North Slope Chillers NSC0500 User manual

Freeze Owner’s Manual 1 | Page
www.northslopechillers.com | (866) 826-299 | 1 0 S 10 0 W, Suite 1 | Salt Lake City, UT 84119
Revised: 12/18/2020

Freeze Owner’s Manual 2 | Page
www.northslopechillers.com | (866) 826-299 | 1 0 S 10 0 W, Suite 1 | Salt Lake City, UT 84119
Revised: 12/18/2020
Table of Contents
Applications
Cautions/Warnings
Specification sheet 4
Chiller Component Overview 5
Installation 8
User Interface 9
Modifying Parameters 9
Display Unit 9
Thermostat Differential 9
Upper and Lower limit of Thermostat Set Point 10
Troubleshooting 11
STANDARD PRODUCT WARRANTY 1
1. LIMIT D WARRANTY 13
2. LIMITATION OF LIABILITY 13
3. R TURNS 13
4. IND MNIFICATION 14

Freeze Owner’s Manual | Page
www.northslopechillers.com | (866) 826-299 | 1 0 S 10 0 W, Suite 1 | Salt Lake City, UT 84119
Revised: 12/18/2020
Applications
This owner’s manual is to be used for the following North Slope Chillers:
TYPE
MODEL NUMBER
COOLING CAPACITY
(BTU/HR)
Freeze
NSC0500
6,000 (1/2 ton)
Freeze
NSC1000
12,000 (1 ton)
Freeze
NSC2000
24,000 (2 ton)
Freeze
NSC5000
60,000 (5 ton)
Freeze
NSC10000
120,000 (10 ton)
Deep Freeze
NSC0500
-
LT
6,000 (1/2 ton)
Deep Freeze
NSC1000
-
LT
12,000 (1 ton)
Deep Fre
eze
NSC2000
-
LT
24,000 (2 ton)
Deep Freeze
NSC5000
-
LT
60,000 (5 ton)
Deep Freeze
NSC10000
-
LT
120,000 (10 ton)
Cautions/Warnings
1. Power (ALWAYS check the Chiller Parameter tag and verify operational voltage before plugging in chiller)
a. Only connect North Slope Chillers to a properly grounded circuit
b. Never connect your North Slope Chiller to voltage that is outside the acceptable voltage range.
Connecting your chiller to any voltage outside of these ranges will damage the compressor.
i. 110V model will operate on voltages between 100 ~ 130V
ii. 230V model will operate on voltages between 200 ~ 250V
iii. 460V model will operate on voltages between 440 ~ 480V
c. Only use power sources that are 60Hz, running the chiller at 50Hz will void the warranty and will
damage the compressor
2. Never run the pump dry, only turn on chiller after the fluid reservoir has been filled. Running the chiller without
fluid will permanently damage the pump and void the warranty
3. This chiller is air cooled and must have good ventilation. For proper function there must be a minimum of 1
foot clearance on both sides and 2 foot clearance at the back of the chiller
4. Flush chiller prior to use. North Slope Chillers tests every chiller on site prior to shipping. During testing North
Slope Chillers uses a water/glycol mix to test their chillers. There will always be a small amount of water/glycol
remaining in the system. Since not all glycols are compatible with each other and vary by manufacture each
chiller should be flushed with water for 10 minutes prior to use.

Freeze Owner’s Manual 4 | Page
www.northslopechillers.com | (866) 826-299 | 1 0 S 10 0 W, Suite 1 | Salt Lake City, UT 84119
Revised: 12/18/2020
Specification sheet
Model
NSC0500
-
110/1
NSC0500
-
LT
-
110/1
NSC1000
-
230/1
NSC1000
-
LT
-
230/1
NSC2000
-
230/1
NSC2000
-
LT
-
230/1
Voltage
110 VAC, SINGL
PHAS , 60 Hz
110 VAC, SINGL
PHAS , 60 Hz 230VAC, SINGL PHAS , 60 Hz
Compressor Power
½ HP
½ HP
1 HP
2
HP
Cooling Capacity
(BTU/hr)
6,000 BTU/hr
90F ambient
65F Fluid Temp
6,000 BTU/hr
90F ambient
65F Fluid Temp
12,000 BTU/hr
90F Ambient
65F Fluid Temp
12,000 BTU/hr
90F Ambient
40F Fluid Temp
24,000 BTU/hr
90F Ambient
65F Fluid Temp
24,000 BTU/hr
90F Ambient
40F Fluid Temp
Fluid Temp Range
40F
–
80F
10F
–
60F
40F
–
80F
10F
–
60F
40F
–
80F
10F
–
60F
Refrigerant
R
-
134a
R404a
R
-
134a
R
-
404a
R
-
134a
R
-
404a
Metering Device
TXV
Pump Power
1/3 HP
3/4 HP
Pump Specs
4 GPM up to 50 PSI, Fixed Displacement
10GPM
@ 28 PSI (Centrifugal)
Glycol %
70/30
(Water/Glycol)
50/50
(Water/Glycol)
70/30 (Water/Glycol)
50/50 (Water/Glycol)
70/30 (Water/Glycol)
50/50 (Water/Glycol)
Acceptable Fluids
thylene Glycol or Propylene Glycol*
North Slope Chillers recommends using distilled water to maximize life and performance of chiller
Consult North Slope Chillers prior to using other fluids in the chiller
Tank Capacity
3.5 Gallons
15 Gallons
Inlet and Outlet
1/2” NPT
3/4” NPT
Dry Weight (lbs)
220 lbs
360 lbs
550 lbs
Dimension
s
28¼"L x 22½"W x 32½"H
34½"L x 28¼"W x 39"H
34¾"L x 43¼"W x 40"H
Model
NSC5000
-
460/3
NSC5000
-
LT
-
460/3
NSC10000
-
460/3
NSC1000
-
LT
-
460/3
Voltage
460 3 Phase
Compressor Power
5 HP
10 HP
Cooling Capacity
(BTU/hr)
60,000 BTU/hr
90F ambient
65F Fluid Temp
60,000 BTU/hr
90F ambient
40F Fluid Temp
120,000 BTU/hr
90F Ambient
65F Fluid Temp
120,000 BTU/hr
90F Ambient
40F Fluid Temp
Fluid Temp Range
40F
–
65F
10F
–
45F
40F
–
65F
10F
–
45F
Refrigerant
R404a
Metering Device
TXV
Pump Power
2 HP
Pump Specs
15
GPM @ 39 PSI
30 GPM @ 35 PSI
45 GPM @ 28 PSI
60 GPM Max
Glycol %
70/30
(Water/Glycol)
50/50
(Water/Glycol)
70/30 (Water/Glycol)
50/50 (Water/Glycol)
Acceptable Fluids
thylene Glycol or Propylene Glycol*
North Slope Chillers recommends using
distilled water to maximize life and
performance of chiller
Tank Capacity
55 Gallons
55 Gallons
Inlet and Outlet
1
-
1/4” NPT
Dry Weight (lbs)
1000 lbs
1150 lbs
Dimensions
34"L x 65"W x 62"H
North Slope Chillers tests every chiller on site prior to shipping. During testing North Slope Chillers uses a water/glycol
mix to test their chillers. Since not all glycols are compatible with each other and vary by manufacture each chiller
should be flushed with water for 10 minutes prior to use.
*The mix of Glycol to Water should be proportional to the desired freeze point. Always select a Glycol/Water mix that
will prevent freezing at 25F below your set point. This will prevent freezing from occurring in the heat exchanger and
prevent damaging the system. For example if your setpoint is 10F you should select a glycol percentage that would
prevent freezing at -15F.

Freeze Owner’s Manual 5 | Page
www.northslopechillers.com | (866) 826-299 | 1 0 S 10 0 W, Suite 1 | Salt Lake City, UT 84119
Revised: 12/18/2020
Chiller Component Overview
NSC0500, NSC 000 and NSC2000 Models
FRONT (NSC0500, NSC1000 and NSC2000 models)
BACK (NSC0500, NSC1000 and NSC2000 models)

Freeze Owner’s Manual 6 | Page
www.northslopechillers.com | (866) 826-299 | 1 0 S 10 0 W, Suite 1 | Salt Lake City, UT 84119
Revised: 12/18/2020
NSC5000 and NSC 0000 Models
FRONT (NSC5000 and NSC10000 models)
BACK (NSC5000 and NSC10000 models)

Freeze Owner’s Manual 7 | Page
www.northslopechillers.com | (866) 826-299 | 1 0 S 10 0 W, Suite 1 | Salt Lake City, UT 84119
Revised: 12/18/2020
Fluid Circuit (NSC5000 and NSC10000 models)
Electrical (NSC5000 and NSC10000 models)

Freeze Owner’s Manual 8 | Page
www.northslopechillers.com | (866) 826-299 | 1 0 S 10 0 W, Suite 1 | Salt Lake City, UT 84119
Revised: 12/18/2020
Installation
1. Position chiller for use
●Place unit on a flat level surface in a well-ventilated area
2. Connect inlet and outlet fluid hoses
●Confirm hoses are connected to proper inlet and outlet ports
. Fill the reservoir
4. Connect to power
●nsure you have the correct power supply before plugging in chiller
5. Turn on chiller and adjust temperature controller
●See page 8 for instructions on how to adjust temperature controller

Freeze Owner’s Manual 9 | Page
www.northslopechillers.com | (866) 826-299 | 1 0 S 10 0 W, Suite 1 | Salt Lake City, UT 84119
Revised: 12/18/2020
User Interface
Set the Setpoint
1
The display shows the current temperature
2
Press "up/down" to access setpoint.
3
Press "up/down" to a
djust setpoint. After 30 seconds, the display automatically reverts to showing the
current temperature. Or Press 2 x "Back"
Modifying Parameters
Display Unit
Default Unit: Fahrenheit (°F). Adjust display unit first before changing other parameters.
1
Pr
ess "up/down" and hold 5 seconds to access the menu.
2
Press "up/down" to find
3
Press “OK”
4
Press "up/down" to find
5
Press “OK”
6
Press "up/down" to change parameter
7
Press “OK”
Thermostat Differential
Default differential: 3°F
1
Press "up/down" and hold 5 seconds to access the menu.
2
Press "up/down" to find

Freeze Owner’s Manual 10 | Page
www.northslopechillers.com | (866) 826-299 | 1 0 S 10 0 W, Suite 1 | Salt Lake City, UT 84119
Revised: 12/18/2020
3
Press “OK”
4
Press "up/down" to find
5
Press “OK”
6
Press "up/down" to change parameter
7
Press “OK”
Upper and Lower limit of Thermostat Set Point
Default Limits: Upper = 65°F, Lower = 25°F
1
Press "up and down" and hold 5 seconds to access the menu.
2
Press "up/down" to find
3
Press “OK”
4
Press "up/down" to find (Upper limit of thermostat set point)
5
Press “OK”
6
Press
"up/down" to change parameter
7
Press “OK”
8
Press "up/down" to find (Lower limit of thermostat set point)
9
Press “OK”
10
Press "up/down" to change parameter
11
Press “OK”

Freeze Owner’s Manual 11 | Page
www.northslopechillers.com | (866) 826-299 | 1 0 S 10 0 W, Suite 1 | Salt Lake City, UT 84119
Revised: 12/18/2020
Troubleshooting
Symptoms
Possible Cause(s)
Compressor does
not start. The temperature rises but
the pump runs fine.
1.
Compressor is not being powered
2. Flow switch is not activated
Compressor hums but doesn’t start
1.
Low line voltage
2. Incorrect wiring
3. Internal compressor damage
Compressor does not run or try to start
( doesn’t hum)
1.
Open circuit due to blown fuse or open disconnects
2. Shorted motor windings
3. Compressor motor protector open
4. Open thermostat
5. Loss of refrigerant
6. Refrigerant solenoid valve not working
Compressor starts but trips on overload protector
1.
Suction
or discharge pressure is too high
2. Low line voltage
3. Broken overload protector
4. Mechanical damage to compressor
5. Shorted motor windings
Chiller short cycles
1.
Insufficient refrigerant
2. Leaking refrigerant solenoid valve
3. Leaking discharge valve
4. Malfunctioning expansion valve
High refrigerant pressure fault
1.
xcessive refrigerant
2. Clogged condenser
3. Condenser fan malfunction
4. Air entering condenser is too hot
Low refrigerant pressure fault
1.
Refrigerant leak
2. Coolant not flowing through heat exchanger
3. Liquid line solenoid valve stuck closed
4. Stuck expansion valve or bulb well not charged
5. Low ambient air temperatures
Lube protector fault
1.
Low compressor oil level due to:
●Oil trapped in system
●Compressor short cycling
●Not enough oil in system

Freeze Owner’s Manual 12 | Page
www.northslopechillers.com | (866) 826-299 | 1 0 S 10 0 W, Suite 1 | Salt Lake City, UT 84119
Revised: 12/18/2020
●
Suction pressure too low
2. xcessive refrigerant
3. Broke oil pump
Fluid temperature too cold
1.
Set point temperature is too low
2. Malfunctioning temperature controller
3. Malfunctioning temperature sensor
4. Leaking refrigerant solenoid valve
Fluid flow fault
1.
Fluid pump not working
2. Insufficient refrigerant
3. Air trapped inside system
4. Malfunctioning flow switch

Freeze Owner’s Manual 1 | Page
www.northslopechillers.com | (866) 826-299 | 1 0 S 10 0 W, Suite 1 | Salt Lake City, UT 84119
Revised: 12/18/2020
STANDARD PRODUCT WARRANTY
. LIMITED WARRANTY
Manufacturer warrants North Slope Chillers Products sold as “new” to be free from defects in material and
workmanship for a period of one (1) year from the date of purchase by a retail customer when used, stored,
inspected and serviced as specified in any operating instructions provided with the North Slope Chillers
Product. Exclusions from warranty consideration include, but are not limited to: normal wear and tear; abuse,
misuse, or non-standard application; act of nature; lack of proper maintenance; improper care or storage
(blankets should be folded and not rolled up); unauthorized repair; unauthorized modification; or attachment to
another product, use with any attachment or as integrated into another product. Neither Manufacturer, nor its
representatives, assumes any responsibility for any other products used with the North Slope Chillers Product
or for results of or damages caused to persons or property by the use of the North Slope Chillers Product. Only
the Manufacturer is authorized to make any warranty or representation and the customer may not rely on any
other warranty or representation. All implied warranties are hereby disclaimed.
MANUFACTURER MAKES NO OTHER WARRANTY OR REPRESENTATION OF ANY KIND, EXPRESSED
OR IMPLIED, IN FACT OR IN LAW, INCLUDING WITHOUT LIMITATION ANY
WARRANTY OF MERCHANTABILITY, NONINFRINGEMENT OR FITNESS FOR A PARTICULAR PURPOSE
OR USE OTHER THAN THE LIMITED WARRANTY SET FORTH ABOVE.
2. LIMITATION OF LIABILITY
MANUFACTURER’S SOLE LIABILITY SHALL BE AS SET FORTH HEREIN, AND SHALL EXTEND ONLY TO
INSPECTION, REPLACEMENT OR REPAIR OF THE NORTH SLOPE CHILLERS PRODUCT, AT THE
DISCRETION OF MANUFACTURER, WITHIN THE TIME PERIOD AND ON THE TERMS SET FORTH
HEREIN. MANUFACTURER HAS NO LIABILITY FOR ANY OTHER PRODUCTS USED WITH, ATTACHED
TO OR WITH WHICH THE NORTH SLOPE CHILLERS PRODUCT MAY BE INTEGRATED INTO, OR FROM
THE RESULTS OF SUCH USE, ATTACHMENT OR INTEGRATION. IN NO EVENT WILL MANUFACTURER
BE LIABLE FOR SPECIAL, INCIDENTAL, INDIRECT, PUNITIVE OR CONSEQUENTIAL DAMAGES. IN NO
EVENT SHALL MANUFACTURER’S LIABILITY EXCEED THE PAYMENTS RECEIVED BY
MANUFACTURER FOR THE NORTH SLOPE CHILLERS PRODUCT.
3. RETURNS
a. When any North Slope Chillers Product has been authorized to return for any inspection, or replacement, it
must be returned as specified in the Return Merchandise Authorization Form.
b. A Manufacturer-issued Returned Material Authorization (RMA) number authorizing a product return must be
acquired prior to sending any return. In addition, documentation of model, product serial number, dealer
invoice number, dated proof of resale, and description of failure shall accompany all returns.
c. All returns must come freight prepaid and in their original containers, or in a manner conducive to proper
shipping and handling procedures. Product(s) replaced, or shipped in accordance with the Return Merchandise
Authorization Form will be returned freight prepaid.
d. Manufacturer reserves the right to postpone, delay, or refuse warranty claim consideration for either
unauthorized returns or returns made by dealers or distributors whose open and active accounts are past due

Freeze Owner’s Manual 14 | Page
www.northslopechillers.com | (866) 826-299 | 1 0 S 10 0 W, Suite 1 | Salt Lake City, UT 84119
Revised: 12/18/2020
or delinquent. The dealer or distributor agrees that no warranties or other guarantees on any products shall be
made in excess of those made by Manufacturer. This agreement excludes Manufacturer or its representatives
from all liability not covered in this Warranty.
4. INDEMNIFICATION
Customer acknowledges that North Slope Chillers has no control over, and is not responsible for the manner in
which the Customer uses the Product(s). The Customer hereby agrees to indemnify, defend and hold
harmless (collectively, “indemnify” or “indemnification”) Customer, its affiliates, and their respective officers,
directors, employees, agents, representatives, successors and assigns from and against any and all suits,
proceedings, demands, judgments (including applicable pre-judgment and post-judgment interest, if any),
awards, losses, damages, costs, penalties, expenses, claims and liabilities, including reasonable attorneys’
fees, witness fees and court costs, and any other losses and liabilities of any kind or nature whatsoever
(“Damages”) of, or awarded to or settled with third parties in third party claims or actions, and the reasonable
costs of North Slope Chillers in successfully enforcing this indemnification obligation, in each case arising out
of one or more of the following: (a) the use, operation or modification of any Product, provided however, that
Customer shall have no indemnification obligation to the extent that the claim arises solely out of any negligent
acts or omissions by North Slope Chillers; (b) negligent acts or omissions or willful or intentional misconduct of
Customer (including its employees, agents, representatives, successors and assigns); and (c) failure to
comply with any relevant federal, state or local laws, regulations, rules or ordinances (including but not limited
to those related to hazardous waste and materials).
This manual suits for next models
9
Table of contents