SGM LEKTRA VLW60T Guide

VLW60T
Manual display unit and conguration for MODBUS level meters.
technical documentation ENG Rev. A

Page 2 of 24 www.sgm-lektra.com
VLW60T - index
INDEX
1-WARRANTY
2-PRODUCT
3-TECHNICAL SPECIFICATIONS
4-DIMENSIONS
5-INSTALLATION
6-ELECTRICAL CONNECTIONS
7-DISPLAY
8-CONFIGURATIONS
9-TESTING/QUALITY CERTIFICATE
page. 3
page. 4
page. 5
page. 6
page. 7
page. 9
page. 13
page. 14
page. 24

Page 3 of 24
www.sgm-lektra.eu
Products supplied by SGM LEKTRA are guaranteed for a period of 12 (twelve) months from delivery date
according to the conditions specied in our sale conditions document.
SGM LEKTRA can choose to repair or replace the Product.
If the Product is repaired it will maintain the original warranty terms, whereas if the Product is replaced it will have
12 (twelve) months of warranty. The warranty will be null if the Client modies, repairs or uses the Products for
other purposes than the normal conditions foreseen by instructions or Contract.
In no circumstances shall SGM LEKTRA be liable for direct, indirect or consequential or other loss or damage
whether caused by negligence on the part of the company or its employees or otherwise howsoever arising out of
defective goods.
1-WARRANTY
VLW60T - warranty

Page 4 of 24 www.sgm-lektra.com
VLW60T - product
2- PRODUCT
2.1 IDENTIFICATION
Each instrument has an adhesive identication plate on which the main instrument data are reported.
The following image describes the information and data on the plate.
2
Model: VLW60T
Input power: 24 Vdc ±20%
Max: 400mA @ 24Vdc,Class2
Serial number: MA0111803398
1. Model
2. Power supply
3. Serial number
12 3 4
5
1. Ethernet
2. USB Host
3. COM1 RS-232, RS-485 2W/4W
COM3 RS-485 2W
4. Power Connector - Morsetto estraibile
5. Skintop M20x1.5
1
2
3
VERSION “A” VERSION “B”

Page 5 of 24
www.sgm-lektra.eu
3-TECHNICAL FEATURES
Display
4.3 “TFT colour resistive touch LCD, 480 x 272 resolution, LED backlight (Life Time> 30000h)
Digital ports
COM Ports: COM1 RS485 (A, B)
RTC Battery
Integrated
Power supply
Version “A” 24Vdc ±20%
Version “B” 85-230Vac (50/60Hz) / 24Vdc/ac
Consumption
Max 15W
Casing material
Version “A” Plastic
Version “B” ABS - Polycarbonate
Dimensions l x h x d (mm)
Version “A” 128x102x32
Version “B” 183.5x250x126
Recess dimensions (mm)
119x93
Assembly
Version “A” panel-type
Version “B” wall mounted, on pole or on DIN bar, with ABS enclosure and clear cover
Front protection
Version “A” IP65 / NEMA4
Version “B” IP66
Storage temperature
-20°÷60°C
Operating temperature
0÷50°C
Relative humidity
10÷90% (senza condensa)
Certied
CE
VLW60T - technical features

Page 6 of 24 www.sgm-lektra.com
VLW60T - dimensions
4-DIMENSIONS
4.1 MECHANICAL DIMENSIONS VERSION “A”
102mm
128mm
92mm
118mm
32mm
126mm 183.5mm
250mm
4.2 MECHANICAL DIMENSIONS VERSION “B”

Page 7 of 24
www.sgm-lektra.eu
VLW60T - installation
5.1 ASSEMBLY OF PANEL FRONT VERSION “A”
Place the instrument in the prepared slot (119x93mm) and fasten the xing supports.
(tightening torque: 0.3÷0.45 Nm to guarantee the seal of the gasket without deforming the panel).
5-INSTALLATION

Page 8 of 24 www.sgm-lektra.com
VLW60T - installation
5.2 WALL MOUNTING OR ON DIN BAR VERSION “B”
• Installation must only be performed by qualied personnel and in compliance with current regulations.
• Install the unit in an environment compatible with the physical characteristics and construction materials of the
enclosure; for outdoor installations, protect the unit from rain and sun with a protective roof.
• Incorrect use of the device could cause serious damage to persons, the product and the equipment connected to it.
125mm
183.5mm
35mm
149mm

Page 9 of 24
www.sgm-lektra.eu
VLW60T - electrical connections
6.1 ELECTRICAL CONNECTIONS VERSION “A” (FRONT PANEL ASSEMBLY)
MODBUS PORT CONNECTION TO THE METER PROBES/KTU5/MTU/PTU/RPL75
The MODBUS connection for connection to the probes must be made to the COM1 [RS485] with 2 wires:
• Pin 1 > B
• Pin 2 > A
6-ELECTRICAL CONNECTIONS
24Vdc
0V
SCH
1 2 34
5678 9
6.2 POWER SUPPLY VOLTAGE CONNECTION 24VDC
The supply voltage must be connected to the removable terminal.
Ground
0V
+24Vdc
Power supply unit 24Vdc – min. 500mA
METER / MTU / RPL75
COM1 [RS485] PTU5x
KTU5
PIN 1 BLUE
PIN 2 GREEN
24Vdc BLACK
0V RED
MAX 5
SENSORS

Page 10 of 24 www.sgm-lektra.com
VLW60T - electrical connections
6.3 CONNECTION TERMINALS VERSION “B”
1) Separate the motor or power control cables from the VLW60T connection cables
2) Remove the caps from the cable glands and open the cover by loosening the appropriate screws.
3) Insert the cables into the transmitter through the cable glands.
4) Close the cover and tighten the cable glands.
6.4 INFILTRATIONS OF HUMIDITY
To avoid moisture inltration inside the enclosure, the following are recommended:
- For the electrical connections use a cable with an external diameter of 6÷12mm and fully tighten the M20 cable gland.
- Close the lid tightly.
- Position the cable in such a way as to form a downward curve in the output of the M20 cable gland; in this way
condensation and/or rainwater will tend to drip from the bottom of the curve.

Page 11 of 24
www.sgm-lektra.eu
VLW60T - electrical connections
6.5 ELECTRICAL CONNECTIONS VERSION B (WALL MOUNT)
Connect the ultrasonic level transmitters, as shown in the following diagram.
METER / MTU / RPL75 PTU5xKTU5
24Vdc RED
GND BLACK
A GREEN
B BLUE

Page 12 of 24 www.sgm-lektra.com
VLW60T - electrical connections
6.6 ELECTRICAL CONNECTIONS VERSION B MAX 5 SENSORS (WALL MOUNT)
Connect the ultrasonic level transmitters, as shown in the following diagram.
METER / MTU / RPL75
PTU5x
KTU5
24Vdc RED
GND BLACK
A GREEN
B BLUE
MAX 5
SENSORS

Page 13 of 24
www.sgm-lektra.eu
VLW60T - display
7.2 LEVELS DISPLAY
VLW60T constantly scans the levels of each individual sensor and automatically updates the probe display pages
every 20 seconds.
7-DISPLAY
By pressing the up or down arrow keys, it is possible to select the next or previous sensor without waiting for the
automatic scroll.
The status display of the RL1 and RL2 relays is only active when the page displays the measurements transmitted
by METER level transmitters (4 wires), KTU5, MTU5 and RPL75.
Press the INFO key to open the system info pop-up window.
7.1 LEGEND OF KEYS
ARROW UP ARROW DOWN ARROW LEFT
SETUP INFO ENTER

Page 14 of 24 www.sgm-lektra.com
By pressing the SETUP key it is possible to access the congurations with 2 authorisation levels:
User USER – password 12345; authorisation to settings only in the “QUICK SETTINGS” menu of the level transmitters.
User SUPERVISOR – password 12345678; authorisation to the settings of the system parameters, in the order
“ENABLE SYSTEM” and “DISPLAY”, and of the “ADVANCED SETTINGS” of the level transmitters.
VLW60T - congurations
8-CONFIGURATIONS
Password entry:
Press on ▼ to select the user Pressing the “password” box opens the input keypad. Enter the password and press
“Enter” to conrm.
N.B. - Entering an incorrect password activates the protection, hiding all the access keys to the system programming
and level transmitters.
8.1 SETUP
8.2 SENSOR SETTINGS
Press the “SENSOR1/2/3/4/5” key to access the level transmitter conguration with UID 1, UID 2, UID 3, UID4 or
UID5 address.
The “ENABLE SENSOR” and “DISPLAY” keys can only be accessed by accessing the programming as a user
SUPERVISOR.

Page 15 of 24
www.sgm-lektra.eu
VLW60T - congurations
From this page it is possible to access the QUICK SETTINGS or the ADVANCED SETTINGS
(only SUPERVISOR user)
8.2.1 SENSOR 1/2/3/4/5
8.2.2 QUICK SETTINGS
Press the “QUICK SETTINGS” key to access the quick conguration of the previously selected level transmitter.
On the “QUICK SETTINGS” page it is possible to program the following parameters:
• DISTANCE 4mA - Pressing on the distance value opens the keypad to enter the new 4mA distance value;
enter the new value and press “Enter” to conrm.
• DISTANCE 20mA - Pressing on the distance value opens the keypad to enter the new 20mA distance value;
enter the new value and press “Enter” to conrm.
• PRODUCT - Press ▼ to select the product type.
• FILTER - Pressing on the lter value opens the keypad to enter the new value; enter the new value and press
“Enter” to conrm.
• BLIND ZONE - Pressing the value opens the keypad to enter the new blind zone value; enter the new value
and press “Enter” to conrm.
• RL1 THRESHOLD (active only with level transmitters (METER, KTU, MTU and RPL75) - Pressing the value
opens the keypad to enter the new threshold value (maximum level) of RL1; enter the new value and press
“Enter” to conrm.
• RL2 THRESHOLD (active only with level transmitters (METER, KTU, MTU and RPL75) - Pressing the value
opens the keypad to enter the new threshold value (minimum level) of RL2; enter the new value and press on
“Enter” to conrm.
Pressing on the left arrow returns to the previous page.

Page 16 of 24 www.sgm-lektra.com
VLW60T - congurations
8.2.3 ADVANCED SETTINGS
Press the “ADVANCED SETTINGS” key to access the advanced conguration of the previously selected level
transmitter.
On the “SETTINGS” page it is possible to program the following parameters:
• DISTANCE 4mA - Pressing on the distance value opens the keypad to enter the new 4mA distance value;
enter the new value and press “Enter” to conrm.
• DISTANCE 20mA - Pressing on the distance value opens the keypad to enter the new 20mA distance value;
enter the new value and press “Enter” to conrm.
• PRODUCT - Press ▼ to select the product type.
• FILTER - Pressing on the lter value opens the keypad to enter the new value; enter the new value and press
“Enter” to conrm.
• BLIND ZONE - Pressing the value opens the keypad to enter the new blind zone value; enter the new value
and press “Enter” to conrm.
• RELAY (active only with level transmitters (METER, KTU, MTU and RPL75) - Pressing the value opens the
keypad to enter the new threshold value (maximum level) of RL1; enter the new value and press “Enter” o conrm.
Pressing the left arrow will return to the previous page.

Page 17 of 24
www.sgm-lektra.eu
VLW60T - congurations
8.2.3.1 RL1/RL2 THRESHOLD
PRESS THE “RL1 THRESHOLD” or ”RL2 THRESHOLD” key.
On the “RL1 THRESHOLD” page it is possible to program the following parameters:
• VALUE - Pressing the value opens the keypad to enter the new value in terms of distance in mm from the sensor;
enter the new value and press “Enter” to conrm.
• MIN/MAX - Press ▼ to select the relay operation mode: maximum or minimum.
• DELAY - Pressing the value opens the keypad to enter the new value for the relay activation delay,
from 0 to 99 sec; enter the new value and press “Enter” to conrm.
• SAFETY - Press ▼ to select YES or NO for the relay safe alarm mode; with the alarm in safety (select SI/YES)
there is then a “closed” contact with relay energised in normal (non-alarm) conditions, and the contact switches
to open in the following cases:
- presence of alarm condition (example exceeding MAX).
- no voltage.
• ENABLE/DISABLE - Press ▼ to select ENABLE or DISABLE to activate or deactivate the relay threshold function.
Pressing the left arrow will return to the previous page.

Page 18 of 24 www.sgm-lektra.com
VLW60T - congurations
8.2.3.2 RL1 PUMPS
On the “RL1 PUMPS” page it is possible to program the following parameters:
• UPPER THRESHOLD - Pressing the value opens the keypad to enter the new value in terms of distance in mm
from the sensor; enter the new value and press “Enter” to conrm.
• LOWER THRESHOLD - Pressing the value opens the keypad to enter the new value in terms of distance in mm
from the sensor; enter the new value and press “Enter” to conrm.
• DELAY - Pressing the value opens the keypad to enter the new value for the relay activation delay,
from 0 to 99 sec; enter the new value and press “Enter” to conrm.
• MODE - Press ▼ to select the pump control operating mode:
FILLING or EMPTYING.
• ENABLE/DISABLE - Press ▼ to select ENABLE or DISABLE to activate or deactivate the pump control
function of RL1.
Pressing the left arrow will return to the previous page.
8.2.4 DIAGNOSTICS
Press the “DIAGNOSTICS” key to access the previously selected level transmitter menu.
On the “DIAGNOSTICS” page it is possible to program the following parameters:
• MEASUREMENT STATUS - It displays the system gain level.
• GAIN LOCK - It is possible to set a gain value (from 1 to 255) and, consequently, to deactivate the automatic gain
control. Entering the value 000 restores operation of the automatic gain control. Pressing on the value opens the
keypad to enter the new value; enter the new value and press “Enter” to conrm.
• MAX GAIN THRESHOLD - It is possible to change the maximum gain value of the received echo signal.
If the gain reaches this value, the “GAIN” error code is activated. Pressing the value opens the keypad to enter
the new value; enter the new value and press “Enter” to conrm.

Page 19 of 24
www.sgm-lektra.eu
VLW60T - congurations
8.2.5 SERVICE
Press the “SERVICE” key to access the previously selected level transmitter menu.
8.2.5.1 SAFETY
It is possible to choose an analog output condition during diagnostic errors:
• “21.5 mA” forces the current output to 21.5mA
• “3.85 mA” forces the current output to 3.85mA
• “HOLD LAST VALUE” keeps the output at the last valid value.
8.2.5.2 SET UID
In this parameter it is possible to modify the UID address for data communication in a MODBUS RTU network
(it is necessary to switch the ultrasonic transmitter o and back on to make the change operational);
it is advisable to perform this operation with only one transmitter connected at a time.
8.2.5.3 FREQUENCY
It is possible to view the sensor’s output frequency.
8.2.5.4 WINDOW
The increment value (expressed in cm), step by step, of the window width during the echo signal search phase is set.
8.2.5.5 ENABLE SENSOR
Press the “ENABLE SENSOR” key to access the number of connected level transmitters.
Pressing on 1, 2, 3, 4 or 5 sets the number of ultrasonic level transmitters connected to VLW60T.
The VLW60T automatically activates the measurement display and sensor conguration pages.

Page 20 of 24 www.sgm-lektra.com
VLW60T - congurations
8.2.5.6 DISPLAYING
Press the “DISPLAYING” key to access the measurement setting to be displayed.
On the “DISPLAYING” page it is possible to set the following parameters:
• 1st VALUE – it is the rst box from the top, larger than the remaining ones, to display the main measurement of
all the sensors; press the ▼ key to select:
LEVEL mm / DISTANCE / LEVEL% / 4 ÷ 20Ma / TEMPERATURE (active only for ultrasonic sensors).
• 2nd VALUE - this is the second box from the top to display the 2nd selected size of all the sensors;
by pressing the ▼ key it is possible to select:
NOT ACTIVE / LEVEL mm / DISTANCE / LEVEL% / 4 ÷ 20mA
TEMPERATURE (active only for ultrasonic sensors)
• 3rd VALUE – it is the third box from the top to display the 3rd selected size of all the sensors;
by pressing the ▼ key it is possible to select:
NOT ACTIVE / LEVEL mm / DISTANCE / LEVEL% / 4 ÷ 20mA
TEMPERATURE (active only for ultrasonic sensors)
• 4th VALUE – it is the fourth box from the top to display the 4th selected size of all the sensors;
by pressing the ▼ key it is possible to select:
NOT ACTIVE / LEVEL mm / DISTANCE / LEVEL% / 4 ÷ 20mA
TEMPERATURE (active only for ultrasonic sensors)
• 5th VALUE – this is the fth box from the top to display the 5th selected size of all the sensors;
by pressing the ▼ key it is possible to select:
NOT ACTIVE / LEVEL mm / DISTANCE / LEVEL% / 4 ÷ 20mA
TEMPERATURE (active only for ultrasonic sensors)