OTT SDI-12 User manual

English
Operating instructions
OTT USB/SDI-12 Adapter

We reserve the right to make technical changes without further notice!

3
Table of contents
1 Scope of delivery 4
2 Order numbers 4
3 Basic saftey information 5
3.1 Markings and symbols used in the instruction 5
3.2 Note the following for safe and trouble-free operation 5
4 Introduction 6
5 Connecting a sensor to the 7
OTT USB/SDI-12 Adapter 7
5.1 Using the RS-485 interface 7
5.2 Via SDI-12 interface 8
5.3 Special case: Connecting OTT SLD via RS-485 interface 9
5.4 Special case: Connecting OTT PLS-C via RS-485-/SDI-12
interface using the OTT FAD 5 connecting kit 10
6 Install, start and operate software 11
7 LED displays 12
8 Repair 13
9 Notes about the disposal of old units 13
10 Technical data 14
Appendix A – Note on Declaration of Conformity 15

1 Scope of delivery
▶– 1 Interface converter with plug-in, 7-pin screw terminal strip
(RS-485-/SDI-12 interface) and USB interface (USB type B socket)
– 1 USB connection cable; USB connector type A to USB type B; 3 m
– 1 USB stick with USB interface driver and "OTT SDI-12 Interface" software
2 Order numbers
▶65.050.002.9.2
▶Accessories "OTT SDI-12 Adapter – OTT FAD 5" connecting kit 97.120.432.3.5
– for temporarily connecting the OTT PLS-C and
the OTT USB/SDI-12 Adapter within the OTT FAD 5
during conductivity sensor calibration
OTT USB/SDI-12 Adapter
OTT USB/SDI-12 Adapter
4

3 Basic saftey information
3.1 Markings and symbols used in the instruction
■This bullet point indicates an instruction relating to a specific action.
▶This bullet point indicates an item in a list.
– This bullet point indicates a sub-item in a list.
Remark: …
▶Information on easier and more efficient work
▶Further information
▶Definition
Please note: …
Information that prevents potential damage or malfunction on the
USB/SDI-12 Adapter.
3.2 Note the following for safe and trouble-free operation
▶Read these operating instructions before using the USB/SDI-12 Adapter for the
first time! Become completely familiar with the installation and operation of the
USB/SDI-12 Adapter! Keep these operating instrucations for later reference.
▶Only use the USB/SDI-12 Adapter as described in the operating instructions!
The intended use of the USB/SDI-12 Adapter is the temporary connection of
a sensor via the SDI-12 or RS-485 interface (SDI-12 protocol) to a PC – espe-
cially for changing the sensor configuration or for maintenance work (sensor
calibration). Any other use is not permitted! For further information ➝ refer to
Chapter 4, "Introduction".
▶In addition, observe the respective operating instructions of the sensor you are
connecting to the USB/SDI-12 Adapter.
▶Only install and maintain the USB/SDI-12 Adapter if you are appropriately
qualified to do so. If necessary, arrange training by OTT HydroService.
▶Ensure the electrical, mechanical, and climatic specifications listed in the
technical data are adhered to.
For further information ➝ refer to Chapter 10, "Technical data".
▶Do not make any changes or retrofits to the USB/SDI-12 Adapter. If changes
or retrofits are made, all guarantee claims are voided.
▶Have a faulty USB/SDI-12 Adapter inspected and repaired by our repair
center. On no account carry out repairs yourself!
For further information ➝ refer to Chapter 8, "Repair".
▶After putting the unit out of service, properly dispose of the USB/SDI-12
Adapter. On no account put the USB/SDI-12 Adapter into the normal domestic
waste. For further information ➝ refer to Chapter 9, "Note about the disposal
of used units".
5

4 Introduction
When the "OTT SDI-12 Interface" PC software is used, the "USB/SDI-12 Adapter"
provides the option of changing an existing SDI-12 sensor configuration via the
SDI-12 or RS-485 interface (SDI-12 protocol).
For this purpose, the sensor must be temporarily connected to the PC via the inter-
face converter.
The PC Software automatically recognizes the connected sensor type and provides
the appropriate SDI-12 commands conveniently as buttons. The software differen-
tiates between "Standard SDI-12 commands" and "Extended SDI-12 commands".
It is also possible to update the firmware of the sensors. For the OTT PLS-C pres-
sure sensor with conductivity sensor, an additional button is available for calibrat-
ing the conductivity sensor.
The "USB/SDI-12 Adapter" supports for example the following sensors:
– OTT Pluvio2 Precipitation Gauge,
– OTT PLS/OTT PLS 500 Pressure Probe,
– OTT PLS-C Pressure Probe with Conductivity Sensor,
– OTT RLS Radar Level Sensor,
– OTT CBS Bubble Sensor,
– OTT SE 200 Shaft Encoder,
– Side Looking Doppler OTT SLD.
You can also connect sensors from third-party manufacturers with a standard
SDI-12 interface. The software also provides buttons for standard SDI-12 com-
mands for these. In this case you can enter extended SDI-12 commands using an
SDI-12 Terminal Mode.
OTT USB/SDI-12
Adapter
USB-
connecting cable
PC with software
"OTT SDI-12 Interface"
OTT PLS 500
Fig. 1: Changing the factory configuration
of an OTT sensor using SDI-12 commands
at the example of a OTT PLS 500 pressure
probe via the "OTT USB/SDI-12 Adapter".
6

5 Connecting a sensor to the OTT USB/SDI-12
Adapter
5.1 Using the RS-485 interface
Please note:
▶The OTT USB/SDI-12 Adapter can supply a connected sensor with a maximum
current consumption of 100 mA. Beyond this, a separate power supply for the
sensor is required. If the green/red LED at the USB/SDI-12 Adapter lights up
red continuously during operation, the current consumption of the sensor is too
high!
▶For individual sensor types, it may be necessary to swap the connected wires at
RS-485 A and RS-485 B for trouble-free operation!
▶Maximum cable length/specification: see operating instructions of the connect-
ed sensor.
+12 VDC
RS-485 B
RS-485 A
GND
RS-485 B
RS-485 A
GND
7-pin screw terminal
strip
7-pin screw terminal
strip
RS-485
interface
sensor
RS-485
interface
sensor
GND
I < 100 mA
I ≥ 100 mA
Voltag supply
sensror
1
2
3
4
2
3
4
Fig. 2: Connection plan of OTT PLS to
"OTT USB/SDI-12 Adapter"via the
RS-485 interface.
7

5.2 Via SDI-12 interface
Please note:
▶The OTT USB/SDI-12 Adapter can supply a connected sensor with a maximum
current consumption of 100 mA. Beyond this, a separate power supply for the
sensor is required. If the green/red LED at the USB/SDI-12 Adapter lights up
red continuously during operation, the current consumption of the sensor is
too high!
▶Maximum cable length/specification: see operating instructions of the con-
nected sensors.
+12 VDC
SDI-12
GND
7-pin screw terminal
strip
7-pin screw terminal
strip
SDI-12
interface
sensor
5
SDI-12
GND
SDI-12
interface
sensor
GND
I < 100 mA
I ≥ 100 mA
Voltage supply
sensor
5
6
7
6
7
Fig. 3: Connection plan of sensor
with SDI-12 interface to the
"OTT USB/SDI-12 Adapter".
8

5.3 Special case: Connecting OTT SLD via RS-485 interface
Note: The connection of an OTT SLD via the SDI-12 interface is carried out as
shown in Chapter 5.2 (variant above; I ≤ 100 mA).
7-pin screw terminal strip
OTT SLD
max. 500 m
RS-422
Voltage supply
Rx+ 1
2
3
4
Rx–
Tx+
GND
+9 … 16 V
Tx–
RS-422
not in use
RS-422 RS-485
RS-485
Fig 4: Connection plan of OTT SLD
to "OTT USB/SDI-12 Adapter"via
RS-485 interface.
9

5.4 Special case: Connecting OTT PLS-C via RS-485-/SDI-12 inter-
face using the OTT FAD 5 connecting kit
The connection variant described here shows the connection of the OTT PLS-C
to the OTT USB/SDI-12 Adapter using the "OTT SDI-12 Adapter – OTT FAD 5
connecting kit".
■Disconnect the 4-pin plug connector (screw terminal strips) in the humidity
absorber. If the voltage supply to the OTT PLS-C is continuous (not switched),
the 2-pin connector can remain plugged.
■Connect the connecting cable of the connecting kit to the 4-pin plug in the
humidity absorber and to the OTT USB/SDI-12.
Note: If you do not use the connecting kit, the connection is made as shown in
Chapter 5.1 or 5.2 (variant in each case above; I ≤ 100 mA).
OTT PLS-C
+6 … 28 V
GND
RS-485 B
RS-485 A
SDI-12: max. 100 m/RS-485: max. 1000 m
SDI-12 Data
SDI
GND
BA
BA
GND
SDI
BA
SDI
GND
+
GND
+
OTT FAD 5
Connecting cable OTT SDI-12
Adapter – OTT FAD 5 connecting kit
Connection
datalogger
7-pin screw terminal strip
Fig. 5: Connection plan of OTT PLS-C to
"OTT USB/SDI-12 Adapter"via
SDI-12-/RS-485 interface.
Depending on the variant of the OTT PLS-C
only one interface type (SDI-12 or RS-485)
is used. The "OTT USB/SDI-12 Adapter –
OTT FAD 5 connecting kit" still offers the
possibility to connect the wires of the inter-
face not in use to the screw terminal block
10

6 Install, start and operate software
In order to change the configuration of an SDI-12 sensor, you need the PC soft-
ware "OTT SDI-12 Interface" (SDI_Interface.exe) in addition to the USB/SDI-12
Adapter.
In addition, a special USB interface driver must be installed on the PC.
The setup files of the software and the USB interface driver are included on the
USB stick supplied at the factory. Alternatively, you can also find them on the
website "www.ott.com/resources" for download (free of charge).
Hardware and software requirements: Current standard PC with USB interface
(USB socket type A; desktop/tower version or notebook); operating system:
Microsoft Windows 10 or newer.
Installing the USB interface driver on the PC:
The USB interface driver must be installed once before using the "OTT SDI-12
Interface" software for the first time. For installation, the USB/SDI-12 adapter
must not yet be connected to the PC!
■Log on to the PC with administrator rights.
■If the setup file of the USB interface driver was downloaded from the internet
(file extension: ".zip"): Extract (unzip) the setup file.
■Start the setup file "CDMxxxxxx_Setup.exe" 1) ➝the "FTDI CDM Drivers –
InstallShield Wizard" opens 2).
■Follow the installation instructions on the screen.
■Then connect the USB/SDI-12 Adapter to the PC via the factory-supplied USB
connection cable ➝the PC completes the driver installation on its own.
Install and start software "OTT SDI-12 Interface"on PC:
■Log on to the PC with administrator rights.
■Start the setup file "Setup_SDI12Interface_Vxxxx_DE.exe" 1) ➝the
"OTT SDI-12 Interface – InstallShield Wizard" opens 2).
■Follow the installation instructions on the screen.
■If the USB connection cable was removed after installing the USB interface
driver: Reconnect the USB/SDI-12 Adapter to the PC via the USB connection
cable.
■Start the software "OTT SDI-12 Interface" (Windows Start menu | subdirectory
"OTT" | "SDI Interface") ➝the USB/SDI-12 Adapter is now ready for use; the
green/red LED on the USB/SDI-12 adapter must be continuously green.
Operating the software "OTT SDI-12 Interface":
The software has an integrated, context-sensitive online help. To get detailed infor-
mation on how to use the software, open a separate window with help topics:
■Select menu "?" | function "Help"or alternatively press "F".
1) „xxxxxx”; „xxxx”: current version number
2) if this file was downloaded from the Internet, a security warning will appear first
11

7 LED displays
To display different operating states, the OTT USB/SDI-12 Adapter has a
▶red LED and
▶green/red LED.
▶red LED – flashes briefly several times
➝connected sensor and PC communicate
via the USB/SDI-12 interface
▶green/red LED – lights up green continuously
➝the USB/SDI-12 Adapter is ready for use
– lights up red continuously
➝Overcurrent shutdown activated: Current consumption
of the connected sensor > 100 mA
– off
➝the USB/SDI-12 Adapter has no supply voltage: USB
connection cable not/not correctly connected
USB interface
(Socket type B)
Communication
activ (flashing) ready for operation
Overcurrent
shutdown
active
Fig. 6: Position of the LEDs and the
USB interface on the side of the
OTT USB/SDI-12 Adapter.
12

8 Repair
■In case of device failure, please contact the OTT repair center.
OTT HydroMet GmbH
Repaircenter
Ludwigstr. 16
87437 Kempten · Germany
Phone +49 831 5617-433
Fax +49 831 5617-439
Please note: Have a faulty OTT USB/SDI-12 Adapter checked and repaired
only by the OTT repair center! Never attempt to repair the unit yourself! Any
repairs or attempted repairs carried out by the customer will void any warranty.
9 Notes about the disposal of old units
Within the member countries of the European Union
In accordance with the European Union guideline 2012/19/EU, OTT takes back
old devices within the member countries of the European Union and disposes of
them in the appropriate way. The devices concerned by this are marked with the
symbol shown aside.
■For further information on the return procedure, please contact your local sales
contact. You will find the addresses of all sales partners in the internet on
"www.ott.com". Please take into consideration also the national implementation
of the EU guideline 2012/19/EU of your country.
For all other countries
■After putting the unit out of service, properly dispose of the
OTT USB/SDI-12 Adapter.
■Observe the regulations applicable in your country for the disposal of
electronic devices!
■Never dispose of the OTT USB/SDI-12 Adapter in the normal domestic waste!
Materials used
Refer to Chapter10, Technical data.
13

10 Technical data
Power supply 5 VDC via USB interface
Current consumption < 500 mA
Supply of sensor
Power supply 12 VDC ±10 %
Current consumption < 100 mA
Interfaces – SDI-12 version 1.4
– RS-485, two-wire (SDI-12 protocol; 1.4)
– USB 2.0
Connections – 7-pin, plug-in, screw terminal strip
– USB socket, type B
Dimensions * (L x W x H) 98 mm x 57 mm x 26 mm
Weight * ca. 0,1 kg
Housing material aluminium, anodised
Protection class IP 20
Operating temperature 0 … +55 °C
Storage temperature –45 … +85 °C
Humidity 0 … 90 %, non-condensing
CE (EU) Device complies with the essentil require-
ments of the EMC Directive 2014/30/EU
FCC (US)
FCC Part 15, Class "B"Limits Device complies with Part 15 of the FCC
Rules.
Operation is subject to the following
conditions:
- the equipment must not cause harmful
interference
- the equipment must accept any interferen-
ce recieved, including interference that
may cause undesired operation.
IC (CN)
Canadian Radio Interference-Causing This Class B digital device meets all require-
Equipment Regulation ments of the Canadian Regulation,
ICES-003, Class B ICES-003, Class B Interference-Causing
Equipment Regulations.
* including 7-pin screw terminal strip
14

Appendix A – Note on Declaration of Conformity
If necessary, you can download the current version of the Declaration of
Conformity for the OTT USB/SDI-12 Adapter from our website as a PDF file:
"www.ott.com/resources".

Document number
65.050.002.B.E 02-0922
OTT HydroMet GmbH
Ludwigstrasse 16
87437 Kempten · Germany
Phone +49 831 5617-0
Fax +49 831 5617-209
www.otthydromet.com