh) of the combined input ratĆ
ing of all appliances installed in that space. This space
also includes adjacent rooms which are not separated by
a door. Though an area may appear to be unconfined, it
might be necessary to bring in outdoor air for combustion
if the structure does not provide enough air by infiltration.
If the furnace is located in a building of tight construction
with weather stripping and sealing around the windows
and doors, follow the procedures in the air from outside
section.
Confined Space
A confined space is an area with volume less than 4.85m3
per 1 kW (50 ft3 per 1000 Btuh of the combined input rating
of all appliances installed in that space. This definition inĆ
cludes furnace cupboards or small equipment rooms.
When the furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space containĆ
ing the furnace, the return air must be handled by ducts
which are sealed to the furnace casing and which terminate
outside the space containing the furnace. This is especially
important when the furnace is mounted on a platform in a
confined space such as a cupboard or small equipment
room. Even a small leak around the base of the unit at the
platform or at the return air duct connection can cause a poĆ
tentially dangerous negative pressure condition. Air for comĆ
bustion and ventilation can be brought into the confined
space either from inside the building or from outside.
Page 5
Air from Inside
If the confined space that houses the furnace adjoins a
space categorized as unconfined, air can be brought in by
providing two permanent openings between the two
spaces. Each opening must have a minimum free area of
22cm2 per 1 kW (1 square inch per 1000 Btuh) of total input
rating of all gas-fired equipment in the confined space. Each
opening must be at least 4 cm2 (100 square inches). One
opening shall be within 305mm (12 inches) of the top of the
enclosure and one opening within 305mm (12 inches) of the
bottom. See figure 1.
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM INSIDE
WATER
FURĆ
NACE
OPENINGS
(To Adjacent
Room)
NOTE-Each opening shall have a free area of at least 22cm2
per 1 kW (1 square inch per 1,000 Btuh) of the total input rating
of all equipment in the enclosure, but not less than 4 cm2
(100 square inches)
G24MCE
FURNACE
CHIMNEY
OR GAS
VENT
FIGURE 1
Air from Outside
If air from outside is brought in for combustion and ventilation,
the confined space must have two permanent openings.
One opening shall be within 305mm (12 inches) of the top
of the enclosure and one within 305mm (12 inches) of the
bottom. These openings must communicate directly or by
ducts with the outdoors or spaces (underfloor or attic) that
freely communicate with the outdoors or indirectly through
vertical ducts. Each opening shall have a minimum free area
of 5.5cm2 per 1 kW (1 square inch per 4000 Btuh) of total
input rating of all equipment in the enclosure. See figures 2
and 3. When communicating with the outdoors through horiĆ
zontal ducts, each opening shall have a minimum free area
of 3cm2 per 1 kW (1 square inch per 2000 Btuh) of total inĆ
put rating of all equipment in the enclosure. See figure 4.
When ducts are used, they shall be of the same cross-secĆ
tional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 75mm (3 inches). In calculating free
area, the blocking effect of louvers, grilles, or screens must
be considered. If the design and free area of protective covĆ
ering is not known for calculating the size opening required,
it may be assumed that wood louvers will have 20 to 25 perĆ
cent free area and metal louvers and grilles will have 0 to
75 percent free area. Louvers and grilles must be fixed in
the open position or interlocked with the equipment so that
they are opened automatically during equipment operation.
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(Inlet Air from Underfloor Space and Outlet Air to Ventilated Attic)
NOTE-The inlet and outlet air openings shall each have a free
area of at least 5 5cm2 per 1 kW (1 square inch per 4000 Btuh)
of the total input rating of all equipment in the enclosure
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR WATER
FURĆ
NACE
INLET
AIR
CHIMNEY
OR GAS
VENT
G24MCE
FURNACE
VENTILATION
LOUVERS
(For unheated underfloor
space)
FIGURE 2
Page 6
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
NOTE-The inlet and outlet air openings shall each have a free area
of at least 5 5cm2 per 1 kW (1 square inch per 4000 Btuh) of the total
input rating of all equipment in the enclosure
CHIMNEY
OR GAS
VENT
WATER
FURNACE
OUTLET
AIR
VENTILATION LOUVERS
(Each end of attic)
INLET AIR
[Ends 305mm
(12") above botĆ
tom]
G24MCE
FURNACE
FIGURE 3
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
OUTLET AIR
INLET AIR
WATER
FURNACE
CHIMNEY
OR GAS
VENT
NOTE-Each air duct opening shall have a free area of at least 3cm2 per 1 kW
(1 square inch per 2000 Btuh) of the total input rating of all equipment in the
enclosure If the equipment room is located against an outside wall and the
air openings communicate directly with the outdoors, each opening shall
have a free area of at least 5 5cm2 per 1 kW (1 square inch per 4000 Btuh) of
the total input rating of all other equipment in the enclosure
G24MCE
FURNACE
FIGURE 4
Setting Equipment
The Lennox G24MCE multi-position gas furnace can be
installed as shipped in upflow position or in horizontal
position with right-hand or left-hand discharge. The furĆ
nace can easily be converted for downflow applications.
Select unit location that will allow for required clearances
listed on the unit rating plate. Also consider gas supply
connections, electrical supply, vent connection and
installation and service clearances [ 10mm (24 in.)] at
unit front.
NOTE - 1/3 and 1/2 hp fan motors are equipped with eiĆ
ther four flexible mounting legs or three flexible legs and
one rigid leg The rigid leg is equipped with a shipping bolt
and a flat white plastic washer (rather than the rubber
mounting grommet used with a flexible mounting leg)
This shipping bolt and flat washer must be removed beĆ
fore the furnace is put into operation Once the shipping
bolt and washer are removed, the rigid leg will not touch
the fan housing
UPFLOW APPLICATIONS
The Lennox G24MCE furnace is shipped in a standard
upflow position. Level the furnace using shims or leveling
bolts. Knockouts are provided in unit base to install field-
provided leveling bolts. Allow for clearances to combusĆ
tible materials as indicated on the unit rating plate. MiniĆ
mum clearances for cupboard or alcove installations are
shown in figure 5.
In upflow applications, return air can be brought in
through the bottom or either side of the furnace. If a furĆ
nace with bottom return air is installed on a platform,
make an airtight seal between the bottom of the furnace
and the platform to ensure proper and safe operation.
Knockouts are provided on both sides of the furnace cabiĆ
net for installations with side return air. When side return
air is used, seal the bottom of the furnace using the panel
provided.
An upflow filter rack is provided. The adjustable rack can
be installed beneath the furnace (flush with cabinet
edges) for bottom return air applications or on the side of
the furnace for side return air.
NOTE - A sheet metal filter puller is provided along with
filter kit In bottom return air applications, filter puller must
be installed between frame and filter to hold filter in place
152mm (6 in.)
25mm (1 in.)
UPFLOW APPLICATION
INSTALLATION CLEARANCES
VENT
CONNECTOR
TYPE SINGLE WALL TWIN WALL
TOP
*FRONT 51mm (2 in.)
BACK
SIDES
FLUE 25mm (1 in.)
RIGHT
SIDE
LEFT
SIDE
TOP
BOTTOM
*Front clearance in alcove installation must e a miniĆ
mum of 610mm (24 in.) for service access.
**On com usti le floor with non-com usti le protecĆ
tion. NC - Non-Com usti le
**NC
BOTTOM **NC
51mm (2 in.)
25mm (1 in.)
25mm (1 in.)
25mm (1 in.)
25mm (1 in.)
25mm (1 in.)
FIGURE 5
Page 7
UNIT CONVERSION FOR DOWNFLOW APPLICATION
REMOVE
TOP CAP
REMOVE
BOTTOM
REMOVE
FOUR
SCREWS
DISCONNECT
WIRE HARNESS AT
CONTROL BOARD
CONNECTOR
DISCONNECT
IGNITOR & SENSOR
LEADS
REINSTALL
TOP CAP ON
UNIT BOTTOM
REINSTALL
BOTTOM
ON UNIT
TOP
ROTATE HEAT
EXCHANGER
& REINSTALL
RECONNECT
IGNITOR & SENSOR
LEADS
UPFLOW CONFIGURATION DOWNFLOW CONFIGURATION
SINGLE-WALLED VENT
PIPE FROM COMBUSTION
AIR FAN FLUE ADAPTER TO
FURNACE FLUE OUTLET
(Furnished y installer)
RECONNECT WIRE
HARNESS AT
CONTROL BOARD
CONNECTOR
FIGURE 6
DOWNFLOW APPLICATIONS
The Lennox G24MCE furnace is shipped in the upflow
configuration and must be converted for downflow instalĆ
lation. Refer to figure and the following steps to convert
the unit for downflow installation:
1 - Place unit on its back and remove access panel.
2 - Disconnect wire harness in control area.
3 - Disconnect ignition lead and sensor wire located in
burner box. Use pliers to remove strain relief plugs
from holes on side of burner box.
4 - Remove four no. 10 screws securing cabinet bottom
to unit and remove bottom.
5 - Remove four no. 10 screws securing cabinet top cap to
cabinet. Remove top cap and replace with bottom.
- Remove four screws holding heat exchanger assemĆ
bly in place. Slide heat exchanger out through top of
cabinet.
7 - Rotate heat exchanger 180o and slide back into cabiĆ
net through top. Resecure using four screws.
8 - Install cabinet bottom using four no. 10 screws.
9 - Position strain relief grommets on ignition and flame
sensor wires. Insert wires and grommets through
holes on side of burner box. Reconnect wires to igniĆ
tor and flame sensor.
10- Reconnect wire harness plug.
11- Replace unit access panel.
In downflow applications, the unit can be installed in three difĆ
ferent ways: on non-combustible flooring, on combustible
floor using an additive base, or on a reverse-flow cooling cabĆ
inet. Do not drag unit across floor.
Allow clearances to combustible materials as outlined on
unit rating plate. Minimum clearances for cupboard or alĆ
cove installations are outlined in figure 7.
A separate downflow filter kit is available for use in downĆ
flow applications. Filter rack provided with unit is for use in
horizontal or upflow applications only.
DOWNFLOW APPLICATION
INSTALLATION CLEARANCES
VENT
CONNECTOR
TYPE
SINGLE WALL TWIN WALL
TOP 25mm (1 in.)
*FRONT 51mm (2 in.)
BACK
SIDES
FLUE 152mm (6 in.) 25mm (1 in.)
TOP
BOTTOM
RIGHT
SIDE
LEFT
SIDE
NC - Non-com usti le floor
*Front clearance in alcove installation must e a min. of 610mm
(24 in.) for service access.
**With additive ase on com usti le floor.
BOTTOM NC** NC**
25mm (1 in.)
51mm (2 in.)
25mm (1 in.)25mm (1 in.)
25mm (1 in.)25mm (1 in.)
FIGURE 7
A-Installation on Non-Com usti le Flooring
1 - Cut floor opening keeping in mind the clearances
listed on the unit rating plate. Also, keep in mind gas
supply and electrical supply, vent connections and
sufficient installation and service clearances. See
table 1 for correct floor opening size.
Page 8
TABLE 1
NONCOMBUSTIBLE FLOOR OPENING
UNIT Front to Rear Side to Side
inmm inmm
G24MCE-45/60/75 502 388
NOTE-Floor opening dimensions lis ed are 6mm (1/4") larger
han uni openings.
19-3/4 15-1/4
G24MCE-100/120 502 47719-3/4 18-3/4
G24MCE-140 502 54619-3/4 21-1/2
2 - Flange warm air plenum and lower into opening.
3 - Set unit over plenum.
4 - Check to see that an adequate seal is made.
B-Installation on Com usti le Flooring
1 - When unit is installed on a combustible floor, an addiĆ
tive base (ordered separately) must be installed beĆ
tween the furnace and the floor. See table 2 for openĆ
ing size to cut in the floor.
TABLE 2
ADDITIVE BASE FLOOR OPENING
UNIT Front to Rear Side to Side
in mm in mm
G24MCE-45/60/75 556 440
NOTE-Floor opening dimensions lis ed are 1/4" (6mm) larger
han addi ive base openings.
21-7/8 17-5/16
G24MCE-100/120 556 52821-7/8 20-3/4
G24MCE-140 556 59721-7/8 23-1/2
G24MCE UNIT
SUPPLY AIR
PLENUM
ADDITIVE
BASE
PROPERLY
SIZED FLOOR
OPENING
1. Cut correct size floor opening
2. Set additive ase into opening.
3. Set supply air plenum into additive ase.
4. Set unit.
FIGURE 8
2 - After opening is cut, set the additive base into
opening.
3 - Check glass fibre strips on additive base to make
sure they are properly glued and positioned.
4 - Lower supply air plenum into additive base until pleĆ
num flanges seal against glass fibre strips.
5 - Set unit on additive base so unit flanges drop into pleĆ
num. Refer to figure 8.
NOTE-Be careful not to damage glass fibre strips
Check for tight seal
C-Installation on Cooling Ca inet
1 - Refer to reverse flow coil installation instructions for
correctly sized opening in floor and installation of
cabinet.
2 - When cooling cabinet is in place, install furnace so
flanges drop inside cabinet opening.
3 - Seal cabinet and check for air leakage.
HORIZONTAL APPLICATIONS
The Lennox G24MCE furnace can be installed in horizonĆ
tal applications in either upflow or downflow configuration
(See figure ). It is preferable to install the unit in the stanĆ
dard upflow configuration, if possible, because the vent
pipe will not interfere with service access for fan. The unit
cannot e installed on its ack.
Filter rack is provided. Adjustable rack can be installed
flush with cabinet edges.
Allow for clearances to combustible materials as indicated
on the unit rating plate. Minimum clearances for cupboard
or alcove installations are shown in figure 9.
HORIZONTAL APPLICATION
INSTALLATION CLEARANCES
VENT
CONNECTOR
TYPE
SINGLE WALL TWIN WALL
TOP 25mm (1 in.) 25mm (1 in.)
*FRONT 51mm (2 in.) 51mm (2 in.)
BACK
SIDES
FLUE 152mm (6 in.)
BOTTOM
TOP
RIGHT
SIDE
LEFT
SIDE
*Front clearance in alcove installation must e a miniĆ
mum of 610mm (24 in.) for service access.
**On com usti le floor with non-com usti le protection.
NC - Non-Com usti les
BOTTOM **NC **NC
25mm (1 in.) 25mm (1 in.)
51mm (2 in.) 51mm (2 in.)
25mm (1 in.)
FIGURE 9
Page 9
Furnaces may be installed in either an attic or a crawlspace.
See figure 10 for furnace installations on a platform.
NOTE - When the furnace is installed on a platform in a
crawlspace, it must be elevated enough to avoid water
damage and to allow the air conditioning coil to drain
Horizontal Application
Unit Installed on Platform
GAS
ENTRY
VENT
PIPE
NOTE - Line contact is permissible See the unit rating plate for clearances
NON-COMBUSTIBLE
WORKING PLATFORM
NON-COMBUSTIBLE
UNIT PLATFORM
FIGURE 10
Anyone of the following methods may be used to suspend
the furnace from roof rafters or floor joists:
1 - Using Lennox hanging bracket kit catalog number
4 J -
Install as indicated in the installation instructions
provided with the hanging bracket kit.
2 - Using angle iron with at least 1/4 in. diameter rods -
Install as shown in figure 11.
Note - Rods must not interfere with plenum or exĆ
haust piping; cooling coils and supply and re urn
air plenums mus be suppor ed separa ely.
Horizontal Application
Unit Suspended in Attic or Crawlspace
Using Angle Iron and Rods
1/4 in. ROD
ANGLE
IRON
SUPPORT TIES -
INSTALL TO PREVENT
SPREADING
Leave sufficient clearance between rod and unit to
remove access panels.
Level unit - side to side and end to end.
Secure the angle iron to the unit with sheetmetal screws:
maximum screw length - 3/4 in. and minimum screw size - # 10.
FIGURE 11
WARNING
Improper installation of unit can result in personal
injury or death. Flue gases must never e allowed
to enter the return air system or the living space.
Sheet metal screws and sealing tape should e
used to seal ducting to the furnace. In platform
installations, return air must always e ducted to
the unit. A unit must never e installed so that it
draws return air from the furnace cham er, attic or
underfloor space. The furnace platform must e
level with no sagging, cracks or gaps.
Furnaces must always e isolated from other heatĆ
ing appliances to prevent fire, explosion, and carĆ
on monoxide poisoning. Personal injury and/or
property damage could result..
Duct System
Use industryĆapproved standards to size and install the
supply and return air duct system. This will result in a quiet
and lowĆstatic system that has uniform air distribution.
SUPPLY AIR PLENUM
Furnaces installed without a cooling coil require the installaĆ
tion of a removable access panel in the supply air duct. The
access panel should be large enough to permit inspection
(either by smoke or reflected light) of the heat exchanger for
leaks after installation . The furnace access panel must alĆ
ways be in place when the furnace is operating and it must
not allow leaks into the supply air duct system.
RETURN AIR PLENUM
Return air must not e drawn from a room where
this furnace, or any other gas appliance (ie., a water
heater), is installed. When return air is drawn from a
room, a negative pressure is created in the room. If a
gas appliance is operating in a room with negative presĆ
sure, the flue products can be pulled back down the vent
pipe and into the room. This reverse flow of the flue gas
may result in incomplete combustion and the formation
of carbon monoxide gas. This toxic gas might then be
distributed throughout the house by the furnace duct
system.
In upflow applications, return air can be brought in
through the bottom or either side of the furnace. If a furĆ
nace with bottom return air is installed on a platform,
make an airtight seal between the bottom of the furnace
and the platform to ensure proper and safe operation.
Use fiberglass sealing strips between the plenum and the
furnace cabinet to ensure a tight seal. If a filter is installed,
size the return air duct to fit the filter frame.
Page 10
In downflow applications, use the following steps when
installing return air plenum:
1 - Flange bottom edge of plenum with a hemmed edge.
See figure 12.
2 - In all cases, secure the plenum to the top flanges of
the furnace using sheet metal screws. See figure 12.
SECURE
HEMMED EDGE
PLENUM
CABINET SIDE PANEL
FIGURE 12
3 - In cupboard installations, it may be necessary to
install sheet metal screws from the inside. If this is the
case, make plenum with a removable front to install
screws as shown in figure 13.
SECURE
FROM
INSIDE HEMMED EDGE
CABINET SIDE PANEL
PLENUM
FIGURE 13
Venting
The G24MCE unit is not certified for common venting.
A flue adapter is supplied with the furnace. It must be fieldĆ
installed between the induced draught fan flue outlet and
the flue connector using one or two corrosion-resistant
sheet metal screws. Modification of or failure to install
the adapter will cause unsafe unit operation and will
void unit certification. The flue adapter does not require
insulation.
VERTICAL FLUE USING METAL FLUE PIPE
The flue system should be of the same nominal diameter
as the adapter supplied with the unit and should be fitted
inside the adapter either directly or using a connector deĆ
signed for the flue system used. Where it is not possible to
use the same nominal diameter, a larger size may be
used with an appropriate conversion piece to suit the unit
adapter. A flue system of smaller nominal diameter than
the unit adapter must not be used.
NOTE - Use these instructions as a guide They do not suĆ
persede local codes
Size and install the G24MCE vertical flue per local codes
and regulations and these instructions.
See figure 14 for typical application of a vertical flue using
twin wall metal flue pipe.
DOUBLE
WALL
FLUE PIPE
VERTICAL FLUE USING METAL FLUE PIPE
FLUE
CONNECTOR
(Dou le-walled, single-walled pipe)
FLUE
ADAPTER
STORM COLLAR
FLASHING
FLUE CAP
.61M (2 FT.)
MINIMUM
MIN. LENGTH - AS SHORT AS PRACTICAL
MAXIMUM LENGTH - SEE NOTE AT SIDE
1M (3 FT.)
MINIMUM
HIGHEST FLUE
CONNECTOR
POINT
3.05M (10 FT.)
MINIMUM
1.5M (5 FT.)
MINIMUM
STRAIGHT PIPE
FIRST 152mm (6")
Note: See the regulations that are in force in the
country of installation for flue connector sizing.
FIGURE 14
Page 11
Recommendations and Requirements
When sizing and installing a vertical flue using metal flue
connectors and either metal flue pipe or a lined masonry
chimney, the following recommendations and requireĆ
ments should be considered in addition to those outlined
above:
1 - Accessories attached to the flue to reduce heat loss
and improve efficiency have not been tested for use
with this furnace.
2 - When the G24MCE furnace is replacing an existing
furnace, inspect the existing flue system for obstrucĆ
tions, corrosion and proper sizing.
3 - Make runs of single-walled or twin-walled metal pipe
used as flue connector easily accessible, so that it
can be inspected annually and cleaned and replaced
if necessary.
4 - See the regulations that are in force in the counĆ
try of installation for flue connector sizing.
5 - When the vent connector must be located in or pass
through a crawl space or other areas which may be
cold, that portion of the vent connector shall be a
listed twinĆwall flue pipe or a pipe of a material having
equivalent insulation qualities.
- Secure all joints with at least two corrosion-resistant
screws. Check all accessible joints for gas tightness
after installation.
WARNING
Failure to properly seal flue system could allow carĆ
on monoxide leakage resulting in injury or death.
7 - Make flue connector horizontal runs as short as posĆ
sible with a minimum number of elbows. One 90° elĆ
bow is equivalent to 1.5m (5 ft.) of straight pipe. One
45° elbow is equivalent to .75m (2.5 ft.) of straight
pipe.
8 - Horizontal runs of flue connector must rise at least
20mm per meter (1/4 in. per ft.) away from the furĆ
nace.
9 - Horizontal run length must not represent more than 75
percent of the vertical rise of the flue system.
10 - Support horizontal runs of flue connector with straps or
hangers, so that there are no dips or sags.
11 - Support the flue connector at 1m (3 ft.) intervals and
at all elbows.
12 - If single wall flue is used, fasten the flue adapter to the
flue outlet of the furnace and the flue connector to the
flue adapter using one or two corrosion-resistant
sheet metal screws. If twin walled flue pipe is used,
fasten according to manufacturer's instructions
13 - Install first flue connector elbow a minimum of in.
(152mm) from furnace flue outlet.
14 - Terminal location must not be within 00 mm (2 ft.) of
an openable window, air vent, or other ventilation
opening. Flue terminal must be located in accorĆ
dance with any national regulations applicable. A
flue guard must be fitted if required by the regulaĆ
tions.
15 - Fit a split flue socket immediately above the furnace
to facilitate servicing and maintenance.
1 - Flue pipes and fittings should be constructed of aluĆ
minium or stainless steel.
VERTICAL FLUE USING MASONRY CHIMNEY
The following additional requirements apply when a lined
masonry chimney is used to vent a G24MCE furnace:
See figure 15 for exterior chimney application.
Masonry chimneys that once served fireplaces cannot be
used for venting purposes unless the fireplace opening is
permanently sealed.
Tile-lined chimneys must be composed of a non-porous,
acid-resistant material. The internal diameter of the chimĆ
ney liner must not be less than the diameter of the furnace
flue adapter.
The G24MCE gas furnace must not be connected to a
chimney that is servicing a separate appliance which burns
solid fuel.
IMPORTANT
SINGLE appliance venting of a fanĆassisted furnace
into a tileĆlined masonry chimney (interior or outĆ
side wall) is PROHIBITED. The chimney must first
e lined with either twinĆwalled flue or an insulated
single wall flexi le vent lining system, sized in acĆ
cordance with the the regulations in force in the
country of installation.
Page 12
VENTING USING METAL-LINED
EXTERIOR MASONRY CHIMNEY
1.5m (5 FT.)
MINIMUM
SEALED
PERMANENTLY SEALED
FIREPLACE OPENING
EXTERIOR CHIMNEY WITH TWIN-WALLED LINER OR
INSULATED (FLEXIBLE) SINGLE-WALLED LINER.
Note: See the regulations that are in force in the
country of installation for flue connector sizing.
MIN. LENGTH - AS SHORT AS PRACTICAL
MAXIMUM LENGTH - SEE NOTE AT SIDE
HIGHEST FLUE
CONNECTOR POINT
FIGURE 15
Do not install a manual damper, barometric draught reguĆ
lator, or flue restrictor between the furnace and the chimĆ
ney. Remove any such existing devices.
If twin-wall flue is used inside a chimney, no other apĆ
pliance can be vented into the chimney. Outer wall of twin-
wall flue pipe must not be exposed to flue products.
If a flexible single-walled liner is used in a masonry chimĆ
ney, the liner must be insulated. Insulation for the flexible
vent pipe must be an encapsulated fiberglass sleeve recĆ
ommended by the flexible vent pipe manufacturer. See
figure 15.
If twin-wall flue or an insulated flexible vent pipe cannot be
used as liners, the chimney must be rebuilt to accommoĆ
date one of these methods or some alternate approved
method must be found to vent the appliance.
The space etween the liner and the chimney wall
should NOT e insulated with puffed mica or any othĆ
er loose granular insulating material.
When inspection reveals that an existing chimney is not
safe for the intended purpose, it shall be rebuilt to conform
to nationally recognized standards. The chimney pasĆ
sageway must be checked periodically to ensure that it is
clear and free of obstructions.
HORIZONTAL FLUE USING METAL FLUE PIPE
These instructions should be used as a guide and do not
supersede local codes in any way. Size and install the
G24MCE horizontal flue according to the national and loĆ
cal codes and regulations which are in effect in the counĆ
try of installation.
The following are specific requirements for installation of
the G24MCE furnace:
1 - Install first flue connector elbow a minimum of
152mm ( in.) from the furnace flue outlet.
2 - If the flue is sloped upward as it is routed away from
the furnace, the furnace must be protected from the
condensate produced in the flue.
3 - The flue system must be sealed (all joints must be
sealed), as positive pressure can occur in the flue.
4 - A 152mm ( in.) clearance must be maintained to all
combustibles when single-walled flue pipe is used. A
25mm (1 in.) clearance to all combustibles must be
maintained when twin-walled flue pipe is used.
5 - If single-walled flue is used, fasten the flue adapter
to the flue outlet of the furnace and the flue connector
to the flue adapter using one or two corrosion-resisĆ
tant sheet metal screws. If twin-walled flue pipe is
used, fasten to the adapter according to manufacturĆ
er's instructions.
- Support flue as required by the regulations in force.
7 - See table 3 for flue diameter, equivalent lengths and
termination allowed.
8 - The tee termination shown in figures 1 and 17 is the
only acceptable termination.
TABLE 3
HORIZONTAL FLUE PIPE SIZING
MODEL SIZE UNIT ORIENTATION MINIMUM FLUE PIPE
DIAMETER mm (in.)
MINIMUM FLUE
EQUIVALENT
LENGTH* m (ft.)
MAXIMUM FLUE
EQUIVALENT
LENGTH* m (ft.)
TERMINATION
TEE
45 HORIZONTAL
UPFLOW / DOWNFLOW 102 (4) 3 (10) 9.2 (30) 1
HORIZONTAL 102 (4) 3 (10) 9.2 (30)
60/75/100/120/140 UPFLOW / DOWNFLOW 102 (4) 3 (10) 13.7 (45) 1
*One 905 elbow equals 1 5 m (5 ft ) of straight pipe One 455 elbow equals 0 75 m (2 5 ft ) of straight pipe
Page 13
9 - The flue termination must be located in accordance
with any national regulations applicable. The termiĆ
nal must be designed such that it will not allow entry
of a 1 mm (. in.) ball when applied with a 5N force.
A terminal guard must be applied where required by
national regulations.
COUPLING
HORIZONTAL TERMINATION DETAIL
203mm
(8 in.) MIN.
WALL THIMBLE
(inside wall) WALL THIMBLE
(outside wall)
FLUE PIPE
INNER
SHIELD
OUTER
OVERLAPPING
SHIELD
INNER
SHIELD
INSIDE
WALL
PROTECTIVE SCREEN
(Both ends)
FIGURE 16
HORIZONTAL TERMINATION DETAIL
HIGH WINTER SNOW LEVELS
SEAL
WALL THIMBLE
FOR COMBUSTIBLE
MATERIALS CLEARANCES
GROUND
LEVEL
306mm (12 in.) MIN.
ABOVE NORMALLY
EXPECTED SNOW
ACCUMULATION
FIGURE 17
Gas Piping
GAS SUPPLY
1 - Service pipes - The gas supply authorities should be
consulted at the installation planning stage in order to
establish the availability of an adequate supply of gas.
2 - Meters - A gas meter is connected to the service pipe
by the gas supply authorities. An existing meter
should be checked by the gas supply authorities to
ensure that the meter is adequate to deal with the
rate of gas supply required.
3 - Pipework from the meter to the air furnace must be
of adequate size. Do not use pipes of a smaller size
than the inlet gas connection on the furnace. The
complete installation must be tested for soundness
as described in the codes in force.
4 - This unit is shipped standard for left or right side
installation of gas piping (or top entry in horizontal
applications). Connect the gas supply to the piping
assembly.
5 - When connecting gas supply, factors such as
length of run, number of fittings and furnace rating
must be considered to avoid excessive pressure
drop. Table 4 and 5 list recommended pipe sizes for
typical applications.
- The gas piping must not run in or through air ducts,
clothes chutes, chimneys or gas vents, dumb waiters
or elevator shafts.
7 - In some localities, it may be necessary to take preĆ
cautions against condensation in gas pipes. Where
condensation in pipes is considered likely to occur,
or if such precautions are required by national reguĆ
lations, the following steps should be taken to preĆ
vent condensation from entering the unit.
The piping should be sloped 1/4 inch per 15 feet upward
toward the meter from the furnace. The piping must be
supported at proper intervals (every 8 to 10 feet) using
suitable hangers or straps. A drip leg should be installed
in vertical pipe runs to the unit.
8 - A manual main shut-off valve and union (furnished
by installer) should be installed external to the unit.
Union must be of the ground joint type. See figure 18.
IMPORTANT
Compounds used on threaded joints of gas piping
must e resistant to the actions of liquified petroĆ
leum gases.
NOTE - Install an 1/8" RC plugged tap in the field piping upĆ
stream of the gas supply connection to the unit Tap must
be accessible for test gauge connection See figure 18
NOTE - In case emergency shutoff is required, shut off main
manual gas valve and disconnect electrical power to unit
These devices should be properly labeled by the installer
Page 14
TABLE 4 - GAS PIPE CAPACITY (FT3/HR)
Nominal
Iron Pipe Size
Internal
Diameter
Length of Pipe - feet
Iron Pipe Size
inches
Diameter
inches 10 20 30 40 50 60 70 80 90 100
1/4 .3 4 43 29 24 20 18 1 15 14 13 12
3/8 .493 95 5 52 45 40 3 33 31 29 27
1/2 . 22 175 120 97 82 73 1 57 53 50
3/4 .824 3 0 250 200 170 151 138 125 118 110 103
1 1.049 80 4 5 375 320 285 2 0 240 220 205 195
1-1/4 1.380 1,400 950 770 0 580 530 490 4 0 430 400
1-1/2 1. 10 2,100 4 0 1,180 990 900 810 750 90 50 20
2 2.0 7 3,950 2,750 2,200 1,900 1, 80 1,520 1,400 1,300 1,220 1,150
2-1/2 2.4 9 ,300 4,350 3,520 3,000 2, 50 2,400 2,250 2,050 1,950 1,850
3 3.0 8 11,000 7,700 ,250 5,300 4,750 4,300 3,900 3,700 3,450 3,250
4 4.02 23,000 15,800 12,800 10,900 9,700 8,800 8,100 7,500 7,200 ,700
NOTE-Capacity given in cubic feet of gas per hour and based on 0 60 specific gravity gas
TABLE 5 - GAS PIPE CAPACITY (M3/HR)
Nominal
Iron Pipe Size
Internal
Diameter
Length of Pipe - metres
Iron Pipe Size
inches
Diameter
inches 3 6 9 12 15 18 21 24 27 30
1/2 . 22 4.29 3.40 2.74 2.32 2.0 1.87 1.72 1. 1 1.50 1.41
3/4 .824 10.20 7.08 5. 4.81 4.27 3.91 3.54 3.34 3.11 2.91
1 1.049 19.27 13.17 10. 2 9.0 8.07 7.3 .80 .23 5.80 5.52
1-1/4 1.380 39. 7 2 .92 21.82 18.70 1 .43 15.02 13.88 13.03 12.18 11.33
1-1/2 1. 10 59.51 41.37 33.43 28.05 25.50 22.95 21.25 19.55 18.42 17.5
2 2.0 7 111.93 79.93 2.34 53.84 47. 0 43.07 39. 7 3 .84 34.57 32.58
2-1/2 2.4 9 178.53 123.27 99.75 85.01 75.09 8.01 3.7 58.09 55.2 52. 2
3 3.0 8 311.72 218.20 117.11 150.19 134. 0 121.85 110.52 104.85 97.7 92.10
4 4.02 51.78 447.74 308.89 274.88 249.37 249.37 229.54 212.53 204.03 189.8
NOTE-Capacity given in cubic metres of gas per hour and based on 0 60 specific gravity gas
GROUND
JOINT
UNION
AUTOMATIC
GAS VALVE
FIELD
PROVIDED
AND INSTALLED
GROUND
JOINT
UNION
LEFT SIDE PIPING (STANDARD)
RIGHT SIDE PIPING
(ALTERNATE)
AUTOMATIC
GAS VALVE
DRIP LEG
(optional)
MANUAL
MAIN SHUT-OFF VALVE
(With 1/8" RC
Plugged Tap Shown)
MANUAL
MAIN SHUT-OFF
VALVE
(With 1/8" RC
Plugged Tap
Shown)
DRIP LEG
(optional)
FIGURE 18
SOUNDNESS CHECK
After gas piping is completed, carefully check all piping
connections (factory- and field-installed) for gas leaks.
Use a leak detecting solution or other preferred means.
NOTE - In case emergency shutdown is required, shut
down main manual gas valve and disconnect electrical
power to unit These devices should be properly labeled
by the installer
CAUTION
Some soaps used for leak detection are corrosive
to certain metals. Carefully rinse piping thoroughly
after leak test has een completed. Do not use
matches, candles, flame or other sources of igniĆ
tion to check for gas leaks.
The furnace must be isolated from the gas supply system
by closing its individual manual shut-off valve during any
pressure testing of the gas supply system at pressures
equal to or less than 20 in w c (50 mBAR)
Page 15
IMPORTANT
At pressures greater than 20 in. w.c. (50 mBAR), gas
valve must e disconnected and isolated. See figĆ
ure 19. Gas valves can e damaged if su jected to
more than 20 in. w.c. (50 mBAR).
MANUAL MAIN
SHUT-OFF VALVE
WILL NOT HOLD
NORMAL TEST
PRESSURE
CAP
ISOLATE
GAS VALVE
furĆ
nace
FIGURE 19
Electrical
CAUTION
Electrostatic discharge can affect electronic comĆ
ponents. Take precautions during furnace installaĆ
tion and service to protect the furnace's electronic
controls. Precautions will help to avoid control exĆ
posure to electrostatic discharge y putting the
furnace, the control and the technician at the same
electrostatic potential. Neutralize electrostatic
charge y touching hand and all tools on an unĆ
painted unit surface, such as the gas valve or lowĆ
er deck, efore performing any service procedure.
These units operate on 240 volt, single phase, 50 hertz
electrical power. Refer to figure 20 for field wiring and figĆ
ure 22 for schematic wiring diagram and troubleshooting.
1 - Select circuit protection and wire size according to
requirements listed on unit rating plate.
2 - Knockouts are provided on both sides of the furnace
cabinet to facilitate wiring.
3 - Install room thermostat according to instructions proĆ
vided with thermostat.
4 - Install a separate disconnect switch (protected by eiĆ
ther fuse or circuit breaker) near the unit so power
can be turned off for servicing.
5 - Before connecting thermostat or power wiring, check
to make sure wires will be long enough to facilitate
servicing at a later date. Remove blower access panĆ
el and swing panel to check wire length for access.
- Complete wiring connections to equipment using wirĆ
ing diagrams provided with unit and in field wiring diaĆ
grams shown in figures 20. Use 18 gauge wire or largĆ
er for thermostat connections.
7 - Electrically earth unit according to national regulaĆ
tions.
8 - Three 240 volt accessory terminals are provided on
the control board. Two are energized with the indoor
blower and one is energized with the combustion air
blower. Any accessory rated up to one amp can be
connected to the accessory terminals with the neutral
leg of the circuit being connected to the 240 volt neuĆ
tral wires.
9 - This unit is equipped with an integrated control board
that controls blower operation, fan off timings and igniĆ
tion. The board includes a terminal strip for thermostat
connections and two diagnostic LEDs. See figure 21
for control board configuration. Diagnostic codes are
given in a chart at the back of this manual.
The red diagnostic button can be used to view the
last failure code.
10- Refer to blower speed chart on wiring diagrams for
factoryĆset cooling, heating and continuous fan
speeds.
Systems using a cooling thermostat subbase may
operate the blower continuously (factory set at low
speed) through the thermostat FAN ON" switch.
Systems which do not include a cooling subbase reĆ
quire a toggle switch which must be wired between
terminals R" and G" on the thermostat connection
terminal strip.
The blower motor will operate at the designated
speed during cooling or heating demand; however,
when demand is satisfied, blower speed will revert to
selected continuous speed.
W
TYPICAL G24MCE FIELD WIRING DIAGRAM
HIGHLIMIT
PRESSURE
SWITCH
GAS
VALVE
BLACK
WHITE
TRANSFORMER
R
G
W
Y
RGY
CONTROL
BOARD
DOOR
INTERLOCK
L1 N
FUSED OR
CIRCUIT
BREAKER
ISOLATOR
(Furnished y
installer)
TO COMPRESSOR
CONTACTOR
HEAT/COOL
THERMOSTAT
C
CAPILLARY
TUBE LIMIT
RW
HEAT ONLY
THERMOSTAT
240V, 1PH, 50HZ
FIGURE 20
Page 16
EGC-3ACE INTEGRATED CONTROL BOARD
NEUTRAL
TERMINALS
ACCESSORY
TERMINALS
THERMOSTAT
TERMINAL STRIP
BLOWER TIME
ADJUSTMENT
JUMPER
HEATING SPEED
TAP TERMINAL
COOLING SPEED
TAP TERMINAL
CONTINUOUS FAN
TERMINAL
HEATING
ACCESSORY
TERMINAL
DIAGNOSTIC
LEDS
RED DIAGNOSTIC BUTTON
(Depress utton and hold for
display of last failure code.)
DIAGNOSTIC CODE
ERASE JUMPER
(Remove power to control
and short pins for 10 secĆ
onds to erase previous
code.)
GND
L1
L2
FIGURE 21
Page 17
G24MCE SCHEMATIC WIRING DIAGRAM
03/99
(240V, 1PH, 50HZ)
FIGURE 22
Page 18
Unit Start-Up
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
Do not use this furnace if any part has een underĆ
water. Immediately call a qualified service techniĆ
cian to inspect the furnace and to replace any part
of the control system and any gas control which
has een under water.
WARNING
If overheating occurs or if gas supply fails to shut
off, shut off the manual gas valve to the appliance
efore shutting off electrical supply.
CAUTION
Before attempting to perform any service or mainteĆ
nance, turn the electrical power to unit OFF at isolaĆ
tor switch.
BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the floor because some
gas is heavier than air and will settle on the floor.
Use only your hand to turn the main manual gas cock. Never
use tools. If the knob will not turn by hand, do not try to repair
it, call a qualified service technician. Force or attempted reĆ
pair may result in a fire or explosion.
PLACING FURNACE INTO OPERATION
G24MCE units are equipped with an automatic direct
spark ignition system. Do not attempt to manually light
burners on these Furnaces. Each time the thermostat
calls for heat, the burners will automatically light.
WARNING
If you do not follow these instructions exactly, a fire
or explosion may result causing property damage,
personal injury or death.
GAS VALVE OPERATION (Figure 23)
1 - STOP! Read the safety information at the beginning
of this section.
2 - Set the thermostat to the lowest setting.
3 - Turn off all electrical power to the unit.
4 - This furnace is equipped with an ignition device
which automatically lights the burners. Do not try to
light the burners by hand.
5 - Wait five (5) minutes to clear out any gas. If you then
smell gas, STOP! Immediately call your gas supplier
from a neighbor's phone. Follow the gas supplier's
instructions. If you do not smell gas go to next step.
S.I.T. GAS VALVE
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
MANIFOLD
PRESSURE
OUTLET
FIGURE 23
- Turn on all electrical power to the unit.
7- Set the thermostat to desired setting.
8- If the appliance will not operate, follow the instrucĆ
tions Turning Off Gas To Unit" and call your service
technician or gas supplier.
NOTE-When unit is initially started, steps 1 through 7
may need to be repeated to purge air from gas line
TURNING OFF GAS TO UNIT
1 - Set the thermostat to lowest setting.
2 - Turn off all electrical power to the unit if service is to
be performed.
Heating Sequence of Operation
1 - When thermostat calls for heat, combustion air blowĆ
er starts after a 5 second delay.
2 - Combustion air pressure switch proves blower opĆ
eration, then allows power to ignition control. Switch
is factory set and requires no adjustment.
3 - After 15-second prepurge, spark ignitor energizes
and gas valve solenoid valves open.
4 - Spark ignites gas, ignition sensor proves the flame
and combustion process continues.
5 - If flame is not detected after first ignition trial, igniĆ
tion control will repeat steps 3 and 4 four more
times before locking out. To reĆestablish ignition
attempts after lockout, proceed as follows:
a - Turn OFF the power to the furnace.
b - Move the thermostat control from the HEAT" to
the OFF" position.
c - Turn ON the power to the furnace.
d - Move the thermostat control from the OFF" to
HEAT" position.
Page 19
Unit Adjustments
HIGH LIMIT AND CAPILLARY TUBE LIMIT
The high limit and manuallyĆreset capillary tube limit are
both located on the heating compartment vestibule panel.
Both limits are factory set and do not require field adjustĆ
ment.
When there is inadequate supply air (a high supply air
temperature), the high limit shuts off the gas supply to
the burners, turns the combustion air blower OFF, and
keeps the air circulating blower ON until the limit resets
itself. While the limit is open, the control board displays
DIAG.1 - FLASHING; DIAG.2 Ć ON. If the limit trips 5
times in succession, a  0 minute Watchguard" occurs.
After 0 minutes, the control board automatically resets
itself. (The control board can also be reset by switching
the thermostat from HEAT to OFF and then back to
HEAT again.)
When there is inadequate supply air (a high supply air
temperature), the manuallyĆreset capillary tube limit
shuts off the gas supply to the burners and turns both the
combustion air blower and the air circulating blower OFF.
(The air circulating blower turns off only after its preset
delayĆoff time expires). While the limit is open, the control
board then displays DIAG.1 - ON; DIAG.2 Ć FLASHING.
To reset the limit, allow the furnace to cool, and then push
the switch on the limit's face inward.
If either limit trips, check for clogged filters or blocked supĆ
ply/return air grilles.
COMBUSTION AIR PRESSURE SWITCH
The combustion air pressure switch is located on the
heating compartment vestibule panel. This switch checks
for proper combustion air fan operation before allowing
ignition trial. The switch is factoryĆset and requires no field
adjustment.
FAN CONTROL
The fan control is part of the control board located on the
heating compartment vestibule panel. The preset fan on
delay time of 45 seconds is not adjustable. The fan off
delay time is factory adjusted at 120 seconds and can be
adjusted by moving the jumper on the integrated control
board. See figure 24 for settings.
120 180
90 60
To adjust fan-off timings:
Remove jumper and select one of the
other pin combinations to achieve the
desired time.
TIMING
JUMPER
TIMING PINS
(seconds)
FAN-OFF TIME ADJUSTMENT
FIGURE 24
GAS FLOW
To check for proper gas flow to combustion chamber, deterĆ
mine heat (kW) input from the unit rating plate. Divide this
input rating (MJ/hr) by the calorific value per unit volume
(MJ/m3) of the gas being used. Result is the volume of gas
required per hour. Determine the flow of gas through gas
meter for two minutes and multiply by 30 to get the hourly
flow of gas.
GAS PRESSURE
1 - Check the gas line pressure with unit firing at maximum
rate. See technical data table on page 22 for minimum
and maximum allowable pressure.
2 - After line pressure has been checked and adĆ
justed, check manifold pressure. Manifold pressurĆ
es are given in technical data table on page 22. See
figure 23 for gas pressure adjustment screw location.
TEMPERATURE RISE
Check the temperature rise and, if necessary, adjust fan
speed to maintain the temperature rise within range
shown on the unit rating plate.
If outdoor air is added to the recirculating room air, the
mixed air temperature at the heat exchanger should not
be lower than 15.5°C for extended periods of time.
THERMOSTAT HEAT ANTICIPATION
Set thermostat heat anticipation to:
0.80 amps S.I.T. gas valve
ELECTRICAL
1 - Check all wiring for loose connections.
2 - Check for correct voltage at the furnace (furnace opĆ
erating).
3 - Check amp-draw on fan motor.
Motor Nameplate__________Actual__________
FAN SPEEDS
Note - CFM readings are taken external to unit with a dry
evaporator coil and without accessories
1 - Turn off electrical power to furnace.
2 - Remove unit access panel.
3 - Disconnect existing speed tap at control board
speed terminal.
NOTE - TERMINATION OF ANY UNUSED MOTOR
LEADS MUST BE INSULATED.
4 - Refer to fan speed selection chart on unit wiring diaĆ
gram for desired heating or cooling speed.
5 - Connect selected speed tap at control board speed
terminal.
- Resecure blower access panel.
7 - Turn on electrical power to furnace.
FLUE AND CHIMNEY
1 - Check flue pipe, chimney and all connections for
tightness and to make sure there is no blockage.
2 - Check unit for proper draught.
3 - Is pressure switch closed? Obstructed flue will cause
unit to shut off at pressure switch. Check flue and
outlet for blockages.
Page 20
BURNER FLAME ADJUSTMENT
The G24MCE burner flame is not adjustable; however,
the flame should be inspected at the beginning of each
heating season. If necessary, clean the burners. The
burner flame should be blue when burning natural gas,
and blue/yellow when burning propane gas. See figure
25.
BURNER FLAME
BURNER
FLAME
HEAT
EXCHANGER
TUBE
VEST
PANEL
FLAME APPEARS BLUE IF
BURNING NAT. GAS; BLUE/
YELLOW FOR PROPANE.
FIGURE 25
FAILURE TO OPERATE
If unit fails to operate check the following:
1 - Is the thermostat calling for heat?
2 - Is the main isolator switch closed?
3 - Is there a blown fuse or tripped circuit breaker?
4 - Is the filter dirty or clogged? Dirty or clogged filters
will cause the limit control to shut the unit off.
5 - Is gas turned on at the meter?
- Is manual main gas cock open?
7 - Is unit ignition system in lock out? If unit locks out
again, call the service technician to inspect unit for
blockages.
Service
WARNING
Disconnect power efore servicing unit.
CAUTION
La el all wires prior to disconnection when servicĆ
ing controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.
At the beginning of each heating season, service items A
through E as described below:
A - ELECTRICAL
1 - Check all wiring for loose connections.
2 - Check for correct voltage at the furnace (furnace opĆ
erating).
3 - Check amp-draw on the fan motor.
Motor Nameplate__________Actual__________
B - FANS
Check and clean fan wheels for debris and clean if necĆ
essary. The fan motors are prelubricated for extended
bearing life. No further lubrication is needed.
C - FILTERS
All G24MCE filters are installed external to the unit. Filters
should be inspected monthly .Clean or replace the filters
when necessary to ensure proper furnace operation. See
table for filter sizes. Replacement filters for
G24MCE-45/ 0/75 units must have a minimum velocity
rating of 2 m/s (400 FPM). Replacement filters for
G24MCE-100/120/140 units require a minimum velocity
rating of 3 m/s ( 25 FPM).
TABLE 6
MODEL NO. FILTER SIZE -
millimeters (inches)
G24MCE-45/ 0/75 40 X508X25
(1 X 20 X 1)
G24MCE-100/120/140 508X508X25
(20 X 20 X 1)
WARNING
The fan door must e securely in place when the fan
and urners are operating. Gas fumes, which could
contain car on monoxide, can e drawn into living
space resulting in personal injury or death.
D - FLUE AND CHIMNEY
Check the flue pipe, chimney and all connections for tightĆ
ness and to make sure there is no blockage.

This manual suits for next models

9

Other Lennox Furnace manuals

Lennox G61MPV Series Dimension Guide

Lennox

Lennox G61MPV Series Dimension Guide

Lennox ML180UHT User manual

Lennox

Lennox ML180UHT User manual

Lennox ML195UH User manual

Lennox

Lennox ML195UH User manual

Lennox GHR26 series Guide

Lennox

Lennox GHR26 series Guide

Lennox ML193DFE Installation and operation manual

Lennox

Lennox ML193DFE Installation and operation manual

Lennox G23 Series Owner's manual

Lennox

Lennox G23 Series Owner's manual

Lennox G61MPVT-36B-070 User manual

Lennox

Lennox G61MPVT-36B-070 User manual

Lennox Merit Series User manual

Lennox

Lennox Merit Series User manual

Lennox LRP14HP Series User manual

Lennox

Lennox LRP14HP Series User manual

Lennox O23V-105 User manual

Lennox

Lennox O23V-105 User manual

Lennox G43UF SERIES Guide

Lennox

Lennox G43UF SERIES Guide

Lennox GCS16−024 Guide

Lennox

Lennox GCS16−024 Guide

Lennox EL180UHNE Series Guide

Lennox

Lennox EL180UHNE Series Guide

Lennox GHR32 Series Guide

Lennox

Lennox GHR32 Series Guide

Lennox E12Q2-05 Operating and installation instructions

Lennox

Lennox E12Q2-05 Operating and installation instructions

Lennox G21Q Series Guide

Lennox

Lennox G21Q Series Guide

Lennox EL280UH User manual

Lennox

Lennox EL280UH User manual

Lennox Merit ML193UH User manual

Lennox

Lennox Merit ML193UH User manual

Lennox ML196UHE Guide

Lennox

Lennox ML196UHE Guide

Lennox G24-200 Guide

Lennox

Lennox G24-200 Guide

Lennox ML180DF045P24A Installation and operation manual

Lennox

Lennox ML180DF045P24A Installation and operation manual

Lennox G60UHX Series Guide

Lennox

Lennox G60UHX Series Guide

Lennox SLP99DFV Series Guide

Lennox

Lennox SLP99DFV Series Guide

Lennox G29M Series User manual

Lennox

Lennox G29M Series User manual

Popular Furnace manuals by other brands

Carrier INDUCED-COMBUSTION GAS FURNACE Quick manual

Carrier

Carrier INDUCED-COMBUSTION GAS FURNACE Quick manual

whitepeaks calidia sintec 770 manual

whitepeaks

whitepeaks calidia sintec 770 manual

Fire Chief 500 owner's manual

Fire Chief

Fire Chief 500 owner's manual

Cleanburn CB-1400 Operator's manual

Cleanburn

Cleanburn CB-1400 Operator's manual

GAMA Gas-Fired Furnace User's information manual

GAMA

GAMA Gas-Fired Furnace User's information manual

Comfortaire Century HEAT CONTROLLER ODF Series Installation and operation manual

Comfortaire

Comfortaire Century HEAT CONTROLLER ODF Series Installation and operation manual

Empire Heating Systems GWT-25-2 Installation instructions and owner's manual

Empire Heating Systems

Empire Heating Systems GWT-25-2 Installation instructions and owner's manual

Sterling outdoor rooftop gas-fired duct furnace Installation and service manual

Sterling

Sterling outdoor rooftop gas-fired duct furnace Installation and service manual

Barnstead F46110CM Operation manual

Barnstead

Barnstead F46110CM Operation manual

Bryant EVOLUTION 987MA Product data

Bryant

Bryant EVOLUTION 987MA Product data

VERDER CARBOLITE GERO E Series Installation, operation and maintenance instructions

VERDER

VERDER CARBOLITE GERO E Series Installation, operation and maintenance instructions

Jaspi ECOWOOD 25 Installation and operation manual

Jaspi

Jaspi ECOWOOD 25 Installation and operation manual

Tarlan Technical Little Cracker installation guide

Tarlan Technical

Tarlan Technical Little Cracker installation guide

SummerAire ELECTRIC WARM AIR FURNACE user manual

SummerAire

SummerAire ELECTRIC WARM AIR FURNACE user manual

Heat Controller GLUA parts list

Heat Controller

Heat Controller GLUA parts list

Clayton CL1660E Owner's installation and operation manual

Clayton

Clayton CL1660E Owner's installation and operation manual

Pro-Fab Industries 100 Installation and operation instructions

Pro-Fab Industries

Pro-Fab Industries 100 Installation and operation instructions

White Rodgers FG9 manual

White Rodgers

White Rodgers FG9 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.