BLOWER PERFORMANCE
G41UF−60C−110 PERFORMANCE − Single Side Return Air − Air volumes in bold require field fabricated transition to ac
commodate 20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity.
External Static Air Volume / Watts at Different Blower Speeds
Pressure High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 02550 1205 1300 2345 1105 1080 2055 970 895 1740 820 715
0.10 25 2500 1180 1270 2280 1075 1050 2025 950 855 1730 815 720
0.20 50 2410 1140 1225 2220 1050 1000 2000 945 840 1715 810 695
0.30 75 2350 1110 1190 2175 1025 965 1945 920 805 1690 795 670
0.40 100 2280 1075 1170 2115 995 940 1910 900 790 1675 790 680
0.50 125 2195 1035 1115 2035 960 910 1840 870 760 1630 770 650
0.60 150 2075 980 1065 1955 925 875 1785 845 735 1585 750 630
0.70 175 1980 935 1030 1860 880 845 1705 805 700 1540 725 605
0.80 200 1895 895 1005 1770 835 810 1615 765 675 1475 695 580
0.90 225 1770 835 975 1640 775 770 1535 725 645 1415 670 565
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
G41UF−60C−110 PERFORMANCE − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from
Both Sides or Return Air from Bottom and One Side.
External Static Air Volume / Watts at Different Blower Speeds
Pressure High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2580 1215 1340 2330 1100 1100 2045 965 950 1760 830 745
0.10 25 2515 1190 1295 2295 1085 1075 2040 960 880 1740 820 745
0.20 50 2450 1155 1255 2255 1065 1040 2005 945 855 1735 820 730
0.30 75 2375 1120 1225 2200 1040 1015 1965 925 835 1715 810 710
0.40 100 2310 1090 1190 2145 1010 975 1925 910 815 1690 800 695
0.50 125 2200 1040 1135 2085 985 955 1870 880 780 1660 785 670
0.60 150 2130 1005 1105 2025 955 930 1825 860 770 1600 755 650
0.70 175 2045 965 1065 1930 910 890 1750 825 730 1575 745 625
0.80 200 1930 910 1025 1825 860 850 1650 780 695 1500 710 600
0.90 225 1820 860 980 1730 815 815 1555 735 660 1430 675 580
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
G41UF−60D−135 PERFORMANCE − Single Side Return Air − Air volumes in bold require field fabricated transition to ac
commodate 20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity.
External Static Air Volume / Watts at Different Blower Speeds
Pressure High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 02550 1205 1340 2330 1100 1145 2035 960 955 1725 815 775
0.10 25 2490 1175 1305 2275 1075 1100 2025 955 900 1720 810 755
0.20 50 2430 1145 1285 2230 1050 1065 1990 940 890 1715 810 740
0.30 75 2355 1110 1235 2180 1030 1035 1955 920 855 1700 800 715
0.40 100 2285 1080 1210 2140 1010 1010 1910 900 830 1680 790 700
0.50 125 2200 1040 1160 2070 975 980 1865 880 805 1645 775 675
0.60 150 2100 990 1110 1985 935 935 1815 855 780 1600 755 660
0.70 175 2010 950 1075 1915 905 910 1740 820 740 1545 730 630
0.80 200 1910 900 1050 1845 870 875 1670 790 720 1490 705 605
0.90 225 1815 855 1005 1735 820 835 1605 755 690 1420 670 580
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
G41UF−60D−135 PERFORMANCE − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from
Both Sides or Return Air from Bottom and One Side.
External Static Air Volume / Watts at Different Blower Speeds
Pressure High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2585 1220 1370 2355 1110 1160 2075 980 985 1730 820 765
0.10 25 2530 1195 1335 2330 1100 1120 2075 980 945 1730 820 750
0.20 50 2475 1170 1300 2295 1085 1090 2050 970 920 1730 815 745
0.30 75 2410 1135 1260 2230 1050 1060 2010 950 890 1715 810 725
0.40 100 2355 1110 1230 2185 1030 1040 1975 930 865 1680 795 695
0.50 125 2275 1075 1190 2120 1000 995 1915 905 830 1650 780 685
0.60 150 2190 1035 1155 2045 965 960 1850 875 805 1615 765 660
0.70 175 2100 990 1125 1955 925 930 1785 840 780 1550 730 635
0.80 200 1995 945 1080 1855 875 890 1715 810 745 1500 710 615
0.90 225 1860 880 1020 1750 825 835 1635 770 720 1425 670 580
NOTES − All air data is measured external to unit without filter (not furnished − field provided).