VITALink® MC/RC90
Fire-Resistive Cable Certified by UL and ULC IM-120-0
VITALink® MC/RC90 Cables Rev 0
Systems 120/120A/60 7/31/2020
RSCC Wire & Cable LLC © 2020 • 20 Bradley Park Road • East Granby, CT 06026 USA • 800-327-7625 Tel: 860-653-8300 • Fax: 860-653-8321 • r-scc.com 2/7
General
This document outlines the minimum installation requirements for installing a
cable to the systems described above.
Electrical Circuit Integrity Systems consist of components and materials that are
intended for installation as protection for specific electrical wiring systems, with
respect to the disruption of electrical circuit integrity upon exterior fire
exposure. The specifications for the protective system and its assembly are
important details in the development of the ratings.
These protective systems are evaluated by the fire exposure and water hose
stream test as described in UL 2196 / ULC S139. Ratings apply only to the entire
protective system assembly. Individual components and materials are
designated for use in a specific system(s) for which corresponding ratings have
been developed and are not intended to be interchanged between systems.
Ratings are not assigned to individual system components or materials.
Authorities having jurisdiction should be consulted in all cases as to the specific
requirements covering the installation and use of these Classified systems.
Cables and supports should be routed and supported separately from non-fire
resistive rated circuits. They should be positioned where any hazard of non-fire
resistive rated systems collapsing or failure will not disturb the system.
These requirements must be followed to maintain the hourly rating in the fire
area.
The VITALink® MC/RC90 cable system must be installed by qualified personnel
familiar with generally accepted construction techniques and safe electrical
practices.
Take all appropriate precautions when installing splices, including following
OSHA and other applicable regulations.
The installation must comply with all national and local electrical codes and all
the requirements of the UL Electrical Circuit Integrity System certification
requirements, and carefully follow the installation instructions.
Ensure the cable is in good condition prior to commencing splice installation.
Do not pull cables around corners that have sharp edges, such as corners in
cable trays, or other obstructions. See RSCC VITALink® MC/RC90 General
Installation and Handling Manual for more information.
Cable Support Distance
Cable shall be supported horizontally or vertically every four feet unless
otherwise stated in this document.
Cables shall also be supported on each side of a bend and not to exceed four
feet.
Support Methods
Drywall is not an acceptable means of support.
Strut
Box and Cables are mounted on 7/8” or larger 12 gauge slotted steel strut.
Painted or galvanized strut is acceptable.
Strut longer than 20” shall be a minimum of 1-1/2” 12 gauge steel.
Secure strut to concrete wall using a minimum 1/4 inch diameter steel
concrete screws by a minimum 2-1/4 inch in length.
Alternatively, Secure strut to concrete wall using a minimum 1/4 inch
diameter steel masonry anchor by a minimum 1-3/4 inch in length. The
deeper the penetration, the more secure the strut is mounted to the wall.
Please account for spalling.
Strut shall be secured to structure at a minimum on each end, and one in the
center for spans 5 feet or greater. Strut shall, at a minimum, be