Technical Data of your thermostat
Sensor:NTC Accuracy:±0.5℃
Temp. Range:5 -35℃Power Consumption:<1.5W
Timing error:<1%Power Supply:100~230VAC, 50
~60Hz
Current Load:5A for fan and 3A for valve
Shell Material:PC+ABS (Fireproof)
Dimension:86x86x13.3mm
Installation box:86*86mm or European 60mm
Ambient Temp.:0 ~ 45℃,5 ~ 95%RH(Non condensing)
Storage Temp:-5~ 55℃
About your thermostat
SS100F series Modern Touch Screen Room Thermostats
are designed to on/off control the fans and valves in air
conditioner applications via comparison of the room
temperature and setting temperature as reaching the aim of
comfort and saving energy. SS100F are microprocessor
based thermostat with LCD display.
Features of your thermostat
Modern design similar as a cell phone.
Acrylic lenses to avoid the finger scrath. Touch Button makes
simple operation.
Large screen display with backlight is easy to read—even in
the dark.
Four periods program schedules maximize comfort and
economy.
One-touch temp control overrides program schedule at any
time.
Precise comfort control keeps temperature within 0.5°C of
the level you set.
Easy installation.
86mm hidden box and european 60mm round box is
available.
Home screen quick reference
Model definition of your thermostat
A1: Two pipe; Control Fan Coil Unit and Two wired Motorized
valve.(when room temperature reaches the setpoint, both will
turn off)
A2: Two pipe; Control Fan Coil Unit and Two wired Motorized
valve.(when room temperature reaches the setpoint, valve will
turn off but fan will turn to low speed)
B: Two pipe; Control on/off Motorized Damper C: Two Pipe;
Control Fan Coil Unit and Three wired Motorized valve
M: Two pipe; Control 0-10V Motorized Valve
E: Four pipe; Control Fan Coil Unit and Two wired Heat and Cool
Motorized valve.
T: Clock
L: Backlight
P: Weekly Programmable
N: RS485/MODBUS RTU communication K: Keycard
E: External sensor
P and N could not be compatible at the same time.
For example: SS100FA1LN
Operation
1. Setting the temperature
In the programming mode, time and timing on/off could not be
adjusted. the set temperature can be adjusted temporarily only,
If the user want to change the timing and temperature, please
reprogram.
In the manual mode, press or to set temperature. will
display in the screen.
2. Setting Lock (optional function)
Press and hold and for 5 sec. to lock the screen. The icon
will display on the screen.
Press and hold and again for 5 sec. to unlock the screen.
3. Setting the fan speed.
Press
to select the fan speed LOW, MED, HIGH, AUTO.
4. Setting the system mode
Press to change the system mode HEATING, COOLING and
VENTILATION. In the mode of VENLITATION, the valve is off
but the fan runs.
5. Selecting manual, programming and Energy-saving
Mode
Press and hold for 5 sec to switch between manual mode
and programming mode.
means manual mode.
means weekly programming mode.
Manual
Set Temp.
Fan Speed
Auto Fan
Net work
Energy Saving
Cooling
Ventilation
Heating
OWD
Programming
Week
Period
/Clock
Timing
ON/OFF
Mode
Fan
Power
ON/OF
Up
Down
Lock

Means energy-saving mode.
Please note that this mode can only be set after this function is turned on
in the item 09 of advanced setting.
6. Clock setting
As the above steps, press and hold for 5 sec, the minute will
flash, THEN
Press or to set minutes of the time.
Press to set hours of the time.
Press to set week of the time.
Press into the adjustment of programmable.
7. Adjusting the weekly programmable
As the above steps, press and hold for 5 sec, the minute of
clock will flash, then press for 3 times to enter programmable
mode. Then press to change the different items.
Press or to set the relative values.
The order is Time adjusting → Temperature. adjusting→ Week
adjusting→ Time setting → Temperature. adjusting →week
adjusting(“12345”,”6”,”7”, is “5+1+1” programmable mode, every
mode has six times zones and six times temperature setting)
Time
display
WEEKDAY (MONDAY
– FRIDAY)
(1 2 3 4 5 shows on screen)
WEEKEND
(SATURDAY)
(6 shows on screen)
WEEKEND(SUNDAY)
(7 shows on screen)
TIME
TEMPERATURE
TIME
TEMPERATURE
TIME
TEMPERATURE
Period 1
06:00
20℃
06:00
20℃
06:00
20℃
Period 2
08:00
15℃
08:00
20℃
08:00
20℃
Period 3
11:30
15℃
11:30
20℃
11:30
20℃
Period 4
13:30
15℃
13:30
15℃
13:30
15℃
Period 5
18:00
15℃
18:00
20℃
18:00
20℃
Period 6
22:00
15℃
23:30
15℃
23:30
15℃
In the mode of programmable, set temp.,time could not be
adjusted.
8. Setting functions and options
During power off, press and hold the and buttons
together for 5 sec. to set the advanced settings. Then press
to change the different items.
Press ︽or ︾to set the relative values.
All the settings will confirm automatically when
power is on.
Wiring your thermostat
Installing your thermostat
This product is suitable for standard 86mm wall box or european
60mm round box.
1. Connect the wire of power and other equipment into
the terminals.
2. Fix the wall plate into the wall box by a screwdriver
3. Connect the LCD board into the wall plate.
WARNING: Please arrange the professional
technician to install this product according to
installation drawing and instruction.
RISK OF ELECTRICAL SHOCK. Disconnect power supply
before making electrical connection. Contact with components
carrying hazardous voltage can cause electrical shock and may
result in severe personal injury or death instruction.
No
Function
Setting & Options
Default
01
Temp.
Calibration
-9℃to 9℃
-2
02
Dead zone Temp.
1-5℃
1
03
Fan Control
00: When room temp. reaches the
setpoint, the fan will turn off.
01: When room temp. reaches the
setpoint, the fan will keep running.
00
04
Lock
00:All the buttons are locked except
POWER
01 :All the buttons are locked
01
05
Heat/Cool
00: Cool/Ventilation only
01: Heat/Cool/Ventilation
01
06
Min. Set Temp.
5-15℃
05
07
Max. Set Temp.
5-35℃
35
08
Display Mode
00:display both set temp. and
room temp.
01:display set temp only
00
09
Energy-saving
Mode
00:Non-evergy saving mode
01:Energy-saving mode,set temp,
keep economy temp.
00
10
Heating Economy
Temp.
10-30℃
20
11
Cooling Economy
Temp.
10-30℃
26
12
Factory Reset
when show“-”and keep press for 5
seconds until show“- - -”, it means
return to the restore factory reset
-