3-WAY ISOLATION OF ANALOG SIGNALS
UNIVERSAL CONVERSION MODULE - INPUTS AND OUTPUTS
SELECTED VIA DIP SWITCH SETTINGS
OVER 35 INPUT AND OUTPUT ANALOG CONVERSION
COMBINATIONS
ULTRA SLIM DESIGN – ONLY 0.244 WIDE
19 to 30 VDC POWER
GENERAL DESCRIPTION
The IAMA can isolate and convert over 35 combinations of analog signal
ranges. The IAMA converts and transmits signals linearly proportional to the
input. DIP switch range selection eliminates the need to order and stoc
different modules for each input and output signal range, and allows quic and
convenient setup for over 35 standard signal conversions. In addition to the
conversion capabilities, the IAMA modules feature optically isolated
Input/Output signal circuits and isolated Power to Input, Power to Output
circuits. The modules’ overall full scale accuracy typically exceed 0.04%. DIN
rail mounting saves time and panel space. The units are equipped with universal
mounting feet for attachment to standard top hat profile rail according to
EN50022 - 35x7.5.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
SPECIFICATIONS
1. POWER: 19.2 to 30 V DC, 450 mW max.
2. INPUT / OUTPUT RANGES: See table 1
3. SPAN ADJUSTMENT: Potentiometer, located below transparent top cover.
4. MAX INPUT SIGNAL:
Current: 50 mA
Voltage: 30 V
5. INPUT RESISTANCE:
Current: Approx. 50 Ω
Voltage: Approx. 100 Ω
6. MAX OUTPUT SIGNAL:
Current: 28 mA/12.5 V
Voltage: 12.5 V/22 mA
7. LOAD RESISTANCE:
Current: 500 Ωmax.
Voltage: 10 Ωmin
8. OUTPUT COMPLIANCE:
Current: 12.5 V max (500 Ω). Ripple: < 20 mV
Voltage: 22 mA (10 Ω). Ripple: < 20 mV
9. TRANSMISSION ERROR:
The transmission error without adjustment is < 0.4%. Using the
potentiometer, the error can be adjusted to < 0.1%.
10. TEMPERATURE COEFFICIENT:
Max.: < 0.01%/K
Typ.: < 0.002%/K
11. CUT-OFF FREQUENCY: 100 Hz
12. STEP RESPONSE (FROM 10 to 90 % : 3.5 msec
13. TEST VOLTAGE (Input/Output/Supply : 1.5 V, 50 Hz, 1 min.
14. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: -20°C to 65°C (-4°F to 149°F)
Storage Temperature Range: -40°C to +85°C (-40°F to 185°F)
MODEL IAMA - CONFIGURABLE 3-WAY ISOLATING AMPLIFIER
Bulletin No. IAMA6-X
Drawing No. LP0609
Released 06/05
el +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
DIMENSIONS In inches (mm)
MODEL NO. DESCRIPTION PART NUMBER
IAMA IAMA0006Configurable 3-Way Isolating Amplifier
CAUTION: Rea complete
instructions prior to installation
an operation of the unit.
CAUTION: Risk of electric shock.
ORDERING INFORMATION
CUS
UL
R
LISTED
PROCESS CO TROL
EQUIPME T FOR HAZARDOUS
LOCATIO S 31Z
CLASS 1, DIV 2
GROUPS A, B, C, D T5

ForSalesandSupport,ContactWalkerEMD•Toll-free:(800)876-4444•Tel:(203)426-7700•Fax:(203)426-7800•www.walkeremd.com
2
15. TESTS/APPROVALS:
PROCESS CONTROL EQUIPMENT FOR
HAZARDOUS LOCATIONS
31ZN
Class I Div 2 Groups A, B, C, D T5
A) This equipment is suitable for use in Class I, Division 2, Groups A, B,
C and D or non- hazardous locations only.
B) Warning - explosion hazard - substitution of components may impair
suitability for Class 1, Division 2.
C) Warning - explosion hazard - do not disconnect equipment unless power
has been switched off or the area is nown to be non-hazardous.
16. CERTIFICATIONS AND COMPLIANCES:
1EN 61000 corresponds to IEC 1000
2Criterion B: Temporary impairment to operational behavior that is corrected
by the device itself.
3Criterion A: Normal operating behavior within the defined limits.
4EN 55011 corresponds to CISPR11
5Class A: Area of application industry.
17. CONNECTIONS: 12 AWG max., Stripping length: 0.47" (12 mm)
18. CONSTRUCTION: Polybutylenterephthalate PBT, blac
19. MOUNTING: Standard DIN top hat (T) profile rail according to EN50022
- 35x7.5
20. WEIGHT: 2 oz. (54 g)
INPUTS
The IAMA accepts a full range of process signal inputs and isolates and
converts these signals to common industrial control signals. The input signal
combinations are configured by ma ing specific DIP switch selections on the 6
and 2 position DIP switches.
OUTPUTS
As with the input choices, the process signal output of the modules is DIP
switch selectable. The maximum output current signal is 28 mA with =500 Ω
output resistance and the maximum output voltage signal is 12.5 V with =10 KΩ
output resistance. The transmission error without adjustment is < 0.4%. Using
the potentiometer, the error can be adjusted to < 0.1%.
TABLE 1 - CONFIGURATION
CUS
UL
R
LISTED
Immunity to Interference Accor ing to EN 61000-6-21
Discharge of static electricity (ESD) E 61000-4-2 Criterion B2
Electromagnetic HF field E 61000-4-3 Criterion A3
Fast transients (Burst) E 61000-4-4 Criterion B2
Surge voltage capacities (Surge) E 61000-4-5 Criterion B2
Conducted disturbance E 61000-4-6 Criterion A3
Noise Emission Accor ing to EN 50081-2
oise emission of housing E 550114Class A5
Conformance With EMC Gui eline 89/336/EEC An Low Voltage Directive 73/23/EEC
BLOCK DIAGRAM
IN
RANGES
OUT 1
DIP SWITCHES
OUTPUT (S2)
234561
INPUT (S1)
2
0 –10 V 0 – 20 mA off off off off off off off off
4 - 20 mA off off off off off O off off
0 – 10 V O off O off off off off off
2 – 10 V O off O off off O off off
0 – 5 V O O off off off off off off
1 – 5 V O O off off off O off off
2 – 10 V 0 – 20 mA off off off O O off off off
4 - 20 mA off off off off off off off off
0 – 10 V O off O O O off off off
2 – 10 V O off O off off off off off
0 – 5 V O O off O O off off off
1 – 5 V O O off off off off off off
0 – 5 V 0 – 20 mA off off off off off off O off
4 - 20 mA off off off off off O O off
0 – 10 V O off O off off off O off
2 – 10 V O off O off off O O off
0 – 5 V O O off off off off O off
1 – 5 V O O off off off O O off
1 – 5 V 0 – 20 mA off off off O O off O off
4 - 20 mA off off off off off off O off
0 – 10 V O off O O O off O off
2 – 10 V O off O off off off O off
0 – 5 V O O off O O off O off
1 – 5 V O O off off off off O off
0 – 20 mA 0 – 20 mA off off off off off off off O
4 - 20 mA off off off off off O off O
0 – 10 V O off O off off off off O
2 – 10 V O off O off off O off O
0 – 5 V O O off off off off off O
1 – 5 V O O off off off O off O
4 - 20 mA 0 – 20 mA off off off O O off off O
4 - 20 mA off off off off off off off O
0 – 10 V O off O O O off off O
2 – 10 V O off O off off off off O
0 – 5 V O O off O O off off O
1 – 5 V O O off off off off off O

ForSalesandSupport,ContactWalkerEMD•Toll-free:(800)876-4444•Tel:(203)426-7700•Fax:(203)426-7800•www.walkeremd.com
3
APPLICATION
Cost efficiency measurements of a printing company included the reduction
of bul stoc of the various in s used in their printing processes. The company
currently had various in flow and level devices with different current and
voltage outputs and wanted to record these measurements into a control
room PC. Several IAMA Universal Signal Conditioning Modules were
the answer. The IAMA’s universal input allowed for easy signal
conditioning of the various output signals to the required PC’s Bus
Board 0 to 10 VDC input signal. In this case, the IAMA’s re-
transmitted 0 to 10 VDC output was field calibrated, negating the
expense and time required to rewrite the PC’s software
parameters. In addition to accepting multiple signal types,
the IAMA also provides the necessary electrical isolation
between the control room PC and the hazards of the
printing floor electrical noise.
WIRING CONNECTIONS
Primary power is connected to terminals 7 or 3 (19.2 – 30 VDC) and 8 or 4
(GND 3). For best results, the power should be relatively “clean” and within the
specified variation limits. Drawing power from heavily loaded circuits or from
circuits that also power loads that cycle on and off, should be avoided.
The input signal is connected to pins 1 (In U,I) and 2 (GND 1). Connections
for the output signal are made on pins 5 (Out U,I) and 6 (GND 2).
INSTALLATION
The unit is equipped with a universal mounting foot for attachment to
standard DIN style top hat (T) profile rail according to EN50022 - 35 x 7.5 and
35 x 15. The unit should be installed in a location that does not exceed the
maximum operating temperature and provides good air circulation. Placing the
unit near devices that generate excessive heat should be avoided.
T Rail Installation
To install the IAMA on a “T”
style rail, angle the module so that
the top groove of the “foot” is
located over the lip of the top rail.
Push the module toward the rail
until it snaps into place. To
remove a module from the rail,
insert a screwdriver into the slot
on the bottom of the “foot”, and
pry upwards on the module until it
releases from the rail.

ForSalesandSupport,ContactWalkerEMD•Toll-free:(800)876-4444•Tel:(203)426-7700•Fax:(203)426-7800•www.walkeremd.com
LIMITED WARRANTY
The Company warrants the products it manufactures against defects in materials and wor manship
for a period limited to one year from the date of shipment, provided the products have been stored,
handled, installed, and used under proper conditions. The Company’s liability under this limited
warranty shall extend only to the repair or replacement of a defective product, at The Company’s
option. The Company disclaims all liability for any affirmation, promise or representation with
respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against
damages, claims, and expenses arising out of subsequent sales of RLC products or products
containing components manufactured by RLC and based upon personal injuries, deaths, property
damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be
to any extent liable, including without limitation penalties imposed by the Consumer Product Safety
Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty
Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those
expressly contained herein. The Customer ac nowledges the disclaimers and limitations contained
herein and relies on no other warranties or affirmations.
Red Lion Controls
20 Willow Springs Circle
York PA 17402
el +1 (717) 767-6511
Fax +1 (717) 764-0839
Red Lion Controls AP
31, Kaki Bukit Road 3,
#06-04/05 echLink
Singapore 417818
el +65 6744-6613
Fax +65 6743-3360
Red Lion Controls BV
Basicweg 11b
NL - 3821 BR Amersfoort
el +31 (0) 334 723 225
Fax +31 (0) 334 893 793
Table of contents