
Page 19
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a
venting system commonly run with separate gas ap
pliances, the venting system is likely to be too large to prop
erly vent the remaining attached appliances.
Conduct the following test while each appliance is operat
ing and the other appliances (which are not operating) re
main connected to the common venting system. If the vent
ing system has been installed improperly, you must
correct the system as indicated in the general venting re
quirements section.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon mon
oxide poisoning or death.
The following steps shall be followed for each ap
pliance connected to the venting system being
placed into operation, while all other appliances
connected to the venting system are not in
operation:
1 - Seal any unused openings in the common venting sys
tem.
2 - Inspect the venting system for proper size and horizon
tal pitch. Determine that there is no blockage, restric
tion, leakage, corrosion, or other deficiencies which
could cause an unsafe condition.
3 - Close all building doors and windows and all doors be
tween the space in which the appliances remaining
connected to the common venting system are located
and other spaces of the building. Turn on clothes dry
ers and any appliances not connected to the common
venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they will oper
ate at maximum speed. Do not operate a summer ex
haust fan. Close fireplace dampers.
4 - Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that
the appliance operates continuously.
5 - After the burner have operated for 5 minutes, test for
leaks of flue gases at the draft hood relief opening. Use
the flame of a match or candle.
6 - After determining that each appliance connected to the
common venting system is venting properly, (step 3)
return all doors, widows, exhaust fans, fireplace damp
ers, and any other gas-burning appliances to their pre
vious mode of operation.
7 - If a venting problem is found during any of the preced
ing tests, the common venting system must be modi
fied to correct the problem.
Using local codes, resize the common venting system
to the minimum vent pipe size.
Gas Piping
See local codes for gas piping requirements and gas
pipe sizing tables.
Gas supply piping should not allow more than 125 Pa
(0.5”W.C.) drop in pressure between gas meter and unit.
Supply gas pipe must not be smaller than unit gas connec
tion.
CAUTION
If a flexible gas connector is required or allowed by
the authority that has jurisdiction, black iron pipe
shall be installed at the gas valve and extend outside
the furnace cabinet. The flexible connector can then
be added between the black iron pipe and the gas
supply line.
Gas Supply
1 - This unit is shipped standard for left or right side instal
lation of gas piping (or top entry in horizontal applica
tions). Connect the gas supply to the piping assembly.
2 - When connecting the gas supply piping, consider fac
tors such as length of run, number of fittings, and fur
nace rating to avoid excessive pressure drop.
3 - The gas piping must not run in or through air ducts,
clothes chutes, gas vents or chimneys, dumb waiters,
or elevator shafts.
4 - The piping should be sloped 6.4 mm (1/4 in) per 4.57 m
(15 ft.) upward toward the meter from the furnace. The
piping must be supported at proper intervals every
2.44 to 3.01 m (8 to 10 ft) with suitable hangers or
straps. Install a drip leg in vertical pipe runs to the unit.
5 - A 3 mm (1/8”) N.P.T. plugged tap or pressure post is
located on the gas valve to facilitate test gauge con
nection. See figure 29.
6 - In some localities, codes may require the installation of
a manual main shut‐off valve and union (furnished by
the installer) external to the unit. The union must be of
the ground joint type.
IMPORTANT
Compounds used on threaded joints of gas piping
must be resistant to the actions of liquified petro
leum gases.
NOTE - If emergency shutoff is necessary, shut off the
main manual gas valve and disconnect main power to the
furnace. The installer should properly label these devices.