Robinson LION BOILERS LEB Series User manual

TM
LION
BOILERS
LEB Series Boiler
Installation Manual
Warning:
Use only water or an
appropriate antifreeze. Do not use any
other liquids especially methanol,
automotive antifreeze or any kind of oil.
August 2013 Printed in Canada

2

Before You Begin
Please read this manual thoroughly before you begin. If you encounter problems please
see the troubleshooting section near the end of this manual. This boiler should only be
installed and tested by qualified personnel with experience in hydronic heating
systems, and electrical installations. This boiler should not be modified or altered in
any manner. Any modification or alteration may cause the boiler to malfunction and
cause serious damage and injury, and will void the manufacturers warranty.
The installation of this boiler must comply with local regulations and
The installation of this boiler must comply with local regulations andThe installation of this boiler must comply with local regulations and
The installation of this boiler must comply with local regulations and
codes. erify the “Name Plate” rating to properly size conductors, and
codes. erify the “Name Plate” rating to properly size conductors, andcodes. erify the “Name Plate” rating to properly size conductors, and
codes. erify the “Name Plate” rating to properly size conductors, and
overcurrent protection.
overcurrent protection.overcurrent protection.
overcurrent protection.
(1)Before installation, ensure that the local electrical inspection authority will
accept connection of this boiler to the existing panel.
(2)This boiler may only be installed and tested by qualified personnel.
(3)The electrical power supply should be checked for adequacy for the additional
load of the boiler. All models require connection of 240 volt single phase power
to terminals L1 and L2, and connection of a neutral conductor to the N terminal
(see Fig. 4).
Introduction
Your Electric Boiler has been designed to exacting specifications to provide controlled
efficient heating and maximum service life. The boiler is controlled internally by an
electronic control board. The boiler is energized when the external thermostat wired to
the control board calls for heat. The circulation pump is started first to provide flow
through the heating system, then the heating elements are staged on as required. A
temperature sensor mounted in the tank monitors the water temperature, and the
internal control board maintains the temperature of the water exiting the boiler by
staging the elements on or off as required. This is know as modulating. The
temperature is set by the aquastat control on the lower left corner of the control board.
The modulating control strategy built into the control board uses only the minimum
number of elements necessary to maintain the desired temperature, resulting in
maximum comfort.
3

Specifications
Model kW Volts Phase Amps Minimum Breaker Size Wire Size (Amps)
LEB-3 3 240 1 12.5 20 16
LEB-4 4 240 1 16.7 30 24
LEB-5 5 240 1 20.8 30 24
LEB-6 6 240 1 25.0 40 32
LEB-7 7 240 1 29.2 40 32
LEB-8 8 240 1 33.3 50 40
LEB-9 9 240 1 37.5 50 40
LEB-10 10 240 1 41.7 60 48
Control oltage 24 olts AC
Tank Capacity – Approx. 1 Gallon
Shipping Weight – about 50 pounds
Inlet and Outlet pipe size 3/4” NPT
Pump Switch Rating, 120 olt, 1 HP
Floor heating temperatures are generally 90º F to 110º F
Minimum Recommended Operating Pressure 12 PSI
Warning: The control transformer is sized to power only the internal
Warning: The control transformer is sized to power only the internalWarning: The control transformer is sized to power only the internal
Warning: The control transformer is sized to power only the internal
controls. External devices must be powered from a separate power
controls. External devices must be powered from a separate powercontrols. External devices must be powered from a separate power
controls. External devices must be powered from a separate power
source.
source.source.
source.
New Boiler Inspection
All Boilers are inspected and tested at the factory prior to shipment. On receipt of your
new boiler, be sure to check for any damage that may have occurred during shipping.
Any such damage should be reported to the carrier immediately.
Never install a damaged boiler.
Never install a damaged boiler.Never install a damaged boiler.
Never install a damaged boiler.
Unpacking
The Boiler is shipped to you in one carton, which contains the boiler, a pressure &
temperature gauge, pressure relief valve, air vent, and fittings.
4

System Design
For proper operation of the heating system, the boiler, the radiation system, and
maximum heat loss of the building must be considered. The boiler selected should
provide between 110% and 130% of the maximum design heat loss of the building.
The radiation system should be designed to properly dissipate the heating capacity of
the boiler at the radiation system design temperature.
The recommended cold fill pressure of the system is 12 psi; this pressure should leave
at least 4 psi at the highest point in the heating system. Pressure will decrease at a rate
of 0.433 psi per foot above the fill point. An expansion tank must be included to allow
for approximately 4% expansion of the water in the entire heating system. As the water
in the system is heated the pressure will increase, but a properly sized expansion tank
will prevent the pressure from exceeding the recommended operating pressure.
The radiators or floor system should be designed with parallel loops. If too many
radiators or floor loops are connected in series, the accumulated heat loss may cause
uneven heating. The minimum recommended flow rate must be used, but higher flow
rates may give more even heating. If a number of parallel heating circuits are used,
valves are usually required to balance the flow in each circuit to provide uniform
heating.
A zoned heating system is also possible with separate heating zones and individual
thermostats in each zone. Individual thermostats in each zone can control a zone valve,
or a circulation pump providing flow to that zone. End switches on the zone valves can
be wired in parallel to the thermostat connection of the boiler.
The entire heating system must comply with any local codes or regulations.
The entire heating system must comply with any local codes or regulations.The entire heating system must comply with any local codes or regulations.
The entire heating system must comply with any local codes or regulations.
Installation
Location
(1)The site selected for installation of your boiler should leave at least 24” of clear
space in front of the unit. The sides and bottom require only enough room for
plumbing and electrical connections (see Fig. 2). The rear of the unit is
considered a “Zero Clearance” face (see Fig. 2). When mounting the boiler on
the wall, ensure that the wall can withstand the weight of the unit including
water (approximately 60 lbs.). Mounting tabs are provided on top for 3/8” bolts
or screws, these are for wall mounting.
(2)The space selected should be well ventilated and kept normally below 77º F or
25º C.
5

(3)Though the unit is suitable for wall mount, only the rear face indicated as “Zero
Clearance” may be mounted against combustible surfaces.
(4)Units must be mounted straight as shown in Fig. 2 with the outlet at the top,
and the inlet on the bottom. See “Up Arrow” on label on side of boiler.
(5)The circulation pump should be connected to the outlet side of the boiler (see
Fig. 3).
Mechanical Installation
(1)Refer to Fig. 3 for a typical system before installation.
(2)Packed with your boiler are the following.
a) Temperature & Pressure Gauge
b) Pressure Relief alve
c) Air ent
d) Necessary fittings.
(3)Mount unit as per instructions under “Location”
(4)Install Pressure Relief alve and Pressure & Temperature Gauge. These must be
connected directly to the boiler as shown in Fig. 1
(5)A discharge line must be attached to the outlet of the pressure relief valve. The
discharge line will direct water or steam from the pressure relief valve should it
open. The discharge line must be as short as possible, not have any valves or
restrictions, not be smaller than the outlet of the pressure relief valve, slope
downwards, and the end must be open to the atmosphere. The discharge line
should terminate at a drain 6 inches above the floor level.
(6)Install inlet and outlet piping.
(7)An expansion tank must be installed (see Fig. 3) to allow for water expansion as
the system is heated.
Dissimilar Metals
Do not connect dissimilar metals to the inlet and outlet. Dielectric Unions should be
used. Another solution is to use brass or cast iron fittings between the boiler and any
copper fittings that you may be using. Failure to do so will result in galvanic corrosion
and cause the tank to fail over time.
This is not covered under the warranty.
This is not covered under the warranty.This is not covered under the warranty.
This is not covered under the warranty.
Pump Installation
The circulation pump should be positioned as close to the boiler as possible, with the
delivery arranged to pump out of the tank outlet on the upper left side of the boiler
(see Fig. 3)
6

The pump is powered by the boiler through terminals PL and PN located on the 120
volt terminal block (lower right terminal block see Fig. 4). The pump starts when the
thermostat terminals on the control board are closed, and stops when these terminals
are opened.
If desired, the pump may be operated continuously during the heating season. Should
you decide to wire the pump in this manner, it should be wired to the same supply
circuit as the boiler to prevent the pump from being turned off while the boiler is still
powered.
hermostat Connection
The thermostat connection is 24 volt AC. Only connect the thermostat after all other
work is complete, and the entire heating system is thoroughly purged of air. The
thermostat is connected to the terminals T1 and T2 on the control circuit board (see
Fig. 4). In zoned systems, the end switches of all the zone valves may be connected in
parallel and hooked up to the thermostat connection on the control board. For a typical
system (see Fig. 5).
Thermostats described as “Power Stealing” or as “Parasitic Thermostats”
Thermostats described as “Power Stealing” or as “Parasitic Thermostats”Thermostats described as “Power Stealing” or as “Parasitic Thermostats”
Thermostats described as “Power Stealing” or as “Parasitic Thermostats”
must not be used.
must not be used.must not be used.
must not be used.
hermostat Anticipator
The thermostat anticipator setting recommended is 0.2 amps. Failure to correctly
adjust this setting may result in unsatisfactory comfort conditions, and could result in
damage to the thermostat.
This setting may have to be adjusted slightly to ideally match the boiler control system
to the thermostat, as well as overcome the normal inertia of the radiation system. A
setting to low will be characterized by a short cycle, which does not allow the room
temperature to be satisfied before the boiler shuts down. A setting too high will be
characterized by a long cycle, which allows the room temperature too rise to high
before the boiler shuts down. Adjustments should be made to the setting, if required,
but should not exceed 0.1 amps per adjustment.
Newer electronic thermostats typically have provisions for the cycle length, and type of
heating system. The instructions for the thermostat should be followed.
In zoned systems where the thermostat is controlling a zone valve, or circulation pump
and not the boiler, the anticipator should be set to match the current draw of the zone
valve being used.
7

emperature Control Setting (Aquastat)
The boiler has a temperature control knob know as an aquastat on the lower left corner
of the control board. This sets the maximum temperature that the boiler will operate
at. The internal control system monitors the water temperature in the tank and
modulates the heating elements to maintain the water temperature. Note that the
setting on the knob only sets the maximum temperature, it is normal for the boiler to
operate at lower temperatures than this setting at times, this is especially true in the
spring and fall when it is not so cold outside. The actual temperature setting you need
The actual temperature setting you needThe actual temperature setting you need
The actual temperature setting you need
to set it to will be determined by the type of heating system the boiler is installed in.
to set it to will be determined by the type of heating system the boiler is installed in.to set it to will be determined by the type of heating system the boiler is installed in.
to set it to will be determined by the type of heating system the boiler is installed in.
The range of the aquastat is from 15 to 54º C (60 to 130º F).
Start Up
A new system must be thoroughly cleaned, flushed and drained, then refilled with
clean water. Foreign material circulating through the system could be detrimental to
the pump and to the heat transfer efficiency of the system and may lead to future
problems. The system must be thoroughly purged of air before it is energized for the
The system must be thoroughly purged of air before it is energized for theThe system must be thoroughly purged of air before it is energized for the
The system must be thoroughly purged of air before it is energized for the
first time. Elements will burn out if the boiler is not full of water when the boiler is
first time. Elements will burn out if the boiler is not full of water when the boiler isfirst time. Elements will burn out if the boiler is not full of water when the boiler is
first time. Elements will burn out if the boiler is not full of water when the boiler is
turned on. Do not connect the thermostat wires until the entire system is full of
turned on. Do not connect the thermostat wires until the entire system is full ofturned on. Do not connect the thermostat wires until the entire system is full of
turned on. Do not connect the thermostat wires until the entire system is full of
water, and thoroughly purged of air.
water, and thoroughly purged of air.water, and thoroughly purged of air.
water, and thoroughly purged of air.
The automatic air vent is to assist in removing air from the top of the tank to prevent
elements from burning out. It alone is not sufficient in removing air from the entire
heating system. Additional air vents must be installed throughout the system to
Additional air vents must be installed throughout the system toAdditional air vents must be installed throughout the system to
Additional air vents must be installed throughout the system to
eliminate any air that may enter the system.
eliminate any air that may enter the system.eliminate any air that may enter the system.
eliminate any air that may enter the system.
Check List
(1)Plumbing complete.
(2)System flushed.
(3)System free of air (purged).
(4)Pump rotates freely.
(5)Thermostat connected.
(6)Thermostat anticipator set.
(7)Electrical supply connections complete.
Maintenance
At the start of each heating season it is advisable to have a qualified technician check
and inspect the boiler and the heating system for proper operation.
8

roubleshooting Guide
Problem
ProblemProblem
Problem Correction
CorrectionCorrection
Correction
Boiler not heating, water cool. Check power supply, fuses or breakers.
Check thermostat setting.
Check temperature control inside the boiler.
Boiler heating pipes cool. Check for air in system.
Check pump circulation.
Check all valves.
Check for flow stoppage, or air locks.
Boiler rapid cycles. Check anticipator setting.
Check pump circulation.
Boiler operates continuously. Check anticipator setting.
Boiler noisy. Oversized pump.
Flow rate too high.
Flow rate too low.
Pump location incorrect.
Boiler not heating enough Insufficient capacity.
Burnt Elements.
Flow rate too low.
Pressure too high. Defective expansion tank.
Defective automatic fill valve.
Expansion tank too small.
Safety relief valve dripping. Check expansion tank.
Flush relief valve.
See the troubleshooting step by step procedure at the end of this manual for additional
information.
9

Lion Boilers Limited Warranty
Concept Manufacturing Inc. (the "Manufacturer") warrants its Hydronic Boiler (the
"Boiler") to be free from defects in material and workmanship under normal use and
maintenance for a period of two (2) years from the date of original installation. The
Manufacturer further warrants the tank to be free from defects in material and
workmanship under normal use and maintenance for an additional eight (8) years for a
total of ten (10) years from the date of original installation.
If any part of the Boiler is found by the Manufacturer, as sole judge, to be defective in
material or workmanship, the Manufacturer, at its sole discretion, agrees to:
(i) Repair any defect;
(ii) replace any defective Boiler; or
(iii) refund the original purchase price of the Boiler.
The Manufacturer, at its sole discretion, reserves the right, at any time during the
warranty period, to refund the original purchase price to the current owner of the
Boiler regardless of any prior attempt by the Manufacturer to repair or replace that
Boiler.
The obligation of the Manufacturer to repair, replace or refund the purchase price
exists provided the defective part or complete unit is returned to the Manufacturer.
ANY AND ALL TRANSPORTATION COSTS WILL BE BORNE BY THE
PURCHASER.
Repair, replacement or refund of any defective part or unit shall be considered as
complete fulfillment of this warranty.
THIS WARRANTY DOES NOT APPLY TO:
1. Labor or other costs incurred for diagnosing, repairing, removing, installing,
reinstalling, shipping, servicing or handling of any defective part or complete unit;
2. Costs incurred for normal maintenance;
3. The workmanship of any installer of the Boiler. In addition, this warranty does not
assume any liability of any nature for unsatisfactory performance caused by improper
installation;
4. Damage or repair as a consequence of storage and handling, improper or careless
installation, improper maintenance, or misuse or neglect as determined by the
10

Manufacturer as sole judge;
5. Damage as a consequence of misapplication, abuse, improper servicing,
unauthorized alteration, improper operation or usage contrary to the Manufacturer's
direction, design or specifications, as to any and all of which the Manufacturer shall be
the sole judge;
6. Damage as a consequence of electrical surges, inadequacy or interruption of
electrical services or corrosion, whether caused by chemicals or the environment;
7. Damages as a consequence of floods, winds, fires, lightning, freezing conditions or
other conditions beyond the control of the Manufacturer.
LIMITATION OF WARRANTY
LIMITATION OF WARRANTYLIMITATION OF WARRANTY
LIMITATION OF WARRANTY
THIS LIMITED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES WHETHER
EXPRESS OR IMPLIED, AND ALL SUCH OTHER WARRANTIES, INCLUDING
WITHOUT LIMITATION IMPLIED WARRANTIES OF MERCHANTABILITY OR
FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED AND
EXCLUDED FROM THIS LIMITED WARRANTY.
THE MANUFACTURER'S LIABILITY ON ANY CLAIM OF ANY KIND, INCLUDING
NEGLIGENCE, WITH RESPECT TO THE GOODS OR SER ICES CO ERED
HEREUNDER, SHALL IN NO WAY EXCEED THE PURCHASE PRICE OF THE
BOILER, OR PART THEREOF, WHICH GI ES RISE TO THE CLAIM. IN NO E ENT
SHALL THE MANUFACTURER BE LIABLE FOR SPECIAL, INCIDENTAL, INDIRECT,
OR CONSEQUENTIAL DAMAGES, OR ANY DAMAGES IN THE NATURE OF
PENALTIES. ALL WORK UNDER THE TERMS OF THIS WARRANTY SHALL BE
PERFORMED DURING NORMAL WORKING HOURS.
ALL REPLACEMENT PARTS OR UNITS, WHETHER NEW OR
REMANUFACTURED, ASSUME AS THEIR WARRANTY PERIOD ONLY THE
REMAINING TIME PERIOD OF THIS WARRANTY.
11

12

13

14

15

16

roubleshooting Step By Step Procedure
The following is a step by step procedure to help in troubleshooting any problems with
this boiler. These steps should be preformed only by qualified personnel with
experience in hydronic heating systems, and electrical heating equipment. You are
working with high voltages and should be extremely careful.
(1)Make sure that there is power to the boiler. There must be power to the boiler
to complete these troubleshooting steps.
a) There should be power at the main terminal block. You should read 120 volts
between L1 and N, 120 volts between L2 and N, and 240 volts between L1
and L2.
b) Disconnect the thermostat wires from terminals T1 and T2. Measure the
voltage at the top of the boiler at each heating element. If you read voltage at
any of the elements, then the element relay for that element is stuck on and
needs to be replaced.
(2)Check the fuse.
a) Remove the fuse located inside the boiler. Check it for continuity. Replace
with a new fuse of the correct type if necessary.
b) Otherwise replace the existing fuse.
(3)Check that there is 24 volt AC power on the secondary side of the transformer.
This is where the two red wires are connected to the transformer. There must be
24 volt AC power on the secondary side of the transformer for the boiler to
operate. If there is no power the transformer needs to be replaced. When there
is 24 volt power to the board the “Power On” light on the board should be on.
(4)With the thermostat wires still disconnected from step (1)b), connect a jumper
wire from terminal T1 to terminal T2. The “Thermostat On” light should now
be on.
a) This should energize the relay to the right of the control board, you should
hear a click. If not check that there is 24 volt AC power on the two relay
terminals with purple wires.
b) If there is no power at the relay, the control board needs to be replaced.
c) If there is power, but the relay is not turning on, replace the relay.
(5)When the relay is energized, it will supply 120 volt power for running the pump,
and activate the control board.
a) There should now be 120 volt AC power to the terminals labeled PL and PN.
b) If there is no power, replace the relay.
17

(6)With the circuit board now activated, the power relays should turn on one at a
time. If they have not started to come on as yet, temporarily turn up the
temperature on the aquastat to the maximum setting, it should be returned to
the normal setting when you are finished troubleshooting. The power relays for
controlling the elements should now start to turn on. As each relay turns on,
one “element relay indicator” light on the control board should come on as well.
a) If the element relay indicator lights do not come on, disconnect the
temperature sensor by pulling out the connector at the control board (the
one with the two gray wires).
b) If the lights now come on the temperature sensor needs to be replaced. If
they still do not come on, short the two gray wires at the pump relay. If they
come on then the pump relay needs to be replaced.
c) If the still do not come on then the control board needs to be replaced.
d) If the element relay indicator lights come on, but the power relays do not
come on then the high limit control may be preventing them from coming
on. This may be due to a faulty component, or may be an actual temperature
condition. A faulty high limit control will prevent the “hi limit indicator”
light from coming on.
(7)Temporarily (no more than one second) place a jumper wire across the two
terminals on the high limit control.
a) If the relays energize, replace the high limit control.
(8)If all the relays energize and there is no heat, then check for power to each of
the heating elements.
a) With all the relays energized, check that there is power to each of the
elements with a volt meter. If there is no voltage reading, replace the relay
18

connected to that element.
b) If there is power to the elements, but no heat, then with the all the power
disconnected to the boiler, check the resistance of each element with an ohm
meter, and replace any elements, as necessary.
If you have gone through the above steps, and the boiler is still not working, please
contact us for assistance.
Concept Manufacturing Inc.
Box 23008 RPO McGillivray
Winnipeg, Manitoba, Canada
R3T 5S3
Phone: 204-284-9111
Fax: 204-284-9229
Toll Free: 800-465-4114
E-mail info@conceptmfginc.com
19
This manual suits for next models
7
Table of contents
Popular Boiler manuals by other brands

DeDietrich
DeDietrich WHE 2.24 user guide

Trianco
Trianco Greenflame Eco Installation, Operation And Service

Fondital
Fondital LINE Tech Installation, use and maintenance

REMEHA
REMEHA Quinta Pro 115 Installation, user and service manual

Fröling
Fröling PE1e installation instructions

VST
VST VRB-110 installation manual

UTICA BOILERS
UTICA BOILERS UB95M-200 installation manual

Ideal Heating
Ideal Heating EVOMAX 2 Series Product & Flue Guide

Gorenje
Gorenje GBFU 50-150EDD/V9 manual

IBC
IBC SL 40-399 G3 quick start guide

Beretta
Beretta JUNIOR GREEN C.S.I. Series installer and user manual

Sime
Sime MIA-30 User, installation and servicing instructions