Lyon 2000 Series User manual

2000 SERIES INDUSTRIAL CLIP SHELVING ASSEMBLY
INSTRUCTIONS
#7002376 / 12-2020
www.lyonworkspace.com
OPEN UNIT ASSEMBLY
1.
The first and last uprights in a row of shelving are End Uprights. The remaining uprights in a row are
Intermediate Uprights (see assembly graphic above). To build the End Upright, lay the front and rear
post parallel to each other on the floor or saw horses. Position Angle Posts with the 1” flange pointing
up. The front post may be Beaded or Angle. The back post is always Angle.
Install Shelf Clips on both posts at the desired shelf locations by inserting the fingers of the clip into
the rectangular holes in the post and sliding down until the clip is fully seated. Install the clips for the
bottom shelf in the bottom two rectangular holes; install the clips for the top shelf in the top two
rectangular holes.
Clip to Post Connection
Using a shelf to determine proper spacing of posts, attach a pair of Side Sway Braces to the posts
forming an “X” with ¼-20 x 5/8” screws and nuts. See page 3 for information regarding sway brace locations. Note: Bolts cannot be placed where
shelves are located.
2.
Intermediate Uprights are built like End Uprights, except Double Angle Posts replace Single Angle Posts (see graphic above). Double Angle Posts
are made by bolting two Single Angle Posts together with two ¼-20 x 5/8” screws and nuts, one near the top of post and one near the bottom.
Install Shelf Clips on both sides of the post assembly.
Attach a pair of Sway Braces to the front and rear posts as in Step 1.
3.
Stand two End Uprights or an End and Intermediate Upright to build the first unit. Hold the uprights in position and install the top and bottom shelves
on to the shelf clips. Make sure shelves are completely seated on the clips by tapping them down with a soft hammer. Repeat this process with the
rest of the shelves in the first unit.
4.
While holding the unit vertical, install a pair of Back Sway Braces in an “X” pattern using ¼-20 x 5/8” screws and nuts. Attach the Back Sway Braces
on the inside of the rear Angle Posts as shown.
5.
If building a row of shelving, continue to add units by standing additional upright assemblies and installing shelves and back braces. The last upright
in the row of shelving must be an End Upright.
6.
Back-to-back (double) rows are built like single rows, except common Back Sway Braces are used. The common braces are installed on the inside of
one of the units, with the bolts going through both rear posts of the back-to-back units. This will securely tie the back-to-back units together.
End Upright
(At row ends)
Back Sway
Brace
Intermediate
Upright
Side
Sway
Angle
Post
Shelf
Clip
Beaded Post
(Used at front
Series 2000 Shelf

2000 SERIES INDUSTRIAL CLIP SHELVING ASSEMBLY
INSTRUCTIONS
#7002376 / 12-2020
www.lyonworkspace.com
CLOSED UNIT ASSEMBLY
1.
End Uprights are the first and last uprights in a row of shelving. The remaining uprights in a row are
Intermediate Uprights (see assembly graphic above). End and Intermediate Uprights are available in
Welded Upright Assemblies –top view
welded assemblies or may be built.
To build, lay the front and rear post parallel to each other on the floor or saw
horses. Position Angle Posts with
the 1” flange pointing up. The front post may be Beaded or Angle. The back
post is always Angle.
Install Shelf Clips on both posts at the desired shelf locations by inserting the fingers of the clip into the
rectangular holes in the post and sliding down until the clip is fully seated. Install the clips for the bottom shelf in
the bottom two rectangular holes; install the clips for the top shelf in the top two rectangular holes.
The Upright Side Sheet is attached to the side of the Angle or Beaded post as shown using ¼- 20 x 5/8” Truss
Head screws and nuts. Upright Sheets are supplied with two screws and nuts for every foot of height. Note: Bolts
cannot be placed where shelves are located.
2.
Intermediate Uprights are built like End Uprights, except Double Angle Posts replace Single Angle Posts (see
graphic above). Double Angle Posts are made by bolting two Single Angle Posts together, along with the
common upright side sheet, with ¼-20 x 5/8”
screws and nuts. The Upright Side Sheet should be positioned to
the
side of the Double Angle Posts. Install shelf clips on both sides of the post assembly.
If a Beaded Post is used, attach the Upright Side Sheet to the side of the Beaded Post with ¼-20 x 5/8” Truss Head screws and nuts.
3.
Stand two End Uprights or an End and Intermediate Upright to build the first unit. Hold the uprights in position and install the top and bottom Shelves on to
the shelf clips. Make sure shelves are completely seated on the clips by tapping them down with a soft hammer. Repeat this process with the rest of the
shelves in the first unit.
4. While holding the unit vertical, install a Back Sheet using ¼-20 x 5/8” screws and nuts. Attach the Back Sheet to the inside of the rear angle posts as
shown. Slide one edge of the sheet between the shelf and post; then slide the other edge bowing the Back Sheet as needed. Line up the holes in the post
with holes in the back and bolt in place using ¼-20 x 5/8” Truss Head screws and nuts. Note: Bolts cannot be placed where shelves are located. Bolt
backs according to number of bolts and spacing shown below.
Height of Closed Back
Total Number of Bolts and Nuts
Maximum Bolt Spacing
To 3’ 11-1/2”
4
46-1/2”
4’1” to 5’11-1/2”
6
36”
6’1” to 7’11-1/2”
8
31-1/2”
8’1” to 9’-11-1/2”
10
30”
5.
If building a row of shelving, continue to add units by standing additional uprights and installing shelves and backs. The last upright in a row is an end
upright. All units in a row are to be securely bolted together.
6.
Back-to-back (double) rows are built like single rows, except common backs are used. The common Back Sheet is installed on the inside of one of the
units, with the bolts going through both rear posts of the back-to-back units. This will securely tie the back-to-back units together.
End Upright
(At row ends)
Back
Sheet
Intermediate
Upright
Side
Sheet
Angle
Post
Shelf
Clip
Beaded Post
(Used at front

2000 SERIES INDUSTRIAL CLIP SHELVING ASSEMBLY
INSTRUCTIONS
#7002376 / 12-2020
www.lyonworkspace.com
SWAY BRACING PATTERNS –NOTE: Bracing patterns represent the minimum bracing required for units 8’-1” high and under in Seismic Zone 0.
Back and Side Bracing –Top View…Side Bracing –Side View
Back-to-back units share common
back sheet or sway brace.
Side-to-side units share common
upright sheet or sway braces.
Indicates bay
reference in “Side
Bracing - Side
View” (right).
Indicates location of sway brace pair.
Indicates bay
reference in “Back
Bracing - Front
View” (below).
Back Bracing –Front View
For more than 4 bays wide, repeat the 4 wide
pattern (i.e. Bay 5 the same as Bay 1, Bay 6 the
same as Bay 2, etc.).
Unit Detail for Back and Side Bracing –Top View
Back Panel or Sway Brace

www.lyonworkspace.com
INDUSTRIAL CLIP SHELVING ASSEMBLY INSTRUCTIONS
#7002376 / 12-2020
SHELVING ACCESSORIES
Half Shelf Clips
Foot Plate –Angle and Beaded Post
Attach Angle Post with ¼-20 x 5/8” truss head
screw and nut. Attach Beaded Post with ¼-20 x
1” truss head screw and nut. Floor anchors are
not supplied with foot plates. *
NOTE: When factory welded uprights are used,
field drill bottom hole of angle post for footplate.
End Base
Attach to posts with Tinnerman Nuts #702517
and #10 x 1/2” truss head sheet metal screws.
Angle Divider
Attach to Series 2000 shelf with #12-24 x 3/8”
truss head screws and nuts.
Front Base - Angle Post
Attach to face of box shelf with (3) #701487
Panel Clips. Half Shelf Clips are furnished
with 1-1/2” bases.
Label Holder
Attach to Series 2000 Shelf With (3) #701487
Panel Clips.
Front Base –Beaded Post
Attach to face of box shelf with (3) #701487
Panel Clips. Half Shelf Clips are furnished
with 1-1/2" bases.
Shelf Divider
Attach to Series 2000 shelf with #701487 Plastic
Panel Clips. When installed, front edge of divider
is 5/8” back from front edge of shelf.
Shelf Box Guide
Attach to Angle Post with ¼-20 x 1” truss head
screws and nuts.
* Lyon recommends securely anchoring all shelving.
Bin Front
Attach to face of box shelf with (3) #701487
Panel Clips.
Panel
Clip

www.lyonworkspace.com
INDUSTRIAL CLIP SHELVING ASSEMBLY INSTRUCTIONS
#7002376 / 12-2020
GUIDELINES FOR INSTALLATION AND GENERAL USE
1. Make sure all fasteners are securely tightened before shelving is to be used.
2. The first shelf should be located close to the floor, typically positioned at 4”, and secured to the posts via shelf clips or nuts & bolts for stability. If the first shelf
is required to be positioned greater than 4”, contact your Lyon Representative or the Product Engineering Department for assistance.
3. Shelving is to be hand loaded only. Any use of machinery to load the shelving may cause damage and/or failure.
4. When loading product on to the shelves, always load from the bottom of the shelving unit to the top. Also, when unloading always remove product from the
top down. This will ensure that the shelving unit does not become top heavy and risk the potential for overturning.
5. Shelving should never be climbed or stepped on.
OWNER MAINTENANCE
The owner shall maintain the structural integrity of the installed shelving by assuring proper operational, housekeeping, and maintenance procedures including,
but not limited to, the following:
•Prohibit any overloading of the shelving, be it a concentrated/point load, moving load, any uniformly distributed load, or the overall load on the system.
•Regularly inspect for damage. If damage is found, immediately isolate the affected area. A design professional should evaluate the damage so that the
system can be restored to its original design capacity.
•Sheared or loose anchors and/or bolts shall be replaced or tightened and dislodged shims shall be realigned.
•Require that all product stored on the shelving is properly stacked and stable.
•Ensure that the shelving is not reconfigured or otherwise modified in a manner not within the original design or intended use without the advice of a
qualified design professional.
FOOT PLATES AND ANCHORING
Lyon recommends the use of foot plates on all shelving units to spread loads, prevent damage to floor surfaces, aid in shimming uprights to a plumb condition
and to allow anchoring when necessary. Anchoring of posts is required when the top loaded shelf is over 8’-1” high AND the height to depth ratio of the shelving
section exceeds four (4). Seismic or wind loading may require anchoring shelving less than 8’-1” in height. However, for maximum safety it is recommended that all
shelving be anchored. Contact the Product Engineering Department at Lyon for assistance when you know or suspect seismic or wind loading must be considered.
•Height, as used in this ratio is defined as the distance from the floor to the top of the highest load on the top shelf, or the top shelf height if no load is
placed on that shelf.
•Depth is the overall depth of the shelving section, or the combined depth of back –to –back sections, provided the sections are securely tied together at
a minimum of two (2) places (top and bottom) at each back –to –back upright.
•Where the height to depth ratio is exceeded, upright assemblies should be top tied across the aisle(s) as well as anchored to the floor.
•If the shelving is attached to the building structure, the vertical and horizontal forces imposed by the shelving on the building must be calculated. The
shelving user, building owner, or their agents should be informed of these forces and their location.
•Shelving should be installed with a maximum tolerance from the vertical of 1/2” in 10’ or more of height, unless tighter tolerances are specified.
•When shims are used on an uneven floor, the posts must have footplates and anchors. Contact Lyon’s Product Engineering Department for information
on correct anchor type and foot plate for your specific application.

www.lyonworkspace.com
INDUSTRIAL CLIP SHELVING ASSEMBLY INSTRUCTIONS
#7002376 / 12-2020
LOADING
Shelving Post Load Table
Post capacities are dependent upon shelf spacing –the carrying capacity of a post increases as shelf spacing decreases.
Do not exceed allowable loads listed.
Allowable shelf loads
WARNING! –Do not exceed evenly distributed (uniform) loads shown above. Concentrated (point) loads or impact (dropped) loads could fail shelves even
though these loads may be considerably less than the allowable evenly distributed load shown.

www.lyonworkspace.com
INDUSTRIAL CLIP SHELVING ASSEMBLY INSTRUCTIONS
#7002376 / 12-2020
LOAD PLAQUE
It is the responsibility of the owner/end user of the shelving to display in one or more conspicuous locations a permanent plaque(s), such as at the ends of rows or
on top of access stairways. The plaque(s) shall show in clear legible print:
a) The maximum permissible uniformly distributed shelf load
b) The average shelf load, if applicable
c) The floor loading if shelving is a shelf-supported pick module
d) The maximum total load per bay
Example of a load capacity and compliance plaque for shelving
The above figure is not intended to limit the plaque details, but rather is presented as a possible example. It is the intent of the plaque to inform the storage
facilities manager of the safe shelving capacity and any plaque that transmits the required information is acceptable. The manager of the facility has the
responsibility to be cognizant of this load limit and to instruct all operating personnel to see that the permissible load is not exceeded.
Plaques should not be transferred to any reconfigured or relocated shelving without first verifying the applicability of the information on the plaque to the new
configuration or location by a qualified design professional.
Table of contents
Popular Rack & Stand manuals by other brands

BalanceBox
BalanceBox X-Line installation manual

Vivo
Vivo MOUNT-VP07DP instruction manual

Tailwind
Tailwind VeriFone MX915 Quick installation guide

U-Line
U-Line H-5816 quick start guide

Havis-Shields
Havis-Shields Trunk Side Mount C-TSM-CHGR-X installation instructions

Testrite Visual
Testrite Visual Rolling Teacher Shield Series Instruction